| 2008-08-07 13:09:55 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | REVIEWED FOR COMPLIANCE WITH THE FOLLOWING: |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. NO DETAIL WAS PROVIDED REGARDING INSTALLATION OF NEW |
| | AHU 2 AND CU 2 ON EXISTING ROOF CURB(S). PROVIDE WIND |
| | LOAD DATA AND ATTACHMENT DETAIL. MECHANICAL EQUIPMENT |
| | AND APPLIANCES THAT ARE EXPOSED TO WIND SHALL BE |
| | DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES AS |
| | DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, BUILDING PER FBCM 301.13. |
| | ALSO, PROVIDE DOCUMENTATION FROM THE |
| | EQUIPMENT/APPLIANCE MANUFACTURER SHOWING THE |
| | EQUIPMENT/APPLIANCES ARE DESIGNED TO RESIST WIND |
| | PRESSURES IN ACCORDANCE WITH THIS SECTION. |
| | |
| | 2. PAGE M-5 A/C EQUIPMENT SCHEDULE SHOWS THE AHU AT |
| | 8000 CFM WITH A FAN MOTOR RATED AT 10 HP. THIS GIVES A |
| | RATIO OF 1.25 HP PER 1000 CFM. THIS EXCEEDS THE FAN |
| | POWER LIMITATION LISTED IN TABLE 13-410.1.ABC.1.1.1. IF |
| | CLAIMING CONDITION 2 OR 3 UNDER THIS SECTION, PROVIDE |
| | SUPPORTING CALCULATIONS AS LISTED IN THIS SECTION. |
| | |
| | 3. DETAIL 1 PG M-5 SHOWS A NEW GRIDDLE UNDER NEW GH-1. |
| | HOWEVER, GH-1 HOOD NOTES CALLS FOR A NEW ROTISSERIE TO |
| | BE INSTALLED UNDER THIS HOOD. PLEASE CLARIFY. A |
| | ROTISSERIE IS LIKELY TO BE MUCH LARGER THAN THE GRIDDLE |
| | SHOWN. THE INSIDE LOWER EDGE OF CANOPY-TYPE COMMERCIAL |
| | COOKING HOODS SHALL OVERHANG OR EXTEND A HORIZONTAL |
| | DISTANCE OF NOT LESS THAN 6 INCHES BEYOND THE EDGE OF |
| | THE COOKING SURFACE IN ACCORDANCE WITH FBCM 507.12. |
| | |
| | 4. FAN SCHEDULE PG M-5: NOTE #3 FOR GREASE EXHAUST FAN |
| | F-3 CALLS FOR THE FAN TO BE UL 705 LISTED. GREASE |
| | EXHAUST FANS SHALL BE LISTED AND LABELED IN ACCORDANCE |
| | WITH UL 762 PER FBCM 506.5.1.1. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |