| Date |
Text |
| 2008-07-29 14:46:18 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | 1.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| | FOR SLIDING GLASS DOORS, FAC9B72.A LOCAL PRODUCT |
| | APPROVAL REQUIRES AN APPLICATION, |
| | HTTP://WWW.DCA.STATE.FL.US/FBC/COMMITTEES/PRODUCT_APPR |
| | O VAL/LOCAL%20PRODUCT%20APPROVAL%20APPL%20080103.PDF |
| | |
| | 2.PLANS ARE TO SPECIFY UNITS INCLUDED IN THIS PERMIT, |
| | FBC*106, FBC*1609.PROVIDE A BUILDING LAYOUT SHOWING |
| | UNIT LOCATIONS. |
| | |
| | 3.TITLE BLOCK IN ACCORDANCE WITH FAC61G15-23.002 |
| | REQUIRED ON EACH SIGNED AND SEALED SHEET. |
| | |
| | 4.SHEET A4, 2001 NATIONAL DESIGN SPECIFICATION FOR |
| | WOOD CONSTURCTION WAS SPECIFIED.I WAS UNABLE TO |
| | LOCATE THIS STANDARD IN THE FLORIDA BUILDING CODE, |
| | FBC35.PLEASE REVISE OR PROVIDE MORE INFORMATION. |
| | |
| | 5.THE DRAWINGS ARE NOT LEGIBLE; PLEASE PROVIDE |
| | LEGIBLE DRAWINGS FBC*106. |
| | |
| | 6.THE JOB NAME AND ADDRESS ON THE DRAWINGS ARE NOT |
| | CORRECT, FBC*106, FAC61G15-23. |
| | |
| | 7.THE PRODUCT TESTED WAS NON IMPACT AND WAS SUBMITTED |
| | WITH A MIAMIDADE NOA FOR NON IMPACT LAMINATED GLASS. |
| | SEE FBC1609.1.4, IMPACT PROTECTION REQUIRED.IF THE |
| | PRODUCT IS IMPACT, IT MUST BE TESTED IN ACCORDANCE WITH |
| | ONE OF THE TEST STANDARDS REFERENCED IN FBC1609.1.4. |
| | |
| | 8.SEE FBC1714.5.2, PROVIDE INFORMATION TO DETERMINE |
| | WATER INFILTRATION REQUIREMENTS. |