Plan Review Notes
Plan Review Notes For Permit 08070580
Permit Number 08070580
Review Stop G
Sequence Number 2
Notes
Date Text
2008-11-17 13:20:33DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT A-2.3 INDICATES A GAS COOKTOP/DOUBLE OVEN. A
 SEPARATE GAS PERMIT IS REQUIRED. PLEASE SUBMIT THE
 FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT THE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. THE RISER DIAGRAM APPEARS TO
 THE UNDER THE SLAB, WHICH IS NOT APPROVED PER SECTION
 404.11. ALL PIPING UNDER THE SLAB, (TO ISLAND
 APPLIANCES), SHALL BE SLEEVED.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ****RESPONSE NOTED, SCHEDULE 40 METALLIC PIPE INDICATED
 SHALL BE PROTECTED PER SECTIONS 404.8, 404.8.1 &
 404.8.2. PLEASE SHOW COMPLIANCE.
  
 C. OK
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 ****RESPONSE NOTED, BUT THE MANUF. SPECIFICATION SHEET
 SUBMITTED FOR THE TANKLESS WATER HEATERS INDICATE THE
 BTU LOAD AS 145,000 BTU'S. THIS WILL BE VERIFIED BY THE
 FIELD INSPECTOR. IF BOTH WATER HEATERS ARE 145,000
 BTU'S THEN THE PIPE SIZING MAY BE REQUIRED TO BE
 CHANGED FOR NEW LOAD. TABLE 402.4(2).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT THE ADDITION OF ALL CUT SECTION
 LENGTHS SUBMITTED ADDS UP TO 138 FEET. PLEASE CORRECT
 INFORMATION IN "GAS NOTES" SHT P-2.0.
  
 F. OK
 G. N/A
 H. N/A
  
 I. PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING AS WELL AS MEETS THE LISTING
 REQUIREMENTS.
 (INFORMATIONAL)
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]