| Date |
Text |
| 2008-08-16 08:53:29 | DENIED |
| | |
| | 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC* |
| | |
| | 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON |
| | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER |
| | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE |
| | ADDED TO THE PERMIT APPLICATION FEES |
| | |
| | |
| | NOTE: FEES ARE DUE IN THE AMOUNT OF $ 160.78 FOR |
| | INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS |
| | REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW |
| | |
| | |
| | 3)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE |
| | PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR |
| | SETBACKS |
| | |
| | 4)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN |
| | COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES. |
| | |
| | 5)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2 |
| | FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER |
| | AND OWNER/AGENT PRIOR TO SUBMITTAL. PLEASE NOTE THAT |
| | THE OWNER AGENT SECTION WAS NOT SIGNED AND SEVERAL |
| | CORRECTION ARE REQUIRED TO COMPLY WITH DRAWINGS SUCH AS |
| | FRAMED SECOND STORY WALLS, NO INSULATION SHOWN ON |
| | RAISED FLOOR BELOW BALCONY IN MASTER BEDROOM OR |
| | INSULATION VALUE FOR VAULTED CEILINGS (NOT UNDER |
| | ATTIC) |
| | |
| | 6)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE, |
| | AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 7)VERIFY THAT BEDROOM WINDOW IN GUEST ROOM ABOVE |
| | GARAGE MEET EMERGENCY EGRESS PER R310 FBC: MIN. NET |
| | CLEAR OPENING OF 5 SQ.FT. ON GRADE FLOOR. MIN. NET |
| | CLEAR OPENING ALL OTHER FLOORS OF 5.7 SQ.FT. IN BOTH |
| | CASES THE MIN.NET CLEAR HEIGHT SHALL BE 24" AND THE NET |
| | CLEAR WIDTH SHALL BE 20" |
| | |
| | 8)VERIFY THE DESIGN CRITERIA THAT WILL BE USED, |
| | ENGINEERING CALC SHEETS PROVIDED DIFFER FROM THOSE ON |
| | THE DRAWINGS A-1.1 AND S-1.1 AND S-1.2 FOR WIND SPEED, |
| | SOIL BEARING CAPACITY , ROOF/TRUSS LOADS ETC. ONCE THE |
| | DESIGN CRITERIA IS SET BE SURE THAT THE DOOR AND WINDOW |
| | PRESSURES ARE AS REQUIRED. |
| | |
| | 9)TIE BEAM #3 ON S-1.1 IS NOT SHOWN IN THE BEAM |
| | SCHEDULE |
| | |
| | 10)PLEASE VERIFY HANGER USED FOR 3 PLY GIRDER TRUSS |
| | AT GARAGE FLOOR FRAMING, SECTION B ON S-1.7 SHOWS A |
| | SINGLE WIDE HANGER THD28 |
| | |
| | 11)CONFIRM LOCATION OF GIRDER TRUSS IN GARAGEWITH |
| | LAYOUT OF STAIRS TO SECOND FLOOR, SHOW OPENING LAYOUT |
| | |
| | 12)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT |
| | COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR |
| | BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND |
| | APPROVED BY THE DESIGNER OF RECORD |
| | |
| | 13)DRAWINGS SHALL SHOW THE MINIMUM DEPTH OF |
| | FOUNDATION ON THE WALL SECTIONS PER R403.1.4 FBC RES. |
| | 12" BELOW UNDISTURBED SOIL, SHEETS S-1.7 AND S-1.8 SHOW |
| | 8" |
| | |
| | 14)PROVIDE BEARING/ATTACHMENT DETAIL FOR HOLLOW CORE |
| | PANELS AT BALCONYAND EXISTING GARAGE WALLAND AT |
| | FIREPLACE, SEE S-1.1 |
| | |
| | 15)HANDRAILS AND GUARDS TO SHOW THAT ATTACHMENT WILL |
| | MEET THE REQUIREMENTS OF 1607.7.1.1 FBC FOR |
| | CONCENTRATED LOADS ANDFURTHER REQUIREMENTS IN |
| | SECTIONS R311 & 312 FBC RES. |
| | |
| | 16)PROVIDE ELEVATIONS FOR NEW GARAGE FLOOR/BEAMS |
| | |
| | 17) PROVIDE REVIEWED AND APPROVED SHOP DRAWINGS FOR |
| | HOLLOW CORE PANELS AND MANUFACTURED STAIRS |
| | |
| | 18)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF |
| | EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. NO |
| | PRODUCT APPROVAL WAS SUBMITTED FOR THE GARAGE DOOR |
| | |
| | 19)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | |
| | 20)THE PRODUCT APPROVAL NOA FOR THE FRENCH DOORS IS |
| | INCOMPLETE, PLEASE SEE THAT THE INFORMATION AT THE TOPS |
| | OF THE DRAWINGS HAS BEEN CUT OFF, THIS INFORMATION IS |
| | REQUIRED FOR ATTACHMENT INSPECTION. |
| | |
| | 21)PER LEVEL 3 ALTERATION IN EXISTING BUILDING CODE |
| | ACCESSIBILITY REQUIREMENTS SHALL MEET CHAPTER 11 FBC |
| | FOR RESIDENTIAL CONSTRUCTION PROVIDE AT MINIMUM 1 |
| | ACCESSIBLE BATHROOM PER R322.1.1 FBC 29" CLEAR WITH |
| | DOOR OPEN 90 DEGREES |
| | |
| | 22)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER |
| | R313.1.1 FBC RES. |
| | |
| | 23)PROVIDE MIN ROOF SHEATHING ATTACHMENT PER |
| | R803.2.3.1 FBC RES. FASTENERS TO BE 4" O/CIN ZONE 3 |
| | FOR WIND DESIGN SPEEDS OVER 130 MPH |
| | |
| | 24)PROVIDE VENTILATION REQUIREMENTS ON DRAWINGS PER |
| | R806.1 AND R806.2 FBC RES. |
| | |
| | 25)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS |
| | REQUIRED PER R807.1 FBC RES. |
| | |
| | 26)SUBMIT A COPY OF THE RECORDED NOTICE OF |
| | COMMENCEMENT TO THE CONSTRUCTION SERVICES DEPARTMENT |
| | |
| | 27)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS |
| | WITH REVISIONS AND INCLUDE 1 COPY OF THE OLD PAGES ONLY |
| | FOR REFERENCE. |
| | |
| | NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006&2007 |
| | AMENDMENTS |
| | FBC* = WEST PALM BEACH ADMINISTRATIVE |
| | AMENDMENTS TO FBC |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | FBC RES. = FLORIDA BUILDING CODE |
| | RESIDENTIAL 2004 W/2006&2007 AMENDMENTS |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |