| Date |
Text |
| 2009-04-05 13:35:56 | |
| | ** DENIED 3RD REVIEW ** |
| | ** SEVERAL NEW NOTES BASED ON REVISED PLANS. SOME ITEMS |
| | WHICH WERE REVISED TO ADDRESS PREVIOUS COMMENTS HAVE |
| | NOW CREATED NEW COMMENTS FOR MANY ITEMS WHICH NEED TO |
| | MEET MINIMUM CODES. |
| | |
| | STORE #50 828 SOUTHERN BLVD. |
| | |
| | |
| | 1) NOTE: THE PLANS SHOW A E PANEL AND EM PANEL BOTH |
| | BEING TAPPED FROM THE ATS. ONLY THE E PANEL CONTAINS |
| | OVER CURRENT PROTECTION FOR THE TAPPED CONDUCTORS. |
| | PANEL EM SHOWN AS MLO. SEE 240.21, 310.16. EC |
| | |
| | |
| | 2) NOTE: PLEASE ALSO SEE 700.9 2005 NEC. PLEASE SEE |
| | HANDBOOK COMMENTARY WHICH WILL PROVIDE MORE |
| | INFORMATION. BASED ON THE RISER AND PANELS, THERE IS |
| | OPTIONAL STAND-BY, AND POSSIBLY LEGALLY REQUIRED |
| | SYSTEMS IN THE SAME EQUIPMENT. SEE E PANEL WHICH SHARES |
| | NUMEROUS OTHER OPTIONAL STAND-BY LOADS. |
| | CODES HAS NOT PERMITTED 700 AND 702 SYSTEMS IN THE SAME |
| | EQUIPMENT FOR MORE THAN TWENTY YEARS. SOME OF THESE |
| | ITEMS HAVE BEEN DONE IN THE LAST TWENTY YEARS AND |
| | PANELS SHOW ADDING MORE OPTIONAL STAND-BY TO PANELS |
| | WHERE LIFE SAFETY WIRING IS LOCATED. |
| | ALL OPTIONAL STAND-BY LOADS NEED TO COME FROM SEPARATE |
| | SYSTEM. |
| | THERE ARE OTHER OPTIONS HOWEVER THIS IS BEING NOTED BY |
| | REVIEWER AS NEEDING TO MEET MINIMUM CODES. |
| | SYSTEMS NEED TO BE LABELED ACCORDINGLY SUCH AS * |
| | OPTIONAL STAND-BY AND LIFE SAFETY. BASED ON PANEL |
| | SCHEDULES SUBMITTED THERE IS LIFE SAFETY, LEGALLY |
| | REQUIRED AND OPTIONAL STAND-BY LOADS. |
| | 700,701, OR 702 SYSTEM LOADS. |
| | |
| | *** IT IS BEING NOTED BY THIS REVIEWER IN ORDER TO NOT |
| | DELAY PROJECT(S) SUBMITTED THAT A MEETING BE HELD AS |
| | SOON AS POSSIBLE TO GO OVER ALL STORES IN SUBMISSION TO |
| | THE CITY OF WEST PALM BEACH. |
| | ONCE RISER AND ALL ELECTRICAL SYSTEMS ARE CORRECTED, |
| | THE GENERATORS THEMSELVES MAY BE UNDER SEPARATE |
| | PERMITS. THIS MAY BE DISCUSSED IN MORE DETAIL ONCE |
| | CONTACT/MEETING HAS BEEN HELD. |
| | |
| | 3) NOTE: LAYOUT FOR ATS, E AND EM NEED TO BE SHOWN ON |
| | PLANS. |
| | 7.2,NFPA-110 , NEC 110.26, 240.24 ETC |
| | |
| | 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS ON THE PROPOSED GENERATOR, GENERATOR ENCLOSURE, |
| | ATS EQUIPMENT. BASED ON COMMENT #2 ABOVE, THERE MAY BE |
| | MORE THAN ONE. |
| | ENCLOSURES SHALL MEET NFPA-110 7.2.1.1 |
| | NEC 110.3, 700.6, 90.7 ETC |
| | |
| | 5) NOTE: FUEL STAND-BY TIME, CAPACITY, SIZING ETC NEEDS |
| | TO BE ON PLANS. MINIMUM TIMES ARE STATED IN NFPA-110 |
| | CHAPTER 4 ALONG WITH NEC 700.12 |
| | |
| | 6) NOTE: PLEASE PROVIDE LOCATION OF DISCONNECT FOR |
| | FEEDERS MEETING 225.31-225.39. IF USING EXCEPTION IN |
| | 700.12B6, 701.11B5, THEN ALL DISCONNECTING MEANS SHALL |
| | BE READILY ACCESSIBLE AND WITHIN SIGHT. BASED ON THE |
| | PLANS THE GENERATOR DOES MEET WITHIN SIGHT HOWEVER AS |
| | NO DISCONNECTING MEANS IS SHOWN NO OTHER CODE |
| | COMPLIANCE CAN BE VERIFIED. THE SHUNT TRIP DOES NOT |
| | MEET 225.38, 225.39. |
| | THE DISCONNECTING MEANS SHALL BE RATED FOR THE LOAD |
| | SERVED. |
| | ** PLEASE BE AWARE THAT ANY BREAKER ON THE GENERATOR |
| | MAY OR MAY NOT MEET READILY ACCESSIBLE DEPENDING ON |
| | LOCKED ENCLOSURE, FENCING AROUND ENCLOSURE ETC. |
| | |
| | 7) NOTE: THE LIGHTING CONTROLS IN BOTH RESTROOMS SHALL |
| | BE DUAL TECHNOLOGY. AS SHOWN IF DEVICES ARE MOTION ONLY |
| | AN OCCUPANT COULD BE OUT OF VIEWING AREA. THIS COULD |
| | CREATE A SAFETY ISSUE. |
| | OTHER DEVICES BEING INSTALLED AS NEW FOR LOCATIONS SUCH |
| | AS COOLERS APPEAR TO BE STANDARD SP SWITCHES. THE |
| | LIGHTING IN THESE AREAS ARE EXEMPT FROM LIGHTING |
| | PERFORMANCE CALCULATIONS HOWEVER ANY NEW BEING |
| | INSTALLED MUST MEET 13-415.1, 13-415.1.ABC.1.1, .1.2 |
| | PLEASE EXPLAIN THE DEVICES WHICH SEEM TO BE A STANDARD |
| | SWITCH WITH AN *A* OR *B* DESIGNATION NEXT TO THEM. ARE |
| | THESE AUTOMATED OVER RIDES? |
| | THE CATALOG NUMBER USED ON PLANS FOR THE WALL DEVICES |
| | WAS NOT READILY LOCATED ON HUBBELL WEBSITE WITH OTHER |
| | DEVICES. |
| | NEW OUTSIDE LIGHTS INDICATE CONTROLS PER ENERGY |
| | MANAGEMENT SYSTEM HOWEVER PLEASE SEE 13-415.1.ABC.1.4. |
| | DOES THIS PROVIDE 10HRS MINIMUM BACK UP FOR SCHEDULING |
| | OR MEET PHOTO-SENSOR REQUIREMENTS? IF THIS WAS THE ONLY |
| | ITEM IT WOULD HAVE BEEN REDLINED. |
| | |
| | 8) NOTE: CODES ON PLANS NEED TO INCLUDE NFPA-110 2002. |
| | ( ON ELECTRIC HOWEVER NOT ON COVER) THIS CAN BE |
| | REDLINED) |
| | |
| | 9) NOTE: NEW NOTE, PLUMBING PLANS SHOW NEW LINES FOR |
| | GAS TO NEW LS GENERATOR. PLEASE BE SURE TO SEE 7.9 OF |
| | NFPA-110, MORE SPECIFICALLY 7.9.3.1. *** THIS IS NOTED |
| | FOR INFORMATION, AS THE GAS REVIEW WILL BE DONE BE THE |
| | PLUMBING PLANS EXAMINERS. LIFE SAFETY SYSTEMS ARE UNDER |
| | REVIEW OF FIRE MARSHAL, BUILDING AND ELECTRICAL PLANS |
| | EXAMINERS. |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |