| Date |
Text |
| 2008-08-11 15:59:39 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 MECHANICAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUES |
| | |
| | 1. SHT A-2.3 SHOW COMPLIANCE WITH SECTIONS P305.9, |
| | PROTECTION OF COMPONETS OF PLUMBING SYSTEM, (WATER |
| | HEATER), AND M303.4 PROTECTION FROM DAMAGE, (WASH |
| | MACHINE - A/C UNIT). INDICATE METHOD FOR BOTH. |
| | |
| | 2. ALL SHEETS WITH WAYNE FERRELL TITLE BLOCK. THE |
| | ADDRESS INDICATED ON THE TITLE BLOCK FOR THE ARCHITECT, |
| | (825 S.E. 8TH STREET DEERFIELD BEACH), DOES NOT REFLECT |
| | THE ADDRESS OF RECORD ON THE FLORIDA DBPR WEBSITE. (801 |
| | S.E. 12TH AVE. DEERFIELD BEACH). PLEASE UPDATE THE |
| | TITLE BLOCKS OR THE DBPR WEBSITE PRIOR TO RESUBMITTING |
| | FOR REVIEW. FAC 61G1-16.004(1) & FS 481.219. |
| | |
| | 3. SHT P-1.0 PLUMBING NOTES #10. AIR CHAMBERS ARE NOT |
| | APPROVED. SECTION 604.9. PLEASE DELETE FROM REFERENCE. |
| | |
| | 4. SHT P-1.0 NEW WATER HEATER DETAIL. A FULL OPEN VALVE |
| | IS REQUIRED ON THE SUPPLY LINE TO THE WATER HEATER. |
| | SECTION 606.1(7). PLEASE INDICATE IN DETAIL. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |