Plan Review Notes
Plan Review Notes For Permit 08070557
Permit Number 08070557
Review Stop E
Sequence Number 1
Notes
Date Text
2008-08-11 13:25:40 
 ** DENIED **
  
 1) NOTE: PLEASE CONFIRM LICENSING OF THE FIRM AS
 LISTED. THE CERTIFICATE OF AUTHORIZATION NUMBER SHOWN
 IS LISTED FOR POST, BUCKLEY, SCHUH AND JERNIGAN, INC AT
 A LOCATION OTHER THAN LISTED ON PLANS. THE FIRM NAME AS
 LISTED ALONG WITH ADDRESS IS NOT LISTED ON STATE
 WEBSITE.
 PLEASE ALSO INDICATE THE ARCHITECTURAL FIRM LICENSE
 NUMBER THE NUMBER AS LISTED DOES COME UP ON WEBSITE FOR
 ENGINEERING FIRM HOWEVER NOT FOR ARCHITECTURAL
 BUSINESS.
 PLEASE SEE FS 471.023 (ENG) FS 481.219 (ARCH) AND FAC
 61G15-23.002, 61G1-16.004.
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED
 ON THE ELECTRICAL PLANS AS WELL AS CORRECTING COVER
 SHEETS.
 PLEASE SEE THE COVER SHEET AS IT STATES A 2004 NEC. YET
 THERE IS NO SUCH CODE.
 THE LIFE SAFETY PLAN HOWEVER DOES LIST THE 2005 NEC.
  
 2004 FBC W/2007 REVISIONS.
 2003 NFPA-101
 2002 NFPA-72
  
 3) NOTE: PLEASE INDICATE THE REQUIRED BATTERY BACK UP
 LIGHTING FOR EGRESS PATHS IN AREAS IN WHICH WORK IS
 BEING DONE. AS THIS LOCATION IS A LOCATION IN WHICH
 OCCUPANCY WILL OCCUR UNDER GENERATOR POWER IN ANY EVENT
 OF POWER FAILURE BATTERY BACK UP LIGHTING FOR 1FT
 CANDLE MINIMUM FOR EGRESS PATHS WILL BE REQUIRED.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.1, .2.2.
  
 ** NORMAL OCCUPANCY IS BEING PROPOSED IN THIS LOCATION
 UNDER EMERGENCY POWER. IN THIS SITUATION LOSING THE
 *EMERGENCY* BACK UP WOULD CAUSE ALL EGRESS AREAS TO
 HAVE NO LIGHTING WHICH IS A LIFE SAFETY SITUATION.
  
 ** IF EGRESS LIGHTING IS CURRENTLY PROVIDED WITH
 BATTERY BACK UP MEETING THE LIFE SAFETY CODE IN ANY
 AREAS, PLEASE INDICATE.
 AT THIS TIME NO KNOWN BATTERY BACK UP POWER FOR MAIN
 AREAS ARE KNOWN TO BE BATTERY BACK UP.
  
 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS IN AREAS IN WHICH NEW LIGHTING IS BEING
 INSTALLED.
 PLEASE SEE13-415.2.ABC.1.1, .1.2.
  
 5) NOTE: PLEASE PROVIDE HOW LIGHTING CONTROLS FOR NEW
 BEING INSTALLED MEET SECTIONS 13-415.1.ABC.1.1,.1.2 AND
 .1.3.
  
 6) NOTE: PLEASE SEE SHEET E-6 AS THIS DOES NOT
 CORRELATE WITH THE INFORMATION ON THE RISER DIAGRAM
 SHEET E-7.
 FOR EXAMPLE:
 E-6 SHOWS CU #4, YET RISER SHEET DOES NOT INDICATE ANY
 CU#4.
  
 FOR EXAMPLE:
 PLEASE SEE E-7 AS A NOTE MENTIONS NEW WORK TO BE SHADED
 IN BLACK LINES. HOWEVER BASED ON NEW UNITS AND
 ELECTRICAL EQUIPMENT SHOWN ON E-6 THIS IS NOT DONE.
 PLEASE COORDINATE ALL.
  
 7) NOTE: PLEASE UPDATE THE ELECTRICAL RISER DIAGRAM
 WITH THE ACTUAL ELECTRICAL ON-SITE.
 230, ETC
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]