Plan Review Notes
Plan Review Notes For Permit 08070557
Permit Number 08070557
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-08-15 15:54:13***DENIED***
  
 1) PLEASE INDICATE DOORS PROVIDED WITH PANIC HARDWARE
 ON DOOR SCHEDULE. PANIC HARDWARE IS INDICATED ON EXIT
 ANALYSIS PLAN.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
 3) PLEASE CLARIFY THE SCOPE OF WORK REGARDING THE FIRE
 ALARM SYSTEM. SOME NEW EQUIPMENT IS SHOWN BUT CONTROL
 PANEL ILLUSTRATES AS EXISTING TO REMAIN.
  
 4) ILLUMINATED EXIT SIGNS SHALL BE PROVIDED AT
 DISTANCES NOT TO EXCEED 100'.
  
 5) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR
 HANDRAILS AND GUARDS.
  
 6) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH THE REQUIREMENTS OF NFPA 241.
  
 7) CLARIFY IF HOOD EQUIPMENT IS FOR WARMING ONLY AS
 PLANS INDICATE GREASE HOOD. PLANS DO NOT INDICATE
 SUPPRESSION SYSTEM.
  
 8) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756