Plan Review Notes
Plan Review Notes For Permit 08070618
Permit Number 08070618
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-08-21 13:17:25***DENIED***
  
 MOST OF THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW
 UNDER THE NOW EXPIRED PERMIT HAVE BEEN ADDRESSED.
 PLEASE SEE THE FOLLOWING COMMENT FROM THE LAST REVIEW
 AND NEW COMMENTS:
  
 1) ILLUSTRATE THE LOCATIONS OF NEW AND EXISTING FIRE
 HYDRANTS. PLEASE ILLUSTRATE ON C- SHEETS.
  
 2) NEW COMMENT- EMERGENCY VEHICLE ACCESS AND WATER
 SUPPLY SHALL COMPLY WITH NFPA 1, 2003.
  
 3) NEW COMMENT- SMOKE ALARMS SHALL BE MINIMUM OF THREE
 (3) FEET FROM AC DIFFUSERS AND COMPLY WITH 101, SEC.
 9.6.2.10 SO THAT THE OPERATION OF ONE (1) SMOKE ALARM
 ACTIVATES ALL SMOKE ALARMS IN THE UNIT.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756