| 2008-10-24 07:46:20 | BUILDING PLAN REVIEW |
| | PERMIT: 08070467 |
| | ADD: 303 BANYAN BLVD |
| | CONT: LCI CONSTRUCTION |
| | TEL: (561)307-4951 |
| | |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 3RD REVIEW |
| | ACTION: DENIED |
| | OCT. 24, 2008 |
| | 1A) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1E) COMPLIED. |
| | |
| | 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| | OF OCCUPANCY: |
| | A) COMPLIED. |
| | B) COMPLIED. |
| | C) COMPLIED. |
| | D) COMPLIED |
| | E) COMPLIED. |
| | F) COMPLIED |
| | G) COMPLIED |
| | H) COMPLIED |
| | I) COMPLIED. |
| | |
| | 3)COMPLIED, VALUE OF $850,000.00. |
| | |
| | 4-7) COMPLIED. |
| | |
| | 8)SEMI-COMPLIED, THESE ARE NEW PRODUCT APPROVALS WITH |
| | NEW ISSUES. 609.1.4 PROTECTION OF OPENINGS IN |
| | WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT |
| | RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3 |
| | M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE |
| | BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING |
| | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT |
| | RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR |
| | PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE |
| | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996, |
| | OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN |
| | AS FOLLOWS: 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET |
| | (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF THE |
| | LARGE MISSILE TEST. 2. GLAZED OPENINGS LOCATED MORE |
| | THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE |
| | PROVISIONS OF THE SMALL MISSILE TEST. |
| | |
| | FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE3 |
| | COPIES,OF PRODUCT APPROVALS YOUR PROJECT IS A THRESHOLD |
| | BUILDING REQUIRING (3) PRODUCT TESTING REPORTS, MISSING |
| | REPORTS ARE AS FOLLOWS: |
| | 8A) STOREFRONT NOA 03-0801.04 MISSILE IMPACT RARING: |
| | NONE/ REQUIRES SHUTTERS |
| | 8B) CURTAIN WALL SYSTEM SMALL MISSILE RATING IT APPEARS |
| | THIS SYSTEM WILL BE USED ONLY AT THE FRONT ENTRY |
| | REQUIRING LARGE MISSILE IMPACT |
| | 8C) DOORS GLAZED- COMPLIED |
| | 8D) DOORS LOUVERS NO SUBMITTALS |
| | 8E) METAL INSULATED EXTERIOR DOORS- NO SUBMITTALS |
| | 8F) LOUVERS- COMPLIED |
| | 8G) STORM SHUTTERS/ USE OF WINDOWS WITH OUT LARGE |
| | MISSILE IMPACT |
| | |
| | 8H) IN LEAU OF LARGE MISSLE IMPACT RATED WINDOWS, STORM |
| | SHUTTERS MAY BE USED ON THE FIRST FLOOR IF: 104.6*/ |
| | 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE DEBRIS IMPACT |
| | PROTECTION |
| | PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR |
| | WIND-BORNE DEBRIS IMPACT PROTECTION QUESTION# 13 |
| | RECOGNIZING SUCH CONCERNS AS ABSENTEE OWNERS, OR CASES |
| | WHERE LONGER TIME & EFFORT IS NECESSARY TO SECURE |
| | SHUTTERS ON LARGE OR MULTI-STORY BUILDINGS, WHAT |
| | MEASURES ARE BEING RECOMMENDED OR IMPLEMENTED TO ENSURE |
| | THAT COMPLETE INSTALLATION OR SECURING IS DONE |
| | SUFFICIENTLY IN ADVANCE OF THE HURRICANE? |
| | |
| | IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE |
| | GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE, |
| | SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING, |
| | CHAPTER 1, |
| | ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY |
| | OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE |
| | BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR |
| | ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION |
| | OF EXISTING BUILDINGS. |
| | |
| | IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR |
| | MULTI-STORY BUILDINGS, OR MULTIPLE |
| | ON THE SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST |
| | BE SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS |
| | FOR REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY |
| | SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION |
| | OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE |
| | SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH |
| | COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND |
| | THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS. |
| | PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN |
| | TWELVE (12) HOURS OR LESS OF THE |
| | OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES |
| | OF A HURRICANE WATCH. |
| | |
| | PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD) |
| | ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE |
| | MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO |
| | REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN |
| | QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE, |
| | DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED |
| | UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE |
| | MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE |
| | BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO |
| | SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE. |
| | |
| | PROVIDE STORM PANEL INFORMATION WITH INSTALLATION |
| | SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND |
| | MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC |
| | 1606.1.4. FL BLD CODE 2004 SECTION 106.3.3, |
| | 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE |
| | SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS, |
| | UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR |
| | REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT |
| | TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT |
| | APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | 9-15) COMPLIED |
| | |
| | 16) NEW COMMENT: REVISION TO PLANS SHEET A2.1 & A2.2 |
| | BOTH INDICATE A CHANGE FROM STONE REVEAL AND MOLDINGS |
| | TO A FOAM TRIM PLEASE SEE 1406.2.2. USE OF FOAM |
| | MOLDINGS OR TRIM ABOVE 40 FEET. |
| | ARCHITECTURAL TRIM THAT EXCEEDS 40 FEET (12 192 MM) IN |
| | HEIGHT ABOVE GRADE PLANE SHALL BE CONSTRUCTED OF |
| | APPROVED NONCOMBUSTIBLE MATERIALS. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |