| Plan Review Notes For Permit 08070467 |
| Permit Number |
08070467 |
|
| Review Stop |
E |
| Sequence Number |
9 |
|
| Notes |
| Date |
Text |
| 2009-09-07 10:06:31 | | | | ** DENIED REVIEW OF REVISIONS** | | | | | | ** PLANS ARE FOR FINAL. NEED TO SHOW ALL ITEMS AS NOTES | | | BELOW. | | | | | | 1) NOTE: PLEASE SEE REDLINED PLANS NOTES FROM PREVIOUS | | | REVIEW DATED 7/28/09 WITH RESPECT TO DISCONNECTS ON | | | SHEETS NOT COORDINATING WITH RISER. | | | | | | 2) NOTE: PLANS HAVE NOW BEEN REVISED FOR 3RD FLOOR | | | REMOVING MOST LIGHTING EXCEPT FOR EGRESS PATH TO EXITS. | | | HOWEVER NO LIGHTING CONTROLS FOR THESE LIGHTS ARE | | | SHOWN? | | | PLEASE SEE FBC 13-415.1.ABC.1.1,.1.2 ( 2004 FBC. ) | | | PLEASE ALSO SEE FBC 1006.1.2 AND NFPA-101 7.8.1.2.2 FOR | | | ANY AUTOMATED CONTROLS SUCH AS OCCUPANCY SENSORS WHICH | | | SHALL BE *FAIL SAFE ON* TYPE DEVICES. | | | | | | 3) NOTE: THIS IS NOTED FOR INFORMATION ONLY. ASME-17 | | | FOR ELEVATOR LOBBY LIGHTING AT SILLS/LANDINGS. STATE | | | ELEVATOR LIGHTING LEVELS. | | | THIS IS NOTED ONLY. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|