Plan Review Notes
Plan Review Notes For Permit 08070580
Permit Number 08070580
Review Stop M
Sequence Number 1
Notes
Date Text
2008-08-06 11:24:52PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) NEED TO SUBMIT ENERGY CALCULATIONS AND COOLING LOAD
 CALCULATIONS FOR THE SECOND FLOOR ABOVE THE GARAGE. PER
 2004 FBC 13-101.2.5.1 RESIDENCES IN WHICH TWO BUILDINGS
 ARE PERMITTED TOGETHER THAT ARE NOT CONNECTED BY
 CONDITIONED SPACE SHALL BE CONSIDERED SEPARATE
 RESIDENCES FOR THE PURPOSES OF COMPLIANCE WITH THIS
 CODE IF THE FOLLOWING CONDITIONS APPLY:
 1. THE SECONDARY BUILDING HAS ITS OWN BATHROOM AND
 KITCHENETTE OR BAR; AND
 2. THE SECONDARY BUILDING IS HEATED AND/OR COOLED BY
 A SEPARATE HEATING AND/OR COOLING SYSTEM.
  
 2) ENERGY CALCULATIONS LINE 12 SHOWS TWO 14 SEER A/C
 SYSTEMS, AS THE SYSTEMS ARE EXISTING (USED) YOU NEED TO
 COMPLY WITH 2004 FBC 13-101.4.2.1 ASSUMPTIONS FOR
 EXISTING BUILDING EFFICIENCIES.
 THE FOLLOWING RESTRICTIONS APPLY IF THE ENTIRE BUILDING
 IS USED TO DEMONSTRATE CODE COMPLIANCE:
 4. EQUIPMENT EFFICIENCIES SHALL BE DEMONSTRATED,
 EITHER FROM MANUFACTURER?S LITERATURE OR CERTIFIED
 EQUIPMENT DIRECTORIES, OR BY THE PROCEDURE PROVIDED IN
 SECTION 407.1.ABC.3 OR SECTION 607.1.ABC.3 BASED ON
 SYSTEM CAPACITY AND TOTAL ON-SITE ENERGY INPUT.
 EQUIPMENT TO BE ADDED SHALL MEET THE APPLICABLE MINIMUM
 EQUIPMENT EFFICIENCY FROM TABLES 407.1.ABC.3.2A THROUGH
 407.1.ABC.3.2D AND 408.1.ABC.3.2E THROUGH 408.1
 .ABC.3.2G FOR COMMERCIAL OCCUPANCIES AND FROM TABLES
 607.1.ABC.3.2A THROUGH 607.1.ABC.3.2D AND
 608.1.ABC.3.2E THROUGH 608.1.ABC.3.2F FOR RESIDENTIAL
 OCCUPANCIES. EXISTING EQUIPMENT EFFICIENCIES NOT
 MEETING THE VALUES GIVEN IN TABLES 407.1.ABC.3.2A
 THROUGH 407.1.ABC.3.2D AND 408.1.ABC.3.2E THROUGH 408.1
 .ABC.3.2G FOR COMMERCIAL OCCUPANCIES SHALL UTILIZE THE
 COOLING OR HEATING SYSTEM MULTIPLIERS PROVIDED BY
 FLA/COM. EXISTING RESIDENTIAL EQUIPMENT NOT MEETING THE
 EFFICIENCIES IN TABLES 607.1.ABC.3.2A THROUGH
 607.1.ABC.3.2D AND 608.1.ABC.3.2E THROUGH
 608.1.ABC.3.2F SHALL UTILIZE THE COOLING OR HEATING
 SYSTEM MULTIPLIERS PROVIDED IN TABLES 6-16 TO 6-17 OF
 APPENDIX C TO THIS CHAPTER. RESIDENTIAL DUCTS WITH LESS
 THAN R-4.2 INSULATION SHALL USE THE MULTIPLIERS
 PROVIDED IN TABLES 6-18 TO 6-20 IN APPENDIX 13-C TO
 THIS CHAPTER.
  
 3)A/C SYSTEM MODEL NUMBERS LISTED ON THE A/C PLAN
 M-3.0 EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI
 DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI
 CERTIFICATE, SEE 2004 FBC 13-407.1.ABC.3.1.1 OR
 13-607.1.ABC.3.1.1.
  
 4) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 5) AREA CALCULATIONS ON PLAN A-2.0 FOR UNDER AIR NEW
 AND EXISTING DO NOT ADD UP, PLEASE RECHECK AND
 CORRECT.
  
 6) ARCHITECTURAL AND ELECTRICAL PLANS SHOW A NEW AIR
 HANDLER IN THE GARAGE NEXT TO THE MAIN KITCHEN AND A
 NEW CONDENSER UNIT UNDER THE STAIRS. AS THIS DOES NOT
 COINCIDE WITH THE MECHANICAL PLANS AND ENERGY
 CALCULATIONS, WHETHER NEW OR EXISTING PLEASE REMOVE,
 SEE 2004 FBC 13-607.1.ABC.1.2.
  
 7) PROVIDE FOR RETURN AIR TO BEDROOM #2 AND THE STUDY
 ON PLAN M-2.0, PER 2004 FBC/R M1602.4.
  
 8) RETURN AIR WILL NOT GET FROM THE MASTER BEDROOM TO
 THE AIR HANDLER IF THE POCKET DOOR ARE CLOSED AT THE
 MASTER BEDROOM OR THE POCKET DOORS AT THE HALL, PLEASE
 CORRECT PER 2004 FBC/R M1602.4.
  
 9) NO PLANS WERE SUBMITTED FOR THE THIRD FLOOR. PLEASE
 SUBMIT PLANS FOR THE THIRD FLOOR AS DUCTS ARE GOING TO
 IT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]