Plan Review Notes For Permit 08070557
Permit Number 08070557
Review Stop M
Sequence Number 2
Notes
Date Text
2008-09-18 09:45:12REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. DETAIL HAS BEEN PROVIDED IN STRUCTURAL PAGES SHOWING
 HOW THE CURBS FOR NEW AHU AND CU ARE TO BE ATTACHED TO
 EXISTING CURB AS WELL AS FOR THE NEW REMOTE CONDENSERS
 TO THE STANDS. HOWEVER, THE NOTES ON PAGE S-2 CALL FOR
 THE APPLIANCE MANUFACTURER TO PROVIDE SHOP DRAWINGS
 WITH THE ATTACHMENT DETAILS FOR THE APPLIANCES TO THE
 CURBS AND/OR STANDS. NO SUCH INFORMATION WAS PROVIDED
 WITH THIS SUBMISSION FOR REVIEW. ALSO, NO INFORMATION
 WAS PROVIDED FROM THE APPLIANCE/EQUIPMENT MANUFACTURERS
 SHOWING THE PROPOSED APPLIANCES THEMSELVES ARE DESIGNED
 TO RESIST WIND PRESSURES. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 AS DETERMINED IN ACCORDANCE WITH FBCM 301.13. PROVIDE
 ALL DOCUMENTATION NECESSARY TO DEMONSTRATE COMPLIANCE
 WITH THESE REQUIREMENTS FOR REVIEW.
 NOTE: THIS REQUIREMENT ALSO APPLIES TO THE PROPOSED NEW
 GREASE EXHAUST FAN F-3.
  
 2. OK
  
 3. OK
  
 4. OK
  