2008-08-12 13:27:34BUILDING PLAN REVIEW
 PERMIT: 08070557
 ADD: 828 SOUTHERN BLVD.
 CONT: OAK CONSTRUCTION
 TEL: (954)583-9625
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 AUGUST 12, 2008
 1STREVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2)PBS & J NO CERTIFICATE OF AUTHORIZATION WAS FOUND
 FOR A ARCHITECTS OFFICE, NO CERTIFICATE OF
 AUTHORIZATION WAS FOUND FOR PBS & J (DBA) FOR AN
 ENGINEERS OFFICE. THERE IS CURRENTLY A CERTIFICATE OF
 AUTHORIZATION FOR POST, BUCKLEY, SCHUH & JEERNIGAN,
 INC.
 481.219 F.S.CERTIFICATE OF AUTHORIZATION.
 (ARCHITECTS)THE TITLE BLOCK FOR ANY SHEET BEARING THE
 NAME OF AN ARCHITECT PRACTICING UNDER A FICTITIOUS
 NAME, A CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER.ADD THE NUMBER TO EACH
 SHEET.
 THIS MAY BE ADDED BY HAND.
 471.023 F.S.CERTIFICATE OF AUTHORIZATION. (ENGINEER)
 THE TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN
 ENGINEER PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3) SHEET A-1 INDICATES TWO ACCESSIBLE RAMPS DETAIL
 8/A-13 AND DETAIL 10/ A-13 NEITHER RAMP INDICATES THE
 LENGTH OF THE BOTTOM LANDING. 11-4.8.4.(2) LANDINGS.
 ALL LANDINGS ON RAMPS SHALL NOT BE LESS THAN 60" CLEAR,
 & THE BOTTOM OF EACH RAMP SHALL HAVE NOT LESS THAN 72"
 OF STRAIGHT & LEVEL CLEARENCE.
  
 4) S-2 GENERAL NOTE (5)INDICATESWIND DESIGN TO THE
 ASCE 7-05, THE 2004 FBC RECOGNIZES THE ASCE 7-02. 004
 FBC CHAPTER 35 REFERENECED STANDARDS RECOGNIZES ASCE
 7-02 .ALSO 1603.1.4 WIND DESIGN DATA.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.