Plan Review Notes
Plan Review Notes For Permit 08070580
Permit Number 08070580
Review Stop E
Sequence Number 1
Notes
Date Text
2008-08-07 12:08:08 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ALL COMMENTS RELATE TO SHEET E-1.0, UNLESS OTHERWISE
 NOTED.
  
 1} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED. SEE GENERAL DESIGN CRITERIA ON SHEET A-1.1
 AND ELECTRICAL NOTES #1 AND 11 SHEET E-1.0
  
 2} THE GENERATOR SHOWN ON SHEET E-1.0 MUST BE PERMITTED
 SEPARATE.
  
 3} THE SMOKE DETECTOR CONNECTION DETAIL CONNECTS THEM
 TO A KITCHEN OR BATH LIGHT CIRCUIT, SEE NOTE #27 THIS
 SHEET (E-1.0) AND 210.12, 2005 NEC.
  
 4} PROVIDE LOAD CALCULATIONS PER 220.83(B) TO DETERMINE
 IF THE EXISTING SERVICE HAS SUFFICIENT CAPACITY FOR THE
 ADDED LOADS. THE "DEMAND CALCULATION" (E-1.0) IS NOT
 CORRECT AS H.V.A.C UNITS #3 AND 4 HAVE BEEN OMITTED.
 THE CALCULATED LOAD SHOULD INCLUDE THE TOTAL CALCULATED
 LOAD BEFORE APPLYING DEMAND FACTORS, THE DEMAND FACTORS
 USED, THE CALCULATED LOAD AFTER APPLYING DEMAND
 FACTORS, ARTICLE 215.5 NEC 2005.
  
 5} NEW PANEL "C" IS NOT LISTED AS BEING FED IN PANEL
 "A" SCHEDULE, E-1.0.
  
 6} VERIFY THE 2/0 FEEDERS SHOWN ON THE RISER DIAGRAM
 FEEDING A 50 AMP PANEL (C) IS WHAT THE DESIGNER
 INTENDED. ALTHOUGH NOT A VIOLATION, IF PART OF THE
 PERMITTED SET OF PLANS THEY MUST BE INSTALLED, OR A
 REVISION WILL BE MUST BE SUBMITTED TO MAKE A CHANGE IN
 THE FUTURE.
  
 7} THE 1" CONDUIT (SHEET E-1.0 RISER) WITH 3-32/0 AND 1
 #6 CONDUCTORS FEEDING PANEL "A" AND PANEL "C" IS IN
 VIOLATION OF ANNEX "C" TABLES, 2005 NEC.
  
 8} THE 40 AMP OCP FOR THE 9500 WATT AIR HANDLERS 3 AND
 4, DOES NOT COMPLY WITH 424.3(B) (125%). 9500/240=39
 AMPS X 125%=49 AMPS.
  
 9} THERE ARE ONLY 3 A/C SYSTEMS ON THE MECHANICAL PLANS
 AND FOUR ON THE ELECTRICAL, CORRELATE SAME.ALSO SEE THE
 MECHANICAL SHEETS LIST THE HEAT AT 10K, THE ELECTRICAL
 SCHEDULES AT 9.5K. CORRELATE THESE PLANS.
  
 10} THE SUB PANEL FEED FROM PANEL "A" TO "B" LISTS
 NUMBER #8 CONDUCTORS ON A 60 AMP BREAKER IN VIOLATION
 OF 310.16. NOTE THE LOAD @ 14KW IS 59 AMPS.
  
 11} THE SMALL APPLIANCE CIRCUIT #A8 IS NOT SHOWN ON THE
 FLOOR PLAN CIRCUIT #A26 SEEMS TO BE THE ONLY SMALL
 APPLIANCE CIRCUIT SERVING THE KITCHEN, SEE 210.52(B)(1)
 FOR MINIMUM REQUIREMENTS.
  
 12} THERE IS AN EXISTING POOL ON SHEET A-2.0, THERE IS
 NO POOL EQUIPMENT LISTED IN THE PANEL SCHEDULES OR IN
 THE LOAD CALCS.
  
 13} CIRCUIT B8 SHOULD BE LABELED BATH CIRCUIT IN THE
 SCHEDULE PER 408.4.
  
 14} CIRCUIT A4 EXTENDING OUT OF THE BATHROOM INTO THE
 CLOSET, SHEET E-2.1, IS IN VIOLATION OF 210.11(C)(3).
  
 15} THE FREEZER, MICROWAVES (TWO EACH) ICEMAKER AND SPA
 ARE NOT LISTED IN THE PANEL SCHEDULE OR IN THE LOAD
 CALCS. 220.83(B).
  
 16} CIRCUITS B11 AND C11CARRY OVER TO INCLUDE GENERAL
 LIGHTING CIRCUITS ALONG WITH AIR HANDLERS. PLEASE
 RENUMBER CIRCUITS.408.4.
  
 17} INDICATE THE NUMBER OF CIRCUITS IN EACH OF THE
 PANELS LISTED AS PART OF THEIR RATING, 408.4 NEC,
 106.3.5.4(8) FBC.
  
 18} PANEL"B" LISTS 2 CONDUCTORS ON CIRCUITS B3, 5, 7, 9
 AND 11, PANEL "C" LISTS TWO CONDUCTORS ON CIRCUITS
 C3,5,7,9 AND 11 AND ONE BREAKER (C1) FOR A 240 CIRCUIT.
 SEE 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION.
 B8 SHOULD BE LISTED AS BATH CIRCUIT.
  
 ALL COMMENTS RELATE TO SHEET E-2.0.
  
 19} THE RECEPTACLE AT THE SINK IN THE "DOG AREA" MUST
 BE GFI PER 210.8(A)(7).
  
 20} A SMOKE ALARM IS REQUIRED ON EACH ADDITIONAL STORY
 OF THE DWELLING, PER 313.1(A) FBCR. THE FIRST FLOOR OF
 THE GARAGE BY THE STAIR WILL MEET THE INTENT.
  
 21} THE LOCATION OF THE DISCONNECTS FOR THE A/C
 CONDENSERS DO NOT COMPLY WITH 110.26 CLEARANCE
 REQUIREMENTS. A NOTE TO COMPLY WITH THAT ARTICLE WILL
 SUFFICE AS THE LOCATION SHOWN IS DIAGRAMMATICAL
  
 ALL COMMENTS REFER TO SHEET E-2.1
  
 22} THE SMOKE DEVICES ARE LABELED "DETECTORS", SEE THE
 DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72,
 CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES.
  
 23} PER 210.11(C)(3) BATHROOM BRANCH CIRCUITS IN
 ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE
 BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM
 RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER
 OUTLETS.
 EXCEPTION: WHERE THE 20-AMPERE CIRCUIT SUPPLIES A
 SINGLE BATHROOM, OUTLETS FOR OTHER EQUIPMENT WITHIN THE
 SAME BATHROOM SHALL BE PERMITTED TO BE SUPPLIED IN
 ACCORDANCE WITH 210.23(A)(1) AND (A)(2).***CIRCUIT C8
 FEEDING THE BATH IN THE UNIT ABOVE THE GARAGE ALSO
 FEEDS THE SMOKE ALARMS AND A RECEPTACLE IN THE KITCHEN
 IN VIOLATION OF THIS ARTICLE.
  
 24} ALTHOUGH COMMENT #8 OF THE ZONING REVIEW DISALLOWS
 THE 240 VOLT OUTLET, THE FBCR VIEWS THIS AREA AS A
 KITCHEN BY DEFINITION IN CHAPTER #2. PER THE NEC
 ARTICLE 210.11(C)(1) TWO SMALL APPLIANCE CIRCUITS ARE
 REQUIRED. INDICATE COMPLIANCE ON THE PLAN AND IN THE
 PANEL SCHEDULE PER 408.4, AS A ZONING VARIANCE MAY BE
 ALLOWED IN THE FUTURE.
  
 25} PER 313.1 FBCR "WHEN MORE THAN ONE SMOKE ALARM IS
 REQUIRED TO BE INSTALLED WITHIN AN INDIVIDUAL DWELLING
 UNIT THE ALARM DEVICES SHALL BE INTERCONNECTED IN SUCH
 A MANNER THAT THE ACTUATION OF ONE ALARM WILL ACTIVATE
 ALL OF THE ALARMS IN THE INDIVIDUAL UNIT." INDICATE THE
 CIRCUIT NUMBER AT ALL SMOKE DEVICES TO HELP ELIMINATE
 NO CONFUSION IN THE FIELD AT INSTALLATION. ALSO SEE
 210.12 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718