| Plan Review Notes For Permit 08070612 |
| Permit Number |
08070612 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-07-25 11:01:38 | | | | | | | | | | PROVISO | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC CHAPTER 1 AS AMENDED AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | THIS PERMIT IS BEING ISSUED TO FACILITATE THE REPAIR OF | | | THIS RESIDENCE, THE PLANS HOWEVER ARE INCOMPLETE. | | | RESUBMIT A REVISION SHOWING ACTUAL ALARM LOCATIONS, | | | USING ACCEPTED SYMBOLS ACCEPTED AS STANDARD IN THE | | | INDUSTRY, PRIOR TO CALLING ELECTRICAL INSPECTION. THE | | | REVIEWED PLAN MUST BE ON THE JOB SITE AT TIME OF | | | INSPECTION. ALLOW AT LEAST ONE WEEK (PER TRADE) FOR | | | PLAN REVIEW. | | | | | | | | | 1} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN | | | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE | | | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS | | | DESIGNED. | | | | | | 2} PLANS ARE REQUIRED TO BE DRAFTSMAN QUALITY, DRAWN TO | | | A MINIMUM OF 1/8 INCH SCALE. PLANS ARE REQUIRED TO | | | CLEARLY INDICATE THE SCOPE OF WORK INTENDED IN THE | | | DESCRIPTION ON THE APPLICATION, AND SUITABLE FOR RECORD | | | RETENTION. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER | | | 106.1.3.FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|