Plan Review Notes
Plan Review Notes For Permit 08070618
Permit Number 08070618
Review Stop E
Sequence Number 1
Notes
Date Text
2008-08-08 16:54:24 
 **DENIEDREVIEW**
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUSLY SUBMITTED
 *PLAN REVIEW * WHICH IS EXPIRED ARE STILL IN NEED OF
 ADDRESSING. PREVIOUS # WAS 07080639
 THERE ARE ALSO SOME NEW COMMENTS FROM CHANGES ON PLANS
 AND INFORMATION NOW SHOWN.
 THERE IS ALSO A NEW COMMENT
  
 1) NOTE: PLEASE ADJUST CODES ON PLANS FOR THE FBC AS
 PERMIT APPLICATION IS NOW MADE OVER ONE YEAR AFTER
 PREVIOUS *PLAN REVIEW ONLY* SOME CODES HAVE CHANGED.
 PLEASE LIST THE 2004 FBC W/2007 REVISIONS.
  
 2) PLEASE SEE THE PREVIOUS REVIEW WHICH REQUESTED ALL
 CIRCUITING TO BE SHOWN ON PLANS AND COORDINATED WITH
 THE PANEL SCHEDULES SUBMITTED. THE RESPONSE MENTIONS
 CIRCUITS ON PANEL SCHEDULES ARE SHOWN. THE CIRCUITS
 REQUIRED ON PLANS ARE STILL MISSING.
 THE CIRCUITS ON PANEL SCHEDULES ARE NOT COMPLETE FOR
 BEING SPECIFIC. PLEASE SEE THE 2005 AS THE CODE WAS
 REVISED TO STATE ALL CIRCUITS SHALL BE SPECIFIC TO
 ROOMS AND AREAS IN WHICH THEY FEED. AN EXAMPLE OF THIS
 IS THE PANEL SCHEDULE WHICH INDICATE CIRCUITS 13-20 AS
 *GENERAL LIGHTING* THE CODE WHICH WILL BE QUOTED BELOW
 STATES THIS IS NOT ACCEPTABLE.
  
 ***
 SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.
  
 **
 PLEASE REVISE PANEL SCHEDULES. THERE ARE SEVERAL ITEMS
 FOR CODE COMPLIANCE WHICH NEEDS TO BE REVIEWED FOR
 ITEMS SUCH AS DINING ROOMS/AREAS FOR COMPLIANCE PER
 210.52B1, 210.11C1, 220.53 ETC
  
 3) NOTE: PLEASE SEE MISSING LIGHTING REQUIRED IN AHU
 CLOSETS PER 210.70
  
 4) NOTE: PLEASE SEE SOME UNITS ARE STILL MISSING
 REQUIRED RECEPTACLES PER 210.52.
 PLEASE SEE UNIT A WHICH IS ON SHEET E-1 ON THE LEFT
 HAND SIDE. PLEASE SEE THE WALL BETWEEN THE KITCHEN AND
 LIVING ROOM. MANY OF THE LOCATIONS WERE REVISED HOWEVER
 NOT ALL.
 PLEASE ALSO SEE WALL SPACE IN KITCHENS IN UNITS B, C AS
 THERE ARE WALL SPACES GREATER THAN 2 FT.
  
 5) NOTE: PLEASE SEE MISSING LIGHTING CONTROLS REQUIRED
 WHEN ENTERING INTO THE UNITS SUCH AS UNIT *A*. PLEASE
 SEE 210.70 FOR REQUIRED HALLWAY LIGHTING AND CONTROLS
 FOR INGRESS AND EGRESS AND ENTRANCES.
 ** ( THIS NOTE IS NOT FOR OUTSIDE WHEN AUTOMATIC
 OUTSIDE LIGHTING IS BEING PROVIDED.
  
 6) NOTE: PLEASE VERIFY THE AIC RATINGS ON PLANS. PLANS
 STATE 30,000 AIC RATING FOR ALL EQUIPMENT. THIS MAY
 WANT TO BE CONFIRMED. IF PLANS INDICATE 30K FOR ALL
 THEN THIS WILL BE REQUIRED.
 THE LET THROUGH CURRENT ON THE LOAD SIDE OF MAINS
 SHOULD BE VERIFIED WITH THE MANUFACTURE ETC
 110.9.
 RESPONSE CONTAINS QUESTION MARKS.
  
 7) NOTE: PLEASE KNOW NOTES HAVE BEEN ROUTED TO
 *ADDRESSING* AS ADDRESSING OF THE BUILDINGS IS NEEDED.
 THE PERMIT APPLICATION STATES *ELEVEN NEW TOWNHOUSES *
 HOWEVER BY DEFINITION THESE ARE NOT FEE SIMPLE
 TOWNHOUSE UNITS. THESE ARE SHOWN AS MULTI-FAMILY
 BUILDINGS. EACH BUILDING WOULD NEED A SEPARATE
 ADDRESS.
 PLEASE KNOW ONCE THE FINAL ADDRESSES FOR EACH ARE
 DETERMINED PLEASE REVISE TITLE BLOCKS ACCORDINGLY.
 FAC 61G16-1.004, 61G15-23.002, FBC 106.5
  
 8) NOTE: PLEASE SEE NEC 90.8. THE SERVICE AS SHOWN IS A
 400AMP SERVICE WITH A LOAD OF 399.6 AMPS. THIS DOES NOT
 ALLOW FOR ANY FUTURE LOADS NOT EVEN FOR ONE CIRCUIT AS
 SHOWN.
 THE LOAD CALCULATIONS FOR BUILDING *A* STATES A TOTAL
 OF FOUR (4) UNITS HOWEVER BASED ON THE PLANS AND THE
 LOAD CALCULATIONS WHICH INDICATE 5 UNITS PLEASE
 REVISE.
 PLEASE REVISE SERVICE FOR BUILDING *B*.
 NEC 220, 240.4,310.16 ETC
  
 ** AS SOME ITEMS ARE NOT SHOWN, FINAL DETERMINATIONF
 FOR CODE COMPLIANCE CAN NOT BE MADE AT THIS TIME.
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]