| 2008-07-23 12:20:14 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) PLAN TWO OF 4 SHOWS TWO 20X30 R/A TRANSFER GRILLS |
| | OPEN TO THE CORRIDOR, PER 2004 FBC 1016.1 CORRIDORS |
| | SHALL BE FIRE-RESISTANCE RATED IN ACCORDANCE WITH TABLE |
| | 1016.1. THE CORRIDOR WALLS REQUIRED TO BE |
| | FIRE-RESISTANCE RATED SHALL COMPLY WITH SECTION 708 FOR |
| | FIRE PARTITIONS, OR MEET THE EXCEPTIONS. AND PER |
| | MECHANICAL CODE 607.5.3 DUCT PENETRATIONS IN FIRE |
| | PARTITIONS SHALL BE PROTECTED WITH APPROVED FIRE |
| | DAMPERS INSTALLED IN ACCORDANCE WITH THEIR LISTING. |
| | PLEASE CORRECT OR ADDRESS COMMENT. |
| | |
| | 2) PER 2004 FBC 716.5.4.1 CORRIDORS. |
| | A LISTED SMOKE DAMPER DESIGNED TO RESIST THE PASSAGE OF |
| | SMOKE SHALL BE PROVIDED AT EACH POINT A DUCT OR AIR |
| | TRANSFER OPENING PENETRATES A CORRIDOR ENCLOSURE |
| | REQUIRED TO HAVE SMOKE AND DRAFT CONTROL DOORS IN |
| | ACCORDANCE WITH SECTION 715.3.3. AND PER MECHANICAL |
| | CODE 607.5.4 CORRIDORS/SMOKE BARRIERS. A LISTED SMOKE |
| | DAMPER DESIGNED TO RESIST THE PASSAGE OF SMOKE SHALL BE |
| | PROVIDED AT EACH POINT A DUCT OR AIR TRANSFER OPENING |
| | PENETRATES A SMOKE BARRIER WALL OR A CORRIDOR ENCLOSURE |
| | REQUIRED TO HAVE SMOKE AND DRAFT CONTROL DOORS IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING. |
| | SMOKE DAMPERS AND SMOKE DAMPER ACTUATION METHODS SHALL |
| | COMPLY WITH SECTION 607.5.4.1 OR MEET THE EXCEPTIONS. |
| | PLEASE CORRECT OR ADDRESS COMMENT. |
| | |
| | 3) PLEASE SHOW THE CFM'S AT ALL NEW SUPPLY AIR GRILLS, |
| | PER 2004 FBC/M 603.2. |
| | |