Plan Review Notes
Plan Review Notes For Permit 08070580
Permit Number 08070580
Review Stop E
Sequence Number 2
Notes
Date Text
2008-11-13 11:11:55 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ALL COMMENTS RELATE TO SHEET E-1.0, UNLESS OTHERWISE
 NOTED.
  
 THESE ARE COMMENTS FROM THE PREVIOUS REVIEW THAT WERE
 NOT CORRECTLY RESPONDED TO.***INDICATES FURTHER
 EXPLANATION OF PREVIOUS COMMENT
  
 2} THE GENERATOR SHOWN ON SHEET E-1.0 MUST BE PERMITTED
 SEPARATE***.THE GENERATOR IS STILL SHOWN ON THE RISER
 DIAGRAM AND ON THE MECHANICAL SHEETS. REMOVE FROM
 PLANS, DESIGNATE AS FUTURE OR PROVIDE ALL DOCUMENTATION
 AND PLANS FOR A RESIDENTIAL GENERATOR PERMIT IF IT IS
 TO BE PART OF THIS PERMIT.
  
 4} PROVIDE LOAD CALCULATIONS PER 220.83(B) TO DETERMINE
 IF THE EXISTING SERVICE HAS SUFFICIENT CAPACITY FOR THE
 ADDED LOADS. THE "DEMAND CALCULATION" (E-1.0) IS NOT
 CORRECT AS H.V.A.C UNITS #3 AND 4 HAVE BEEN OMITTED.
 THE CALCULATED LOAD SHOULD INCLUDE THE TOTAL CALCULATED
 LOAD BEFORE APPLYING DEMAND FACTORS, THE DEMAND FACTORS
 USED, THE CALCULATED LOAD AFTER APPLYING DEMAND
 FACTORS, ARTICLE 215.5 NEC 2005*** THE CALCULATION
 GIVEN IS INCORRECT PER 220.83. THE AMPERAGE WOULD BE
 212 AMPS AFTER DEMANDS. THE EXISTING SERVICE IS 200
 AMPS..
  
 6} VERIFY THE 2/0 FEEDERS SHOWN ON THE RISER DIAGRAM
 FEEDING A 50 AMP PANEL (C) IS WHAT THE DESIGNER
 INTENDED. ALTHOUGH NOT A VIOLATION, IF PART OF THE
 PERMITTED SET OF PLANS THEY MUST BE INSTALLED, OR A
 REVISION WILL BE MUST BE SUBMITTED TO MAKE A CHANGE IN
 THE FUTURE***THE PANEL SCHEDULE LISTS THE FEEDER FOR
 PANEL "B" AS 40 AMP (NOT LARGE ENOUGH FOR THE
 CALCULATED LOAD FOR THAT PANEL), AND 60 AMPS FOR PANEL
 "C". CORRELATE THE RISER INFORMATIONN WITH THE PANEL
 INFORMATIO..
  
 7} THE 1" CONDUIT (SHEET E-1.0 RISER) WITH 3-2/0 AND 1
 #6 CONDUCTORS FEEDING PANEL "A" , "B" AND PANEL "C" IS
 IN VIOLATION OF ANNEX "C" TABLES, 2005 NEC***.THIS
 ISSUE STILL REMAINS ON THE PLAN, NO CHANGE.
  
 13} CIRCUIT B8 SHOULD BE LABELED BATH CIRCUIT IN THE
 SCHEDULE PER 408.4*** NOW LABELED CORRECTLY BU ON A 15
 AMP CIRCUIT IN VIOLATION OF.210.11(C)(3)--20 AMP
 CIRCUIT.
  
 15} THE FREEZER, MICROWAVES (TWO EACH) ICEMAKER AND SPA
 ARE NOT LISTED IN THE PANEL SCHEDULE OR IN THE LOAD
 CALCS. 220.83(B).*** NO CHANGE , STILL NOT LISTED IN
 THE SCHEDULES.
  
 ALL COMMENTS RELATE TO SHEET E-2.0.
  
 20} A SMOKE ALARM IS REQUIRED ON EACH ADDITIONAL STORY
 OF THE DWELLING, PER 313.1(A) FBCR. THE FIRST FLOOR OF
 THE GARAGE BY THE STAIR WILL MEET THE INTENT***WAS NOT
 ADDED, STILL IN VIOLATION..
  
 21} THE LOCATION OF THE DISCONNECTS FOR THE A/C
 CONDENSERS DO NOT COMPLY WITH 110.26 CLEARANCE
 REQUIREMENTS. A NOTE TO COMPLY WITH THAT ARTICLE WILL
 SUFFICE AS THE LOCATION SHOWN IS DIAGRAMMATICALLY*** NO
 NOTE ADDED, NO DISCONNECTS LOCATED ON THE PLAN.
  
 ALL COMMENTS REFER TO SHEET E-2.1
  
 22} THE SMOKE DEVICES ARE LABELED "DETECTORS", SEE THE
 DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72,
 CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES*** NOT ADDRESSED..
  
  
 25} PER 313.1 FBCR "WHEN MORE THAN ONE SMOKE ALARM IS
 REQUIRED TO BE INSTALLED WITHIN AN INDIVIDUAL DWELLING
 UNIT THE ALARM DEVICES SHALL BE INTERCONNECTED IN SUCH
 A MANNER THAT THE ACTUATION OF ONE ALARM WILL ACTIVATE
 ALL OF THE ALARMS IN THE INDIVIDUAL UNIT." INDICATE THE
 CIRCUIT NUMBER AT ALL SMOKE DEVICES TO HELP ELIMINATE
 NO CONFUSION IN THE FIELD AT INSTALLATION. ALSO SEE
 210.12 NEC.***THE CIRCUITS ASSIGN TO THE SMOKE ALARMS
 ARE MULTIPLE. ALL INTERCONNECTED ALARMS ARE TO BE ON
 THE SAME CIRCUIT PER MANUFACTURERS INSTRUCTIONS AND TO
 PREVENT SHORT CIRCUITS.
  
 NEW COMMENTS GENERATED BY PLAN CHANGES
  
 26} SHEET E-1.0, CIRCUIT A4, PANEL "A" SHOULD BE
 LABELED "BATH CIRCUIT".
  
 27} PANEL "B", CIRCUITS #B8,B10, AND B12 MUST BE 20 AMP
 PER 210.11(C)(1) AND 210.11(C)(3).
  
 28 } PANEL "C" CIRCUIT C8 MUST BE LABELED BATH CIRCUIT
 AND BE 20 AMPS PER 210.11(C)(3)
  
 SHEET E-2.0
  
 29} THE LOCATION OF AHU #1 VIOLATES THE CLEARANCE
 REQUIREMENTS OF 3' FOR THE PANELS. 110.26
  
 RESPOND TO ALL COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER