Plan Review Notes
Plan Review Notes For Permit 08070618
Permit Number 08070618
Review Stop B
Sequence Number 1
Notes
Date Text
2008-08-20 07:52:112ND REVIEW 8-18-08
  
 BUILDING PLAN REVIEW
 PERMIT: 08070618
 ADD: 605-609 PBL BLVD.
 CONT: D. STEPHENSON CONSTRUCTION
 TEL: (954)315-7020
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 / 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
  
 ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL BE
 DESIGNED TO THE 2004 FLORIDA BUILDING CODE WITH THE
 2007 REVISIONS. THE PERMIT APPLICATION STILL DESCRIBES
 THE PROJECT AS TOWNHOUSES. THESE ARE NOT TOWNHOUSES AND
 WILL BE REVIEWED AS R-2 MULTI-FAMILY DWELLINGS.
 1) OK
 2) OK
 3) OK
 4) OK
 5) OK
  
 NOTED: SUBMIT THE BLUE RECEIT FOR THE IMPACT FEES FROM
 PALM BEACH COUNTY.
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 *******************************************************
 *******************************************************
 ******************
  
 7) NOTED: HOWEVER, THE REPORT MAKES REFERENCE TO FBC
 2001. ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL
 BE DESIGNED TO THE 2004 FLORIDA BUILDING CODE. THE SOIL
 INVESTIGATION REPORT SHALL CONTAIN THE ORIGINAL RAISED
 SEAL OF THE ENGINEER RESPONSIBLE FOR THE REPORT. FAC
 61G15-23.002. A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS,
 REPORTS, FINAL BID DOCUMENTS PROVIDED TO THE OWNER OR
 THE OWNERS REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED
 OR ISSUED BY SAID REGISTRANT AND BEING FILED FOR PUBLIC
 RECORD. THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED
 AS PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER.
  
 A) FBC 1802.2.1 QUESTIONABLE SOIL. WHERE THE BEARING
 CAPACITY OF THE SOIL IS NOT DEFINITELY KNOWN OR IS IN
 QUESTION, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. THE INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 OF THE FBC. THE INVESTIGATION SHALL BE
 CERTIFIED BY A GEOTECHNICAL REPORT FROM A DESIGN
 PROFESSIONAL PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 8) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2). IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6).
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 9) OK
 10) OK
 11) OK
  
 12) FBC 2303.4.1 TRUSS CONSTRUCTION DOCUMENTS SHALL
 CONFORM TO THIS SECTION OF THE FBC AND SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE BUILDING OFFICIAL PRIOR TO
 INSTALLATION.
  
 13) OK
  
 14) NOTED: HOWEVER, SOME OF THE INFORMATION INDICATED
 ON THE FORMS FOR THE BUILDING ENVELOPE DOES NOT
 CORRESPOND WITH THE ARCHITECTURAL DRAWINGS. EXAMPLE,
 SLAB-ON-GRADE SHOWS R-13 INSULATION, ALL EXTERIOR WALLS
 ARE SHOWN AS CONCRETE, BUT WALL TYPES ?F? AND ?I?
 INDICATE 2?X6? STUD PARTITION. THE LEGEND NEEDS TO
 INDICATE THE TYPE OF STUDS ALONG WITH THE STUD SPACING
 AND THE THICKNESS OF THE EXTERIOR WALL SHEATHING. THE
 INSULATION FOR THE EXTERIOR WALLS IS SHOWN AS R-11
 HOWEVER, THE LEGEND SHOWS IT AS ?? RIGID INSULATION.
 THE ENERGY CALCULATION FORMS NEED TO CORRESPOND WITH
 THE ARCHITECTURAL DRAWINGS. THERE IS NO CONCRETE ROOF
 DECK SHOWN ON THE PLANS.
 A) FL ENERGY EFFICIENCY CODE 400.ABCD. THE PERSON
 PREPARING THE COMPLIANCE CALCULATION SHALL CERTIFY THAT
 THE CALCULATION IS TRUE AND ACCURATE & DEMONSTRATES
 THAT THE BUILDING IS IN COMPLIANCE. SEE SUBCHAPTER 13-6
 OF THE FBC.
  
 15) OK
 16) OK
 17) OK
  
 **NO RESPONSE NOT ADDRESSED**
 NOTE: THE ABBREVIATION LEGEND ON SHEET SP - 1 IS NOT
 LEGIBLE.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  