| 2008-09-10 16:06:12 | |
| | |
| | |
| | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ALONG |
| | WITH NEW NOTES DUE TO INFORMATION NOW SHOWN ON PLANS |
| | WHICH WAS NOT ON PREVIOUS PLANS. |
| | |
| | 1) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE LEVELS FOR |
| | EACH FLOOR NEEDS TO BE SHOWN. THE AMOUNT OF LIGHTING IN |
| | DESIGN DOES NOT EXCEED ALLOWANCE PER 13-415.2.C TABLE |
| | HOWEVER THE TOTAL DESIGN WATTAGE IS ABOUT HALF OF THE |
| | ACTUAL WATTAGE FOR EACH FLOOR BASED ON THE FIXTURES ON |
| | THE SCHEDULE. |
| | 13-415.2.ABC.2.1, .2.2. |
| | |
| | 2) NOTE: PLEASE COMPLETE ALL FIXTURES ON PLANS. FOR |
| | EXAMPLE THERE ARE A COUPLE OF FIXTURES WITH NOT |
| | DESIGNATIONS AT ALL. *3RD FLOOR SOUTHEAST CORNER, AND |
| | 4TH FLOOR CENTER. THESE COULD BE *ASSUMED* HOWEVER |
| | PLANS NEED TO BE SPECIFIC. |
| | ** THIS IS ONLY A NOTE, HOWEVER THERE IS ONLY *ONE* |
| | TYPE *A* FIXTURE. ALL FIXTURES ON LIGHTING PLANS ARE |
| | SHOWN AS *AE* WITH THE EXCEPTIONS AS NOTED. |
| | PLEASE COORDINATE. |
| | **** PLEASE COORDINATE THE FIXTURE DESIGNATIONS AND |
| | OTHER INFORMATION FOR FIXTURES ON THE PHOTO-METRIC |
| | PLANS WITH THE LIGHTING PLANS. THE NORMAL LIGHTING |
| | LEVEL PHOTO-METRIC PLANS CALL FOR ALL TYPE *A* FIXTURES |
| | YET THIS DOES NOT CORRESPOND TO LIGHTING PLANS. THIS |
| | WAS NOTED PREVIOUSLY AND RESPONSE MENTIONS THIS WAS |
| | CORRECTED HOWEVER BASED ON PLANS SUBMITTED THIS IS NOT |
| | THE CASE. |
| | 13-415.2.ABC.1.1, .1.2. |
| | FBC 106.1.1 FOR CLARITY AND COORDINATION. |
| | |
| | 3) NOTE: PLEASE SEE 230.2. AS STATED ON PREVIOUS REVIEW |
| | AT THIS TIME THE NEW SERVICE AS SHOWN CAN NOT BE |
| | PERMITTED. IN PHONE CONVERSATION WITH ENGINEER BEFORE |
| | PLANS WERE RESUBMITTED, THIS REVIEWER ASKED TO PROVIDE |
| | WHERE THIS WOULD MEET AN EXCEPTION TO ALLOW ANOTHER |
| | SERVICE. THE RESPONSE LETTER MENTIONS BECAUSE OF THE |
| | LOADS. HOWEVER BASED ON THE SECTION OF THE CODE AS |
| | NOTED IF A SERVICE REACHES THE LIMIT OF 2000AMPS, THEN |
| | AN ADDITIONAL SERVICE MAY BE GRANTED BY SPECIAL |
| | PERMISSION. (SEE DEFINITIONS OF SPECIAL PERMISSION). |
| | AT THIS TIME THE SERVICE IS NOT A SEPARATE VOLTAGE, IS |
| | NOT OVER 2000 AMPS ETC. |
| | |
| | 4) NOTE: PLEASE VERIFY EQUIPMENT GROUNDING PATH FROM |
| | MAINS TO SUB PANELS. |
| | 250.110,250.122 |
| | NEW NOTE: |
| | |
| | 5) NOTE: PLEASE CORRECT CODES ON ELECTRICAL NOTES. |
| | PLEASE SEE NOTES MENTIONS THE STANDARD BUILDING CODE |
| | AND MARTIN COUNTY AMENDMENTS. |
| | THIS APPEARS TO BE A MISPRINT. |
| | |
| | SHOULD READ AS FOLLOWS. |
| | 2004 FBC /W2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 AS ON OTHER SHEETS. |
| | |
| | 6) NOTE: VALUE FOR COMPLETE SCOPE OF WORK WAS INCREASED |
| | BASED ON RESPONSE LETTER AND FEE BALANCE OF $7, 777.00 |
| | WILL BE DUE BEFORE PERMIT CAN BE PRINTED. THE PERMIT |
| | APPLICATION STATES TO DESCRIBE PROJECT IN DETAIL. THIS |
| | WAS NOTED ON PREVIOUS REVIEW HOWEVER THE VALUE WAS |
| | INCREASED BY THIS OFFICE AND APPLICATION NEEDS TO BE |
| | DONE BY THE CONTRACTOR. |
| | FBC 108.3 |
| | |
| | 7) NOTE: PLEASE SHOW CIRCUTING AND HOW LIGTHING WILL BE |
| | CONTROLLED IN STAIRS. THE RESPONSE DOES NTO MENTION HOW |
| | THIS WAS ADDRESSED AND PLANS DO NOT INDICATE ANY |
| | CONTROLS. NFPA- 101 7.8.1.2.2, FBC 1006.1.2 |
| | |
| | 8) NOTE: PLEASE LIST MAXIMUM TIMES ON OCCUPANCY |
| | SENSORS. IF THIS WAS THE ONLY COMMENT THIS WOULD HAVE |
| | BEEN REDLINED. 13-415.1.ABC.1.1. |
| | |
| | |
| | |
| | |
| | |
| | ** PLEASE KNOW AS PLANS ARE NOT COMPLETE WITH |
| | INFORMATION ABOVE AT THIS TIME, WHEN PLANS COME BACK |
| | WITH THE INFORMATION NEW COMMENTS MAY BE PART OF THE |
| | REVIEW. |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |