2008-11-14 14:22:45PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) ENERGY CALCULATIONS FOR MAIN HOUSE, LINE 12C IS
 SHOWING A/C SYSTEM 4 AS 17 SEER, PLANS ARE SHOWING A/C
 SYSTEM AS 13 SEER. PLEASE CORRECT ENERGY CAL'S. PER
 2004 FBC13-103.3 AND 13-607.1.ABC.3.1.1.
  
 2) ENERGY CALCULATIONS FOR APT. ABOVE NEW GARAGE, LINE
 12A SHOW THE A/C SYSTEM AS 14 SEER, SEE ATTACHED COPY
 OF ARI CERTIFICATE SHOWS THE SYSTEM IS A 13 SEER,
 PLEASE CORRECT ENERGY CAL'S. PER 2004 FBC 13-103.3 AND
 13-607.1.ABC.3.1.1.
  
 3) ENERGY CALCULATIONS FOR THE APT. ABOVE NEW GARAGE
 NEED TO BE SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC
 13-103.3.
  
 4) PLEASE SHOW WHICH GAS TANKLESS WATER HEATER MODEL IS
 BEING INSTALLED (INDOOR) (OUTDOOR) (DIRECT VENT). BE
 ADVISED IF NOT THE DIRECT VENT MODEL THEN COMBUSTION
 AIR WILL NEED TO BE PROVIDED FOR AND SHOWN ON
 MECHANICAL PLANS. PER 2004 FBC/R G2407 AND G2407.5.1.
  
 5) SEE PLAN M-1.0, PLEASE SIZE THE SUPPLY AIR DUCT FROM
 A.H.U. #1, R-6 INS. BOX TO THE LIVING ROOM (HOOK TO
 EXISTING TRUNK LINE). PER 2004 FBC/R M1601.1.
  
 6) SEE PLAN M-2.0 APT. ABOVE NEW GARAGE, THE 4X8 RETURN
 AIR TRANSFER GRILL TO THE BEDROOM IS UNDER SIZED. PER
 2004 FBC/R M1602.1 BALANCED RETURN AIR MAY BE ACHIEVED
 BY.
  
 (B) TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO ACHIEVE
 PROPER RETURN AIR BALANCE
  
 (C) HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED. PER 2004 FBC/R M1602.4.
  