Plan Review Notes
Plan Review Notes For Permit 08070549
Permit Number 08070549
Review Stop B
Sequence Number 1
Notes
Date Text
2008-08-04 15:09:15****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 1.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR
 PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT, FBC*106.TWO SETS REQUIRED.
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 2.PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS
 WILL BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH
 THE INSTALLATION SCHEDULE, ITEM 1 ABOVE.AN
 INSTALLATION SCHEDULE WAS SUBMITTED WITH ONE OPENING,
 BUT ALL OF THE WINDOWS ARE TO HAVE IMPACT PROTECTION
 FBC R301.
  
 3.PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 505.1.
  
 4.ON THE INSTALLATION SCHEDULE, THE SHUTTER
 CONNECTION MOUNTING TYPE IS TO CORRELATE WITH THE
 ANCHOR SCHEDULE; FOR INSTANCE, A THROUGH G, SEE DETAILS
 ON PRODUCT APPROVAL.