2008-07-31 10:49:19***PROVISO***
  
 STRUCTURAL PERMIT ONLY
  
 IN ADDITION TO THIS PERMIT APPLICATION, THE FOLLOWING
 COMMENTS ARE REQUIRED TO BE ADDRESSED AT THE TIME OF
 APPLICATION FOR BUILDING PERMIT.
  
 1) EMERGENCY VEHICLE ACCESS AND WATER SUPPLY TO COMPLY
 WITH NFPA 1, 2003 CHAPTER-18.
  
 2) NEW FIRE HYDRANTS SHALL BE FULLY OPERATIONAL PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 3) FIRE LINES SHALL NOT PASS BENEATH ANY PART OF THE
 STRUCTURE, PAD, FOUNDATION ETC.
  
 4) PROPER CLEARANCES SHALL BE MAINTAINED AROUND FIRE
 HYDRANT ASSEMBLIES. CLEARANCES OF 7'-6" TO FRONT AND
 SIDES AND 4' TO REAR ARE REQUIRED AT ALL TIMES. ALL
 FIRE PROTECTION EQUIPMENT SHALL REMAIN CLEAR OF ANY
 OBSTRUCTIONS THAT WOULD IMPACT ACCESS OR USE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL