Plan Review Notes
Plan Review Notes For Permit 08070485
Permit Number 08070485
Review Stop P
Sequence Number 1
Notes
Date Text
2008-07-17 16:16:33PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-3.01 DETAIL #3 LOUNGE SINK: PLEASE ADD THE
 FOLLOWING FOR THE ADA COMPLIANT LOUNGE SINK ON THE
 ELEVATION DETAIL PER FBC- CHAPTER 11, SECTIONS.
  
 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE,
 AND 19" DEEP.
  
 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
  
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
  
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
  
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
  
 2. SHEET A-3.01 DETAIL #9 NEW ADA COMPLIANT LAVATORY
 DETAIL FOR EXISTING RESTROOM #110: PLEASE ADD THE
 FOLLOWING FOR THE ADA COMPLIANT LAVATORY ON THE
 ELEVATION DETAIL REQUIRED PER FBC- CHAPTER 11,
 SECTIONS.
  
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
  
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
  
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
  
 3. SHEET P-1 PLUMBING PLAN PLEASE ADD THE FOLLOWING
 PER FBC-PLUMBING SECTIONS.
  
 A} THE UNDERGROUND POTABLE HOT AND COLD WATER IS
 MISSING TO THE SHAMPOO STATIONS. PER SECTION 601.1
 SCOPE.
  
 B} THE REQUIRED TWO-WAY CLEANOUTS AT THE JUNCTION OF
 THE BUILDING DRAIN AND BUILDING SEWER ARE MISSING FROM
 THE SANITARY PIPES IN SUITE #103 & #104. PER FBC-
 PLUMBING SECTION 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION.
  
 4. SHEET P-2 SANITARY RISER DIAGRAM: THE REQUIRED
 TWO-WAY CLEANOUTS AT THE JUNCTION OF THE BUILDING DRAIN
 AND BUILDING SEWER ARE MISSING FROM THE SANITARY PIPES
 IN SUITE #103 AND #104. PER FBC- PLUMBING SECTION
 708.3.5 BUILDING DRAIN AND BUILDING SEWER JUNCTION.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]