Plan Review Notes
Plan Review Notes For Permit 08070457
Permit Number 08070457
Review Stop B
Sequence Number 1
Notes
Date Text
2008-07-17 17:12:20RESIDENTIAL (R3)SHUTTERS BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- PANELS SPANSDIMENSIONSSHOWN ON INSTALLATION
 SCHEDULE DON'T WORK TO ACHIEVE THE EDGE DISTANCE SHOWN.
 ALSO,DIMENSIONS SHOWN ON THE PANEL SPAN COLUMN DON'T
 CORRESPOND TO THE OPENING SIZE SHOWN. (EG: OPENING #3
 IS 37" X 52". HOW CAN YOU HAVE ASHUTTER SPAN OF
 30.25?). COORDINATEALL OPENINGS AS NECESSARY AND
 REVISE AS REQUIRED.
  
 2-DRAWINGS FOR STORM SHUTTERS (DRAWING NO 06-169) ARE
 NOT LEGIBLE. UNABLE TO READ.PROVIDE CLEARAND
 LEGIBLE DRAWINGS.
  
 3- ANCHOR SPECIFIED FOR OPENINGS #11 AND #12SPECIFIED
 ON THE INSTALLATION SCHEDULE DON'T CORRESPOND TO ANCHOR
 TYPE SPECIFIED ON STORM PANELS DRAWINGS. REVISE AS
 REQUIRED.ALSO, SPACING OF ANCHORS SHOWN ON
 INSTALLATION SCHEDULE DOESN'TMATCH SPACING
 HIGHLIGHTED ONON STORM PANELS DRAWINGS, PAGE 17 OF
 17.REVISE AS REQUIRED.
  
 4- WIND LOAD TABLES:
 THERE ARE TWO DIFFERENT TABLES THAT WHERE
 HIGHLIGHTED. ONE IS FOR MEAN ROOF HEIGHT LESS THAN 60'
 AND THE OTHER ONE IS FOR MEAN ROOF HEIGHT OVER 60'.
 CONTRACTOR HIGHLIGHTED BOTH TABLESAND ONE OF THEM WAS
 HIGHLIGHTED FOR 130MPH. CIRCLE ONLY ONE TABLE.
 CORRECT TABLE IS FOR 140 MPH.
 ALSO, PROVIDE 2 COPIES
  