| Notes |
| Date |
Text |
| 2008-08-05 13:00:59 | BUILDING PLAN REVIEW | | | PERMIT: 08070532 | | | ADD: 1101 S. FLAGLER DR. | | | CONT: CREATIVE CONSTRUCTION CORP. | | | TEL: (561)842-5311 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 8-5-08 | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) PROVIDE A DOOR SCHEDULE FOR THE NEW DOORS INDICATING | | | THE TYPES OF LOCKS, FIRE RATING AND THE AMOUNT OF | | | GLAZING PER DOOR IN ACCORDANCE WITH TABLE 715.4.3. | | | | | | 3) 715.3.3 DOORS LOCATED IN CORRIDORS WALLS OR SMOKE | | | BARRIER WALLS HAVING A FIRE-RESISTANCE RATING IN | | | ACCORDANCE WITH TABLE 715.3 SHALL BE TESTED IN | | | ACCORDANCE WITH NFPA 252 OR UL 10C. | | | | | | 4) IS ANY OF THE CMU WALL BEING DEMOED LOAD BEARING | | | WALLS? PROVIDE DETAIL DRAWINGS SHOWING THESE WALLS | | | BEING DEMOED WILL NOT AFFECT THE MAIN STRUCTURE. ALSO, | | | SHOW THE WALLS WERE ATTACHED TO THE STRUCTURE ABOVE. | | | ADDITIONAL INFORMATION REQUIRED 106.1.2* | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|