| 2008-08-07 12:08:08 | |
| | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 |
| | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | ALL COMMENTS RELATE TO SHEET E-1.0, UNLESS OTHERWISE |
| | NOTED. |
| | |
| | 1} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE |
| | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| | DESIGNED. SEE GENERAL DESIGN CRITERIA ON SHEET A-1.1 |
| | AND ELECTRICAL NOTES #1 AND 11 SHEET E-1.0 |
| | |
| | 2} THE GENERATOR SHOWN ON SHEET E-1.0 MUST BE PERMITTED |
| | SEPARATE. |
| | |
| | 3} THE SMOKE DETECTOR CONNECTION DETAIL CONNECTS THEM |
| | TO A KITCHEN OR BATH LIGHT CIRCUIT, SEE NOTE #27 THIS |
| | SHEET (E-1.0) AND 210.12, 2005 NEC. |
| | |
| | 4} PROVIDE LOAD CALCULATIONS PER 220.83(B) TO DETERMINE |
| | IF THE EXISTING SERVICE HAS SUFFICIENT CAPACITY FOR THE |
| | ADDED LOADS. THE "DEMAND CALCULATION" (E-1.0) IS NOT |
| | CORRECT AS H.V.A.C UNITS #3 AND 4 HAVE BEEN OMITTED. |
| | THE CALCULATED LOAD SHOULD INCLUDE THE TOTAL CALCULATED |
| | LOAD BEFORE APPLYING DEMAND FACTORS, THE DEMAND FACTORS |
| | USED, THE CALCULATED LOAD AFTER APPLYING DEMAND |
| | FACTORS, ARTICLE 215.5 NEC 2005. |
| | |
| | 5} NEW PANEL "C" IS NOT LISTED AS BEING FED IN PANEL |
| | "A" SCHEDULE, E-1.0. |
| | |
| | 6} VERIFY THE 2/0 FEEDERS SHOWN ON THE RISER DIAGRAM |
| | FEEDING A 50 AMP PANEL (C) IS WHAT THE DESIGNER |
| | INTENDED. ALTHOUGH NOT A VIOLATION, IF PART OF THE |
| | PERMITTED SET OF PLANS THEY MUST BE INSTALLED, OR A |
| | REVISION WILL BE MUST BE SUBMITTED TO MAKE A CHANGE IN |
| | THE FUTURE. |
| | |
| | 7} THE 1" CONDUIT (SHEET E-1.0 RISER) WITH 3-32/0 AND 1 |
| | #6 CONDUCTORS FEEDING PANEL "A" AND PANEL "C" IS IN |
| | VIOLATION OF ANNEX "C" TABLES, 2005 NEC. |
| | |
| | 8} THE 40 AMP OCP FOR THE 9500 WATT AIR HANDLERS 3 AND |
| | 4, DOES NOT COMPLY WITH 424.3(B) (125%). 9500/240=39 |
| | AMPS X 125%=49 AMPS. |
| | |
| | 9} THERE ARE ONLY 3 A/C SYSTEMS ON THE MECHANICAL PLANS |
| | AND FOUR ON THE ELECTRICAL, CORRELATE SAME.ALSO SEE THE |
| | MECHANICAL SHEETS LIST THE HEAT AT 10K, THE ELECTRICAL |
| | SCHEDULES AT 9.5K. CORRELATE THESE PLANS. |
| | |
| | 10} THE SUB PANEL FEED FROM PANEL "A" TO "B" LISTS |
| | NUMBER #8 CONDUCTORS ON A 60 AMP BREAKER IN VIOLATION |
| | OF 310.16. NOTE THE LOAD @ 14KW IS 59 AMPS. |
| | |
| | 11} THE SMALL APPLIANCE CIRCUIT #A8 IS NOT SHOWN ON THE |
| | FLOOR PLAN CIRCUIT #A26 SEEMS TO BE THE ONLY SMALL |
| | APPLIANCE CIRCUIT SERVING THE KITCHEN, SEE 210.52(B)(1) |
| | FOR MINIMUM REQUIREMENTS. |
| | |
| | 12} THERE IS AN EXISTING POOL ON SHEET A-2.0, THERE IS |
| | NO POOL EQUIPMENT LISTED IN THE PANEL SCHEDULES OR IN |
| | THE LOAD CALCS. |
| | |
| | 13} CIRCUIT B8 SHOULD BE LABELED BATH CIRCUIT IN THE |
| | SCHEDULE PER 408.4. |
| | |
| | 14} CIRCUIT A4 EXTENDING OUT OF THE BATHROOM INTO THE |
| | CLOSET, SHEET E-2.1, IS IN VIOLATION OF 210.11(C)(3). |
| | |
| | 15} THE FREEZER, MICROWAVES (TWO EACH) ICEMAKER AND SPA |
| | ARE NOT LISTED IN THE PANEL SCHEDULE OR IN THE LOAD |
| | CALCS. 220.83(B). |
| | |
| | 16} CIRCUITS B11 AND C11CARRY OVER TO INCLUDE GENERAL |
| | LIGHTING CIRCUITS ALONG WITH AIR HANDLERS. PLEASE |
| | RENUMBER CIRCUITS.408.4. |
| | |
| | 17} INDICATE THE NUMBER OF CIRCUITS IN EACH OF THE |
| | PANELS LISTED AS PART OF THEIR RATING, 408.4 NEC, |
| | 106.3.5.4(8) FBC. |
| | |
| | 18} PANEL"B" LISTS 2 CONDUCTORS ON CIRCUITS B3, 5, 7, 9 |
| | AND 11, PANEL "C" LISTS TWO CONDUCTORS ON CIRCUITS |
| | C3,5,7,9 AND 11 AND ONE BREAKER (C1) FOR A 240 CIRCUIT. |
| | SEE 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION. |
| | B8 SHOULD BE LISTED AS BATH CIRCUIT. |
| | |
| | ALL COMMENTS RELATE TO SHEET E-2.0. |
| | |
| | 19} THE RECEPTACLE AT THE SINK IN THE "DOG AREA" MUST |
| | BE GFI PER 210.8(A)(7). |
| | |
| | 20} A SMOKE ALARM IS REQUIRED ON EACH ADDITIONAL STORY |
| | OF THE DWELLING, PER 313.1(A) FBCR. THE FIRST FLOOR OF |
| | THE GARAGE BY THE STAIR WILL MEET THE INTENT. |
| | |
| | 21} THE LOCATION OF THE DISCONNECTS FOR THE A/C |
| | CONDENSERS DO NOT COMPLY WITH 110.26 CLEARANCE |
| | REQUIREMENTS. A NOTE TO COMPLY WITH THAT ARTICLE WILL |
| | SUFFICE AS THE LOCATION SHOWN IS DIAGRAMMATICAL |
| | |
| | ALL COMMENTS REFER TO SHEET E-2.1 |
| | |
| | 22} THE SMOKE DEVICES ARE LABELED "DETECTORS", SEE THE |
| | DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72, |
| | CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID |
| | CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE |
| | LOCATIONS OF THE SOUNDING DEVICES. |
| | |
| | 23} PER 210.11(C)(3) BATHROOM BRANCH CIRCUITS IN |
| | ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY |
| | OTHER PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE |
| | BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM |
| | RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER |
| | OUTLETS. |
| | EXCEPTION: WHERE THE 20-AMPERE CIRCUIT SUPPLIES A |
| | SINGLE BATHROOM, OUTLETS FOR OTHER EQUIPMENT WITHIN THE |
| | SAME BATHROOM SHALL BE PERMITTED TO BE SUPPLIED IN |
| | ACCORDANCE WITH 210.23(A)(1) AND (A)(2).***CIRCUIT C8 |
| | FEEDING THE BATH IN THE UNIT ABOVE THE GARAGE ALSO |
| | FEEDS THE SMOKE ALARMS AND A RECEPTACLE IN THE KITCHEN |
| | IN VIOLATION OF THIS ARTICLE. |
| | |
| | 24} ALTHOUGH COMMENT #8 OF THE ZONING REVIEW DISALLOWS |
| | THE 240 VOLT OUTLET, THE FBCR VIEWS THIS AREA AS A |
| | KITCHEN BY DEFINITION IN CHAPTER #2. PER THE NEC |
| | ARTICLE 210.11(C)(1) TWO SMALL APPLIANCE CIRCUITS ARE |
| | REQUIRED. INDICATE COMPLIANCE ON THE PLAN AND IN THE |
| | PANEL SCHEDULE PER 408.4, AS A ZONING VARIANCE MAY BE |
| | ALLOWED IN THE FUTURE. |
| | |
| | 25} PER 313.1 FBCR "WHEN MORE THAN ONE SMOKE ALARM IS |
| | REQUIRED TO BE INSTALLED WITHIN AN INDIVIDUAL DWELLING |
| | UNIT THE ALARM DEVICES SHALL BE INTERCONNECTED IN SUCH |
| | A MANNER THAT THE ACTUATION OF ONE ALARM WILL ACTIVATE |
| | ALL OF THE ALARMS IN THE INDIVIDUAL UNIT." INDICATE THE |
| | CIRCUIT NUMBER AT ALL SMOKE DEVICES TO HELP ELIMINATE |
| | NO CONFUSION IN THE FIELD AT INSTALLATION. ALSO SEE |
| | 210.12 NEC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |