2008-07-24 10:02:27PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) MECHANICAL PLAN M-1 SHOWS THE AIR HANDLER UNIT ON
 TOP OF THE ATTIC ACCESS, THE UNIT MUST BE SERVICEABLE
 PER 2004 FBC/R M1305.1.3. PLEASE CORRECT.
  
 2) MECHANICAL PLAN SECOND FLOOR SHOWS NO DUCT (FLEX)
 GOING TO THE 14X14 R/A GRILL NEAR THE STAIRWAY. PLEASE
 CORRECT PER 2004 FBC/R M1602.4 AND FBC 106.1.1.
  
 3) SHOW THE LOCATION OF THE A/C CONDENSER UNIT ON THE
 MECHANICAL PLAN AND STATE IF NEW OR EXISTING, PER 2004
 FBC 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;