| Date |
Text |
| 2008-08-20 07:52:11 | 2ND REVIEW 8-18-08 |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 08070618 |
| | ADD: 605-609 PBL BLVD. |
| | CONT: D. STEPHENSON CONSTRUCTION |
| | TEL: (954)315-7020 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 / 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 2ND |
| | ACTION: DENIED |
| | |
| | ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL BE |
| | DESIGNED TO THE 2004 FLORIDA BUILDING CODE WITH THE |
| | 2007 REVISIONS. THE PERMIT APPLICATION STILL DESCRIBES |
| | THE PROJECT AS TOWNHOUSES. THESE ARE NOT TOWNHOUSES AND |
| | WILL BE REVIEWED AS R-2 MULTI-FAMILY DWELLINGS. |
| | 1) OK |
| | 2) OK |
| | 3) OK |
| | 4) OK |
| | 5) OK |
| | |
| | NOTED: SUBMIT THE BLUE RECEIT FOR THE IMPACT FEES FROM |
| | PALM BEACH COUNTY. |
| | 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | ******************************************************* |
| | ******************************************************* |
| | ****************** |
| | |
| | 7) NOTED: HOWEVER, THE REPORT MAKES REFERENCE TO FBC |
| | 2001. ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL |
| | BE DESIGNED TO THE 2004 FLORIDA BUILDING CODE. THE SOIL |
| | INVESTIGATION REPORT SHALL CONTAIN THE ORIGINAL RAISED |
| | SEAL OF THE ENGINEER RESPONSIBLE FOR THE REPORT. FAC |
| | 61G15-23.002. A PROFESSIONAL ENGINEER SHALL SIGN HIS |
| | NAME AND AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS, |
| | REPORTS, FINAL BID DOCUMENTS PROVIDED TO THE OWNER OR |
| | THE OWNERS REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED |
| | OR ISSUED BY SAID REGISTRANT AND BEING FILED FOR PUBLIC |
| | RECORD. THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED |
| | AS PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS IMMEDIATELY |
| | UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER. |
| | |
| | A) FBC 1802.2.1 QUESTIONABLE SOIL. WHERE THE BEARING |
| | CAPACITY OF THE SOIL IS NOT DEFINITELY KNOWN OR IS IN |
| | QUESTION, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE |
| | NECESSARY INVESTIGATION BE MADE. THE INVESTIGATION |
| | SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4 |
| | THROUGH 1802.6 OF THE FBC. THE INVESTIGATION SHALL BE |
| | CERTIFIED BY A GEOTECHNICAL REPORT FROM A DESIGN |
| | PROFESSIONAL PROPERLY LICENSED IN THE STATE OF |
| | FLORIDA. |
| | |
| | 8) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. NOTE: 713.13(2). IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6). |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 9) OK |
| | 10) OK |
| | 11) OK |
| | |
| | 12) FBC 2303.4.1 TRUSS CONSTRUCTION DOCUMENTS SHALL |
| | CONFORM TO THIS SECTION OF THE FBC AND SHALL BE |
| | PREPARED BY A REGISTERED DESIGN PROFESSIONAL AND |
| | SUBMITTED TO THE BUILDING OFFICIAL PRIOR TO |
| | INSTALLATION. |
| | |
| | 13) OK |
| | |
| | 14) NOTED: HOWEVER, SOME OF THE INFORMATION INDICATED |
| | ON THE FORMS FOR THE BUILDING ENVELOPE DOES NOT |
| | CORRESPOND WITH THE ARCHITECTURAL DRAWINGS. EXAMPLE, |
| | SLAB-ON-GRADE SHOWS R-13 INSULATION, ALL EXTERIOR WALLS |
| | ARE SHOWN AS CONCRETE, BUT WALL TYPES ?F? AND ?I? |
| | INDICATE 2?X6? STUD PARTITION. THE LEGEND NEEDS TO |
| | INDICATE THE TYPE OF STUDS ALONG WITH THE STUD SPACING |
| | AND THE THICKNESS OF THE EXTERIOR WALL SHEATHING. THE |
| | INSULATION FOR THE EXTERIOR WALLS IS SHOWN AS R-11 |
| | HOWEVER, THE LEGEND SHOWS IT AS ?? RIGID INSULATION. |
| | THE ENERGY CALCULATION FORMS NEED TO CORRESPOND WITH |
| | THE ARCHITECTURAL DRAWINGS. THERE IS NO CONCRETE ROOF |
| | DECK SHOWN ON THE PLANS. |
| | A) FL ENERGY EFFICIENCY CODE 400.ABCD. THE PERSON |
| | PREPARING THE COMPLIANCE CALCULATION SHALL CERTIFY THAT |
| | THE CALCULATION IS TRUE AND ACCURATE & DEMONSTRATES |
| | THAT THE BUILDING IS IN COMPLIANCE. SEE SUBCHAPTER 13-6 |
| | OF THE FBC. |
| | |
| | 15) OK |
| | 16) OK |
| | 17) OK |
| | |
| | **NO RESPONSE NOT ADDRESSED** |
| | NOTE: THE ABBREVIATION LEGEND ON SHEET SP - 1 IS NOT |
| | LEGIBLE. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |