Notes
Date Text
2008-08-14 09:13:18PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) INFORMATION MISSING FROM TITLE BLOCK. ENGINEERS
 PRINTED NAME AND LICENSE NUMBER, AND THE ENGINEERING
 BUSINESS C. OF A. NUMBER.
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 2) THE JOB ADDRESS (325 GARDENIA ST.) MUST APPEAR IN
 THE TITLE BLOCK OF EACH PAGE OF THE PLANS, PER CITY WPB
 AMEND. 106.1.1.
  
 3) THE INFORMATION REGARDING THE VESDA PIPING SYSTEM
 MUST APPEAR ON THE MECHANICAL PLANS ALSO, AS THE
 MECHANICAL INSPECTOR MAY NOT BE LOOKING AT THE
 ELECTRICAL PLANS, PER 2004 FBC/M 602.2.1.
  
 4) PLEASE ALSO SHOW THE SIZE (O.D.) OF THE CPVC PIPE
 FOR THE VESDA PIPING SYSTEM ON THE MECHANICAL PLANS,
 PER 2004 FBC/M 602.2.1
  
 5) PLEASE SHOW COMPLIANCE WITH 2004 FBC/M 606.2.2
 COMMON SUPPLY, RETURN AIR AND SUPPLY AIR SYSTEMS.
 WHERE MULTIPLE AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY
 OR RETURN AIR DUCTS OR PLENUMS WITH A COMBINED DESIGN
 CAPACITY GREATER THAN 2,000 CFM (0.9 M 3 /S), THE
 RETURN AIR AND SUPPLY AIR SYSTEM SHALL BE PROVIDED WITH
 SMOKE DETECTORS IN ACCORDANCE WITH SECTION 606.2.1.
  
 6) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S FOR THE VESDA PIPING SYSTEM, PER 2004
 W.P.B. AMEND. 106.1.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]