| 2008-07-29 10:21:24 | 2004 FBC W/2007 REVISIONS |
| | ENCLOSED COVERED PORCH |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) THE STRUCTURE IS LOCATED IN AN AO FLOOD ZONE, AN |
| | ELEVATION CERTIFICATE WILL BE REQUIRED FOR THE ENCLOSED |
| | PORCH. |
| | |
| | 4)SUBMIT TWO COPIES OF A SURVEY, SHOWING THE |
| | DISTANCES TO PROPERTY LINES AND SHOWING COMPLIANCE WITH |
| | R302.1 EXTERIOR WALLS. |
| | EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) |
| | SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE |
| | RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL |
| | NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM |
| | AN ADJACENT PROJECTION OR WALL. |
| | |
| | 5) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE |
| | ENCLOSED PORCH. OWNER/AGENT IS REQUIRED TO SIGN THE |
| | FORM. SEE FBC 13-600. |
| | |
| | 6) SPECIFY THE CEILING INSULATION ON THE PLANS. FBC |
| | 13-600. |
| | |
| | 7) THE BLOCK WALL LOAD CALCULATIONS STAPLED TO SHEET 3 |
| | OF THE PLANS IS REQUIRED TO BE SIGNED AND SEALED. FS |
| | 471 AND FBC 106.1* CITY AMENDMENTS. |
| | |
| | 8) PLEASE PROVIDE THE WIND DESIGN DATA FOR THE ENCLOSED |
| | PORCH. BASIC WIND SPEED, WIND IMPORTANCE FACTOR, WIND |
| | EXPOSURE, ENCLOSURE CLASSIFICATION, EXPOSURE CATEGORY |
| | AND COMPONENT AND CLADDING PRESSURES (WINDOWS AND |
| | DOOR). FBC 1603.1.4 AND R301. |
| | |
| | 9) SHOW COMPLIANCE WITH R403.1.4 MINIMUM DEPTH. ALL |
| | EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 INCHES |
| | (305 MM) BELOW THE UNDISTURBED GROUND SURFACE. |
| | |
| | 10) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE |
| | PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WITH 1/8 |
| | INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM |
| | OPENINGS. |
| | |
| | 11) SPECIFY THE WINDOW TYPE ON THE PLANS, SO THAT THE |
| | CORRECT PRODUCT APPROVALS CAN BE VERIFIED. DCA RULE |
| | 9B-72 AND FBC R301.2.1. |
| | |
| | 12)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. |
| | THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 13) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | WINDOWS ARE EXPIRED AND ARE FOR A XOX HORIZONTAL |
| | SLIDING WINDOW THAT ARE NOT SHOWN ON PLANS. SUBMIT A |
| | CURRENT PRODUCT APPROVAL FOR THE WINDOWS THAT WILL BE |
| | INSTALLED. RULE 9B-72 |
| | |
| | 14) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | DOORS ARE EXPIRED AND ARE FOR A SLIDING GLASS DOOR AND |
| | THE PLANS SPECIFY A DOUBLE OUTSWING FRENCH DOOR. SUBMIT |
| | A CURRENT PRODUCT APPROVAL FOR THE DOOR THAT WILL BE |
| | INSTALLED. RULE 9B-72 |
| | |
| | 15) THE DOOR PRODUCT APPROVAL THAT WAS SUBMITTED IS FOR |
| | A NON-IMPACT RATED DOOR. SUBMIT PRODUCT APPROVALS FOR |
| | STORM PANELS AS REQUIRED BY FBC R301.2.1.2. SPECIFY THE |
| | MOUNT TYPE, EDGE DISTANCE, GLASS SEPARATION DISTANCE, |
| | FASTENER TYPE AND SPACING, SPANS, ETC. |
| | |