Plan Review Notes
Plan Review Notes For Permit 08070599
Permit Number 08070599
Review Stop B
Sequence Number 1
Notes
Date Text
2008-07-21 17:06:15RESIDENTIAL (R3)REROOFING, BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- FLAT ROOF SYSTEM:
 A) CLEARLY SPECIFIED BASE SHEET FASTENING OPTION AS
 REQUIRED BY CITY POLICY FOR RE-ROOFING PERMITS TO
 VERIFY THE UPLIFT PRESSURES.SEE ATTACHED COPY OF CITY
 POLICY.
 *** NOTE: SELECTED FASTENING OPTION CAN'T NOT BE
 LIMITED BY GENERAL LIMITATION #9 BECAUSE IT DOESN'T
 ALLOW FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS.
  
 B) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING
 AT PERIMETER AND CORNERAREAS AS REQUIRED BY GENERAL
 LIMITATION #7. CALCULATIONSSHALL BE SIGNED AND
 SEALED BY ANY OF THEPROFESSIONALS LISTED IN GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA 06-0417.09
 SUBMITTED.
  
 2- CLEARLY SPECIFY HOW MUCH SQUARE FOOTAGE IS FOR PITCH
 ROOF AND HOW MUCH IS FOR FLAT ROOFTO PROPERLY UPDATE
 THE PERMIT VALUATION AS REQUIRED BY SEC. 108.3 CITY
 AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561) 805-6712