| Plan Review Notes For Permit 08070427 |
| Permit Number |
08070427 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-07-16 13:52:30 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} INDICATE IF THIS HEAT PUMP IS A REPLACEMENT OR A NEW | | | INSTALLATION. IF NEW PROVIDE A LOAD CALCULATION FOR THE | | | ELECTRICAL SERVICE, INDICATING ALL EXISTING LOADS AND | | | ALL LOADS TO BE IMPOSED BY THE ADDITION OF THE NEW | | | EQUIPMENT. 215.5 NEC 2005. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|