| Plan Review Notes For Permit 08070557 |
| Permit Number |
08070557 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-08-15 15:54:13 | ***DENIED*** | | | | | | 1) PLEASE INDICATE DOORS PROVIDED WITH PANIC HARDWARE | | | ON DOOR SCHEDULE. PANIC HARDWARE IS INDICATED ON EXIT | | | ANALYSIS PLAN. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | 3) PLEASE CLARIFY THE SCOPE OF WORK REGARDING THE FIRE | | | ALARM SYSTEM. SOME NEW EQUIPMENT IS SHOWN BUT CONTROL | | | PANEL ILLUSTRATES AS EXISTING TO REMAIN. | | | | | | 4) ILLUMINATED EXIT SIGNS SHALL BE PROVIDED AT | | | DISTANCES NOT TO EXCEED 100'. | | | | | | 5) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR | | | HANDRAILS AND GUARDS. | | | | | | 6) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH THE REQUIREMENTS OF NFPA 241. | | | | | | 7) CLARIFY IF HOOD EQUIPMENT IS FOR WARMING ONLY AS | | | PLANS INDICATE GREASE HOOD. PLANS DO NOT INDICATE | | | SUPPRESSION SYSTEM. | | | | | | 8) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|