Plan Review Notes
Plan Review Notes For Permit 08070618
Permit Number 08070618
Review Stop M
Sequence Number 1
Notes
Date Text
2008-08-11 13:28:02REVIEW #: 2ND
 ACTION: DENIED
  
 REVIEWED UNDER THE FOLLOWING CODES:
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
 NOTE: THESE COMMENTS ARE BASED AND NUMBERED ON COMMENTS
 UNDER EXPIRED PERMIT #07080639 DATED 10/31/07.
 ADDITIONAL COMMENTS ARE POSSIBLE. THIS IS A NEW PERMIT
 APPLICATION AND WILL BE REVIEWED ACCORDINGLY.
  
 1. THE JOB DESCRIPTION ON THE PERMIT APPLICATION IS
 STILL DESCRIBING THIS WORK AS TOWNHOUSES. BY DEFINITION
 IN FBCB SECTION 202, THESE ARE NOT TOWNHOUSES AND WILL
 CONTINUE TO BE REVIEWED UNDER THE FBC AS R-2
 MULTI-FAMILY DWELLINGS.
  
 2. ENERGY CODE COMPLIANCE FORMS HAVE BEEN SUBMITTED.
 HOWEVER, THE BUILDING ENVELOPE COMPONENTS SHOWN ON THE
 COMPLIANCE FORM BARE NO RESEMBLANCE TO THE COMPONENTS
 SHOWN ON THE ARCHITECTURAL PLANS. PLEASE SEE BUILDING
 PLAN REVIEW FOR MORE SPECIFIC INFORMATION. ALSO, A
 COOLING AND HEATING LOAD CALCULATION SHALL BE PERFORMED
 ON THE BUILDING AND SHALL BE ATTACHED TO THE FORM 600
 SUBMITTED WHEN APPLICATION IS MADE FOR A BUILDING
 PERMIT IN ACCORDANCE WITH FBCB 13-607.1.ABC.1. COOLING
 EQUIPMENT CAPACITY SHALL BE DETERMINED IN ACCORDANCE
 WITH 13-607.1.ABC.1.1.
  
 3. OK
  
 4. OK
  
 5. OK
  
 6. PAGE M-5 SHOWS A PRESCRIPTIVE TIE-DOWN METHOD PER
 FBCB 301.13.1. PLEASE NOTE THAT 301.13.1 IS ONLY
 APPLICABLE TO R-3 OCCUPANCIES. AS STATED IN COMMENT #1
 ABOVE, THESE BUILDINGS ARE CLASSIFIED AS R-2
 OCCUPANCIES. THEREFORE, AN ENGINEERED DESIGN OF
 ATTACHMENT WITH SUPPORTING WIND LOAD CALCULATIONS IS
 REQUIRED IN ACCORDANCE WITH FBCM 301.13. PLEASE PROVIDE
 THE REQUESTED INFORMATION AND RESUBMIT.
  
 7. PAGE M-1 THROUGH M-4 CALL FOR 1 INCH CPVC PIPE TO BE
 USED FOR CONDENSATE. SUPPORTING DOCUMENTATION WAS
 REQUESTED SHOWING THAT THE SPECIFIED SIZE OF CPVC WOULD
 MEET THE 25/50 RATING WHEN TESTED IN ACCORDANCE WITH
 ASTM E84 PER FBCM 602.2.1. NO SUCH DOCUMENTATION WAS
 PROVIDED. THE ONLINE DOCUMENTATION WHICH WAS RESEARCHED
 DURING THIS REVIEW INDICATES THAT ONLY 1/2 INCH AND 3/4
 INCH CPVC HAS MET THE 25/50 REQUIREMENT WHEN NOT FILLED
 WITH WATER. CONDENSATE DRAIN PIPES ARE NOT FILLED WITH
 WATER AND THEREFORE 1 INCH CPVC IS NOT ACCEPTABLE IN
 THE PLENUM SPACES PER FBCM 602.2.1. PLEASE BE REMINDED
 THAT 3/4 INCH CPVC DOES NOT MEET THE INTERNAL DIAMETER
 REQUIREMENTS OF FBCM 307.2.2. PLEASE SHOW A CONDENSATE
 DRAIN MATERIAL WITHIN THE PLENUM SPACE WHICH MEETS THE
 REQUIREMENTS OF BOTH CODE SECTIONS REFERENCED ABOVE.
  
 8. OK
  
 NEW COMMENTS:
  
 9. PAGES M-1 THROUGH M-4 SHOW PLAN NOTE #3 WHICH CALLS
 FOR BATHROOM AND DRYER EXHAUST TO TERMINATE ON THE ROOF
 AT A GOOSENECK WITH BACK DRAFT DAMPER AND BIRD SCREEN.
 DRYER EXHAUST DUCTS FOR CLOTHES DRYERS SHALL TERMINATE
 ON THE OUTSIDE OF THE BUILDING AND SHALL BE EQUIPPED
 WITH A BACKDRAFT DAMPER. SCREENS SHALL NOT BE INSTALLED
 AT THE DUCT TERMINATION IN ACCORDANCE WITH FBCM 504.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: