Plan Review Notes
Plan Review Notes For Permit 08070532
Permit Number 08070532
Review Stop B
Sequence Number 1
Notes
Date Text
2008-08-05 13:00:59BUILDING PLAN REVIEW
 PERMIT: 08070532
 ADD: 1101 S. FLAGLER DR.
 CONT: CREATIVE CONSTRUCTION CORP.
 TEL: (561)842-5311
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 8-5-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PROVIDE A DOOR SCHEDULE FOR THE NEW DOORS INDICATING
 THE TYPES OF LOCKS, FIRE RATING AND THE AMOUNT OF
 GLAZING PER DOOR IN ACCORDANCE WITH TABLE 715.4.3.
  
 3) 715.3.3 DOORS LOCATED IN CORRIDORS WALLS OR SMOKE
 BARRIER WALLS HAVING A FIRE-RESISTANCE RATING IN
 ACCORDANCE WITH TABLE 715.3 SHALL BE TESTED IN
 ACCORDANCE WITH NFPA 252 OR UL 10C.
  
 4) IS ANY OF THE CMU WALL BEING DEMOED LOAD BEARING
 WALLS? PROVIDE DETAIL DRAWINGS SHOWING THESE WALLS
 BEING DEMOED WILL NOT AFFECT THE MAIN STRUCTURE. ALSO,
 SHOW THE WALLS WERE ATTACHED TO THE STRUCTURE ABOVE.
 ADDITIONAL INFORMATION REQUIRED 106.1.2*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]