Plan Review Notes
Plan Review Notes For Permit 08070580
Permit Number 08070580
Review Stop P
Sequence Number 1
Notes
Date Text
2008-08-11 15:59:39DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 MECHANICAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUES
  
 1. SHT A-2.3 SHOW COMPLIANCE WITH SECTIONS P305.9,
 PROTECTION OF COMPONETS OF PLUMBING SYSTEM, (WATER
 HEATER), AND M303.4 PROTECTION FROM DAMAGE, (WASH
 MACHINE - A/C UNIT). INDICATE METHOD FOR BOTH.
  
 2. ALL SHEETS WITH WAYNE FERRELL TITLE BLOCK. THE
 ADDRESS INDICATED ON THE TITLE BLOCK FOR THE ARCHITECT,
 (825 S.E. 8TH STREET DEERFIELD BEACH), DOES NOT REFLECT
 THE ADDRESS OF RECORD ON THE FLORIDA DBPR WEBSITE. (801
 S.E. 12TH AVE. DEERFIELD BEACH). PLEASE UPDATE THE
 TITLE BLOCKS OR THE DBPR WEBSITE PRIOR TO RESUBMITTING
 FOR REVIEW. FAC 61G1-16.004(1) & FS 481.219.
  
 3. SHT P-1.0 PLUMBING NOTES #10. AIR CHAMBERS ARE NOT
 APPROVED. SECTION 604.9. PLEASE DELETE FROM REFERENCE.
  
 4. SHT P-1.0 NEW WATER HEATER DETAIL. A FULL OPEN VALVE
 IS REQUIRED ON THE SUPPLY LINE TO THE WATER HEATER.
 SECTION 606.1(7). PLEASE INDICATE IN DETAIL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  