Plan Review Notes
Plan Review Notes For Permit 08070532
Permit Number 08070532
Review Stop M
Sequence Number 1
Notes
Date Text
2008-07-23 12:20:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLAN TWO OF 4 SHOWS TWO 20X30 R/A TRANSFER GRILLS
 OPEN TO THE CORRIDOR, PER 2004 FBC 1016.1 CORRIDORS
 SHALL BE FIRE-RESISTANCE RATED IN ACCORDANCE WITH TABLE
 1016.1. THE CORRIDOR WALLS REQUIRED TO BE
 FIRE-RESISTANCE RATED SHALL COMPLY WITH SECTION 708 FOR
 FIRE PARTITIONS, OR MEET THE EXCEPTIONS. AND PER
 MECHANICAL CODE 607.5.3 DUCT PENETRATIONS IN FIRE
 PARTITIONS SHALL BE PROTECTED WITH APPROVED FIRE
 DAMPERS INSTALLED IN ACCORDANCE WITH THEIR LISTING.
 PLEASE CORRECT OR ADDRESS COMMENT.
  
 2) PER 2004 FBC 716.5.4.1 CORRIDORS.
 A LISTED SMOKE DAMPER DESIGNED TO RESIST THE PASSAGE OF
 SMOKE SHALL BE PROVIDED AT EACH POINT A DUCT OR AIR
 TRANSFER OPENING PENETRATES A CORRIDOR ENCLOSURE
 REQUIRED TO HAVE SMOKE AND DRAFT CONTROL DOORS IN
 ACCORDANCE WITH SECTION 715.3.3. AND PER MECHANICAL
 CODE 607.5.4 CORRIDORS/SMOKE BARRIERS. A LISTED SMOKE
 DAMPER DESIGNED TO RESIST THE PASSAGE OF SMOKE SHALL BE
 PROVIDED AT EACH POINT A DUCT OR AIR TRANSFER OPENING
 PENETRATES A SMOKE BARRIER WALL OR A CORRIDOR ENCLOSURE
 REQUIRED TO HAVE SMOKE AND DRAFT CONTROL DOORS IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
 SMOKE DAMPERS AND SMOKE DAMPER ACTUATION METHODS SHALL
 COMPLY WITH SECTION 607.5.4.1 OR MEET THE EXCEPTIONS.
 PLEASE CORRECT OR ADDRESS COMMENT.
  
 3) PLEASE SHOW THE CFM'S AT ALL NEW SUPPLY AIR GRILLS,
 PER 2004 FBC/M 603.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]