| Plan Review Notes For Permit 08070608 |
| Permit Number |
08070608 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-07-24 10:02:27 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) MECHANICAL PLAN M-1 SHOWS THE AIR HANDLER UNIT ON | | | TOP OF THE ATTIC ACCESS, THE UNIT MUST BE SERVICEABLE | | | PER 2004 FBC/R M1305.1.3. PLEASE CORRECT. | | | | | | 2) MECHANICAL PLAN SECOND FLOOR SHOWS NO DUCT (FLEX) | | | GOING TO THE 14X14 R/A GRILL NEAR THE STAIRWAY. PLEASE | | | CORRECT PER 2004 FBC/R M1602.4 AND FBC 106.1.1. | | | | | | 3) SHOW THE LOCATION OF THE A/C CONDENSER UNIT ON THE | | | MECHANICAL PLAN AND STATE IF NEW OR EXISTING, PER 2004 | | | FBC 106.1.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|