Plan Review Notes
Plan Review Notes For Permit 08070398
Permit Number 08070398
Review Stop Z
Sequence Number 1
Notes
Date Text
2008-07-17 14:24:43PARKING SPACES TO BE STRIPED IN ACCORDANCE WITH
 ATTACHED DIAGRAM.
  
 FAILED
  
 A) THE SURVEY SUBMITTED DOES NOT SHOW THE SAME PARKING
 LOT CONFIGURATION AS THAT APPROVED BY THE SITE PLAN
 WITH THE ORIGINAL BUILDING PERMIT.THE FOLLOWING
 DIFFERENT ITEMS ARE HIGHLIGHTED ON THE ATTACHED PLAN:
 1. THE ADA SPACES HAVE BEEN RELOCATED AND ONE REGULAR
 PARKING SPACE HAS BEEN REMOVED.
 2. A REGULAR PARKING SPACE HAS BEEN REMOVED.
 3. A REGULAR PARKING SPACE HAS BEEN REMOVED.
 4. THE PARKING TABLE SHOWS THREE MORE SPACES THAN ON
 THE PROVIDED SURVEY.8 ADA SPACES ARE REQUIRED FOR THE
 NUMBER OF SPACES PROVIDED.NOTE: THE SCOPE OF WORK
 ONLY LISTS 5 HC SPACES TO BE PAINTED, AS STATED 8
 ADA/HC SPACES ARE REQUIRED.
 5. THE LOADING AREA NO LONGER EXISTS.
 6. THE PARKING LOT IS SHIFTED TO THE SOUTHEAST.
  
 B) STAFF FOUND NO RECORD THAT THE CHANGES IN A) WERE
 APPROVED BY EITHER THE PLANNING AND ZONING DEPARTMENT
 OR THE CONSTRUCTION SERVICES DEPARTMENT.EITHER
 PROVIDE A COPY THAT THESE CHANGES WERE APPROVED BY THE
 CITY, OR SUBMIT A MINOR AMENDMENT APPLICATION FOR THE
 REVISED PLAN.
  
 C) PROVIDE A REVISED PARKING TABLE ON THE PLANS FOR THE
 RESTRIPPING SHOWING ACCURATE CONDITIONS AFTER CHANGES
 ABOVE ARE ADDRESSED.
  
 D) LIMITS OF WORK NOT SHOWN ON THE PLANS.
  
 E) ALL CROSS-WALK PAINTING SHALL BE MAINTAINED.
  