| Plan Review Notes For Permit 08070391 |
| Permit Number |
08070391 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-07-31 10:49:19 | ***PROVISO*** | | | | | | STRUCTURAL PERMIT ONLY | | | | | | IN ADDITION TO THIS PERMIT APPLICATION, THE FOLLOWING | | | COMMENTS ARE REQUIRED TO BE ADDRESSED AT THE TIME OF | | | APPLICATION FOR BUILDING PERMIT. | | | | | | 1) EMERGENCY VEHICLE ACCESS AND WATER SUPPLY TO COMPLY | | | WITH NFPA 1, 2003 CHAPTER-18. | | | | | | 2) NEW FIRE HYDRANTS SHALL BE FULLY OPERATIONAL PRIOR | | | TO, DURING AND AFTER CONSTRUCTION. | | | | | | 3) FIRE LINES SHALL NOT PASS BENEATH ANY PART OF THE | | | STRUCTURE, PAD, FOUNDATION ETC. | | | | | | 4) PROPER CLEARANCES SHALL BE MAINTAINED AROUND FIRE | | | HYDRANT ASSEMBLIES. CLEARANCES OF 7'-6" TO FRONT AND | | | SIDES AND 4' TO REAR ARE REQUIRED AT ALL TIMES. ALL | | | FIRE PROTECTION EQUIPMENT SHALL REMAIN CLEAR OF ANY | | | OBSTRUCTIONS THAT WOULD IMPACT ACCESS OR USE. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|