| Plan Review Notes For Permit 08070618 |
| Permit Number |
08070618 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-08-21 13:17:25 | ***DENIED*** | | | | | | MOST OF THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW | | | UNDER THE NOW EXPIRED PERMIT HAVE BEEN ADDRESSED. | | | PLEASE SEE THE FOLLOWING COMMENT FROM THE LAST REVIEW | | | AND NEW COMMENTS: | | | | | | 1) ILLUSTRATE THE LOCATIONS OF NEW AND EXISTING FIRE | | | HYDRANTS. PLEASE ILLUSTRATE ON C- SHEETS. | | | | | | 2) NEW COMMENT- EMERGENCY VEHICLE ACCESS AND WATER | | | SUPPLY SHALL COMPLY WITH NFPA 1, 2003. | | | | | | 3) NEW COMMENT- SMOKE ALARMS SHALL BE MINIMUM OF THREE | | | (3) FEET FROM AC DIFFUSERS AND COMPLY WITH 101, SEC. | | | 9.6.2.10 SO THAT THE OPERATION OF ONE (1) SMOKE ALARM | | | ACTIVATES ALL SMOKE ALARMS IN THE UNIT. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|