2008-08-29 13:51:26****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 1. INSTALLATION SCHEDULE WAS COMPLETED, BUT NOTE THE
 FOLLOWING:
  
 A. SHUTTER CONNECTION MOUNTING TYPE SHOULD REFER TO THE
 TYPE OF CONNECTION USED, NOT FASTENER. YOU HAVE MARKED
 A-A ON THE PRODUCT APPROVAL, SEE SHEET 3.
 B. A-A REQUIRES USE OF CHART 1 FOR CONCRETE BLOCK; YOU
 HAVE USED CHART 3. CHECK ALL; OTHER INFORMATION MAY BE
 INCORRECT. THE SCHEDULE IS SPOT CHECKED; IT DOES NOT
 HAVE ALL INFORMATION SO EVEN A SPOT CHECK IS DIFFICULT.
 C. SPECIFIC ANCHOR TYPE SHOULD INCLUDE THE VERY BASIC
 INFORMATION FROM THE PRODUCT APPROVAL; IN THIS CASE,
 1/4" TAPCON WOULD SUFFICE.
 D. YOU'VE SPECIFIED A TAPCON LENGTH. PLEASE BE ADVISED
 THAT THE TRACK AND STUCCO MUST BE ADDED TO THE MINIMUM
 EMBEDMENT REQUIRED ON THE PRODUCT APPROVAL, SHEET 7.
 E. A 2" EDGE DISTANCE REQUIRES A FACTOR OF .71, SEE
 SHEET 7.
 THANK YOU FOR PROVIDING TWO SETS. WHEN RESUBMITTING,
 PLEASE BE SURE THAT TWO COMPLETE COLLATED SETS OF
 DOCUMENTS ARE IN THE PACKAGE.
  
 2. ADDRESSED.
  
 3. FROM PREVIOUS LIST, NOTE EXISTING CONDITIONS (TYPE
 OF WINDOW) AND OPENING SIZE FOR BEDROOMS, FBC R310, FBC
 EB 505.1. PLEASE STATE WHAT TYPE OF WINDOW WAS ON THE
 HOUSE BEFORE THEY WERE CHANGED WITHOUT A PERMIT. TYPE
 OF WINDOW WOULD BE JALOUSY, SINGLE HUNG, ETC.
  
 4. FROM PREVIOUS LIST; ON THE INSTALLATION SCHEDULE,
 THE SHUTTER CONNECTION MOUNTING TYPE IS TO CORRELATE
 WITH THE ANCHOR SCHEDULE; FOR INSTANCE, A THROUGH G,
 SEE DETAILS ON PRODUCT APPROVAL. THIS COMMENT WAS NOT
 ADDRESSED, SEE OTHER COMMENTS.
  
  