2008-08-13 12:23:23*****DENIED*****
  
  
 1.THE ADDRESS OF THE SCOPE OF WORK SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH DAY OR MORE
 FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.AS PER LOCAL CODES, SMOKE DUCT DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM.
  
 5.PROVIDE INFORMATION AND SPECS ON THE VESDA SYSTEM
 IN REFEENCE TO ITS FIRE ALARM CAPABILITY.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  