| Date |
Text |
| 2008-08-01 16:45:41 | |
| | **DENIEDREVIEW** |
| | |
| | 1) NOTE: PLEASE SEE THE LIFE SAFETY CODE NFPA-101 2003 |
| | CHAPTER 7. PLEASE SEE SECTIONS 7.8 AND 7.9. PLEASE |
| | EXPLAIN HOW THE LIGHTING SHOWN FOR NORMAL USE IS |
| | DIFFERENT FIXTURES THAN THE LIGHTING SHOWN FOR |
| | EMERGENCY USE. THE FACT IS THESE ARE SHOWN AS |
| | COMPLETELY DIFFERENT FIXTURES. |
| | PLEASE SEE MISSING EXIT LIGHTS IN SEVERAL LOCATIONS. |
| | THIS MAY ALSO BE NOTED BY THE FIRE MARSHAL. |
| | PLEASE SEE 7.8.1.3, 7.9.2.1, 7.9.2.2 AND PLEASE SEE |
| | 7.8.1.2.2 FOR FAIL SAFE CONTROLS. THIS IS ALSO IN FBC |
| | 1006.1.2 (SEE COMMENTS BELOW FOR CHAPTER 13 LIGHTING |
| | CONTROLS REQUIRED). |
| | PLEASE SEE SECTIONS 7.10.1.1, 7.10.5.1 ETC. LOCATIONS |
| | WILL ALSO BE NOTED BY THE FIRE MARSHAL. |
| | |
| | 2) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3 |
| | FOR MINIMUM CONTROLS REQUIRED FOR LIGHTING. PLEASE SEE |
| | NOTES ABOVE WITH RESPECT TO LIGHTING IN EGRESS AREAS. |
| | |
| | 3) NOTE: PLEASE SEE FBC CHAPTER 11. 11-4.28.1,.2,.3. |
| | PLEASE INDICATE THE MINIMUM LEVELS FOR ADA COMPLIANCE |
| | FOR ALL HORN/STROBE DEVICES. |
| | |
| | 4) NOTE: PLEASE SEE 230.2AS THE NEW SERVICE WHICH IS |
| | NOW BEING SHOWN DOES NOT MEET THE EXCEPTIONS TO GRANT A |
| | NEW SERVICE. |
| | PLEASE SEE THE NEW MDP AS THIS SHOWS NEW 400AMP FEED TO |
| | NEW PANELS ON THIRD AND FORTH FLOORS YET BASED ON THE |
| | PANEL SCHEDULES THESE PANELS ARE SHOWN WITH A RATING OF |
| | 400AMPS YET THEY ARE ALSO SHOWN WITH 150AMPMAIN LUG |
| | ONLY. |
| | WHAT IS THE VOLTAGE ON THE EXISTING SERVICE? SHOWN AS |
| | 120/208 YET RISER ALSO SHOWS A TRANSFORMER. |
| | |
| | 5) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP PER |
| | 13-413.1.ABC.1.1,..1.2. |
| | |
| | 6) NOTE: PLEASE PROVIDE NOTES ON PLANS PER |
| | 13-413.1.ABC.2.1,.2.2. |
| | |
| | 7) NOTE: PLEASE INDICATE LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2.ABC.1.1, .1.2 AND .1.3. |
| | |
| | 8) NOTE: PLEASE SEE THE APPLIED SCOPE OF WORK ON PERMIT |
| | APPLICATION STATES REPLACE WINDOWS AND STUCCO HOWEVER |
| | BASED ON PLANS THE SCOPE OF WORK IS SUBSTANTIALLY MORE. |
| | PLEASE KNOW THE PERMIT APPLICATION VALUE SHALL INCLUDE |
| | ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COSTS ETC PER |
| | FBC108.3 THIS IS FOR ALL TRADES. |
| | |
| | ** IF THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE |
| | NOT CLEAR IN ANY MANOR PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | |
| | |
| | IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |