| 2008-08-08 16:54:24 | |
| | **DENIEDREVIEW** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUSLY SUBMITTED |
| | *PLAN REVIEW * WHICH IS EXPIRED ARE STILL IN NEED OF |
| | ADDRESSING. PREVIOUS # WAS 07080639 |
| | THERE ARE ALSO SOME NEW COMMENTS FROM CHANGES ON PLANS |
| | AND INFORMATION NOW SHOWN. |
| | THERE IS ALSO A NEW COMMENT |
| | |
| | 1) NOTE: PLEASE ADJUST CODES ON PLANS FOR THE FBC AS |
| | PERMIT APPLICATION IS NOW MADE OVER ONE YEAR AFTER |
| | PREVIOUS *PLAN REVIEW ONLY* SOME CODES HAVE CHANGED. |
| | PLEASE LIST THE 2004 FBC W/2007 REVISIONS. |
| | |
| | 2) PLEASE SEE THE PREVIOUS REVIEW WHICH REQUESTED ALL |
| | CIRCUITING TO BE SHOWN ON PLANS AND COORDINATED WITH |
| | THE PANEL SCHEDULES SUBMITTED. THE RESPONSE MENTIONS |
| | CIRCUITS ON PANEL SCHEDULES ARE SHOWN. THE CIRCUITS |
| | REQUIRED ON PLANS ARE STILL MISSING. |
| | THE CIRCUITS ON PANEL SCHEDULES ARE NOT COMPLETE FOR |
| | BEING SPECIFIC. PLEASE SEE THE 2005 AS THE CODE WAS |
| | REVISED TO STATE ALL CIRCUITS SHALL BE SPECIFIC TO |
| | ROOMS AND AREAS IN WHICH THEY FEED. AN EXAMPLE OF THIS |
| | IS THE PANEL SCHEDULE WHICH INDICATE CIRCUITS 13-20 AS |
| | *GENERAL LIGHTING* THE CODE WHICH WILL BE QUOTED BELOW |
| | STATES THIS IS NOT ACCEPTABLE. |
| | |
| | *** |
| | SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION. |
| | |
| | ** |
| | PLEASE REVISE PANEL SCHEDULES. THERE ARE SEVERAL ITEMS |
| | FOR CODE COMPLIANCE WHICH NEEDS TO BE REVIEWED FOR |
| | ITEMS SUCH AS DINING ROOMS/AREAS FOR COMPLIANCE PER |
| | 210.52B1, 210.11C1, 220.53 ETC |
| | |
| | 3) NOTE: PLEASE SEE MISSING LIGHTING REQUIRED IN AHU |
| | CLOSETS PER 210.70 |
| | |
| | 4) NOTE: PLEASE SEE SOME UNITS ARE STILL MISSING |
| | REQUIRED RECEPTACLES PER 210.52. |
| | PLEASE SEE UNIT A WHICH IS ON SHEET E-1 ON THE LEFT |
| | HAND SIDE. PLEASE SEE THE WALL BETWEEN THE KITCHEN AND |
| | LIVING ROOM. MANY OF THE LOCATIONS WERE REVISED HOWEVER |
| | NOT ALL. |
| | PLEASE ALSO SEE WALL SPACE IN KITCHENS IN UNITS B, C AS |
| | THERE ARE WALL SPACES GREATER THAN 2 FT. |
| | |
| | 5) NOTE: PLEASE SEE MISSING LIGHTING CONTROLS REQUIRED |
| | WHEN ENTERING INTO THE UNITS SUCH AS UNIT *A*. PLEASE |
| | SEE 210.70 FOR REQUIRED HALLWAY LIGHTING AND CONTROLS |
| | FOR INGRESS AND EGRESS AND ENTRANCES. |
| | ** ( THIS NOTE IS NOT FOR OUTSIDE WHEN AUTOMATIC |
| | OUTSIDE LIGHTING IS BEING PROVIDED. |
| | |
| | 6) NOTE: PLEASE VERIFY THE AIC RATINGS ON PLANS. PLANS |
| | STATE 30,000 AIC RATING FOR ALL EQUIPMENT. THIS MAY |
| | WANT TO BE CONFIRMED. IF PLANS INDICATE 30K FOR ALL |
| | THEN THIS WILL BE REQUIRED. |
| | THE LET THROUGH CURRENT ON THE LOAD SIDE OF MAINS |
| | SHOULD BE VERIFIED WITH THE MANUFACTURE ETC |
| | 110.9. |
| | RESPONSE CONTAINS QUESTION MARKS. |
| | |
| | 7) NOTE: PLEASE KNOW NOTES HAVE BEEN ROUTED TO |
| | *ADDRESSING* AS ADDRESSING OF THE BUILDINGS IS NEEDED. |
| | THE PERMIT APPLICATION STATES *ELEVEN NEW TOWNHOUSES * |
| | HOWEVER BY DEFINITION THESE ARE NOT FEE SIMPLE |
| | TOWNHOUSE UNITS. THESE ARE SHOWN AS MULTI-FAMILY |
| | BUILDINGS. EACH BUILDING WOULD NEED A SEPARATE |
| | ADDRESS. |
| | PLEASE KNOW ONCE THE FINAL ADDRESSES FOR EACH ARE |
| | DETERMINED PLEASE REVISE TITLE BLOCKS ACCORDINGLY. |
| | FAC 61G16-1.004, 61G15-23.002, FBC 106.5 |
| | |
| | 8) NOTE: PLEASE SEE NEC 90.8. THE SERVICE AS SHOWN IS A |
| | 400AMP SERVICE WITH A LOAD OF 399.6 AMPS. THIS DOES NOT |
| | ALLOW FOR ANY FUTURE LOADS NOT EVEN FOR ONE CIRCUIT AS |
| | SHOWN. |
| | THE LOAD CALCULATIONS FOR BUILDING *A* STATES A TOTAL |
| | OF FOUR (4) UNITS HOWEVER BASED ON THE PLANS AND THE |
| | LOAD CALCULATIONS WHICH INDICATE 5 UNITS PLEASE |
| | REVISE. |
| | PLEASE REVISE SERVICE FOR BUILDING *B*. |
| | NEC 220, 240.4,310.16 ETC |
| | |
| | ** AS SOME ITEMS ARE NOT SHOWN, FINAL DETERMINATIONF |
| | FOR CODE COMPLIANCE CAN NOT BE MADE AT THIS TIME. |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |