| 2008-11-17 13:20:33 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. SHT A-2.3 INDICATES A GAS COOKTOP/DOUBLE OVEN. A |
| | SEPARATE GAS PERMIT IS REQUIRED. PLEASE SUBMIT THE |
| | FOLLOWING INFORMATION: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ****RESPONSE NOTED, BUT THE RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. THE RISER DIAGRAM APPEARS TO |
| | THE UNDER THE SLAB, WHICH IS NOT APPROVED PER SECTION |
| | 404.11. ALL PIPING UNDER THE SLAB, (TO ISLAND |
| | APPLIANCES), SHALL BE SLEEVED. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | ****RESPONSE NOTED, SCHEDULE 40 METALLIC PIPE INDICATED |
| | SHALL BE PROTECTED PER SECTIONS 404.8, 404.8.1 & |
| | 404.8.2. PLEASE SHOW COMPLIANCE. |
| | |
| | C. OK |
| | |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | ****RESPONSE NOTED, BUT THE MANUF. SPECIFICATION SHEET |
| | SUBMITTED FOR THE TANKLESS WATER HEATERS INDICATE THE |
| | BTU LOAD AS 145,000 BTU'S. THIS WILL BE VERIFIED BY THE |
| | FIELD INSPECTOR. IF BOTH WATER HEATERS ARE 145,000 |
| | BTU'S THEN THE PIPE SIZING MAY BE REQUIRED TO BE |
| | CHANGED FOR NEW LOAD. TABLE 402.4(2). |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ****RESPONSE NOTED, BUT THE ADDITION OF ALL CUT SECTION |
| | LENGTHS SUBMITTED ADDS UP TO 138 FEET. PLEASE CORRECT |
| | INFORMATION IN "GAS NOTES" SHT P-2.0. |
| | |
| | F. OK |
| | G. N/A |
| | H. N/A |
| | |
| | I. PER N. MELICK MANUFACTURE INFO |
| | NOT REQUIRED FOR 1 & 2 FAMILY HOMES. |
| | JULY 17, 2002 OFFICAL INTERPRETATION. |
| | THE FIELD INSPECTOR SHALL VERIFY THE |
| | INSTALLED EQUIPMENT INPUT DOES NOT EX- |
| | CEED THE PIPE SIZING AS WELL AS MEETS THE LISTING |
| | REQUIREMENTS. |
| | (INFORMATIONAL) |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |