Plan Review Notes
Plan Review Notes For Permit 08070548
Permit Number 08070548
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-08-04 15:17:51*****DENIED*****
  
  
 1.ALL POWER SUPPLIES TO THE FIRE ALARM SYSTEM SHALL
 BE INSTALLED IN ACCORDANCE WITH NFPA 70, NATIONAL
 ELETRICAL CODE, 2002 EDITION.
  
 2.THE FIRE ALARM SYSTEM SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 72, NATIONAL FIRE ALARM CODE, 2002
 EDITION.
  
 3.EQUIPMENT SHALL BE INSTALLED IN LOCATIONS WHERE
 CONDITIONS DO NOT EXCEED THE VOLTAGE, TEMPERATURE, AND
 HUMIDITY LIMITS SPECIFIED IN 4.4.4.1 OF NFPA 72.DOES
 THE UTILITY CLOSET MEET THESE SPECIFICATIONS?
  
 4.PROVIDE SPEC SHEETS/INFORMATION ON THE NEWLY
 INSTALLED FIRE ALARM PANEL AND SMOKE DETECTOR.
  
 5.WHAT MEANS WILL THERE BE TO PREVENT UNAUTHORIZED
 ACCESS TO OR TAMPERING WITH THE FIRE ALARM PANEL.
  
 6.SIGNAGE SHALL BE REQUIRED INDICATING THE LOCATION
 OF THE FIRE ALARM PANEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW THE COMMENTS WERE
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW