| Plan Review Notes For Permit 08070320 |
| Permit Number |
08070320 |
|
| Review Stop |
E |
| Sequence Number |
9 |
|
| Notes |
| Date |
Text |
| 2009-04-01 17:50:04 | ** DENIED REVIEW ** | | | | | | 1) NOTE: SHEETS E107, 120 AND 121 SHALL COORDINATE WITH | | | THE ELECTRICAL PLANS FOR THE EQUIPMENT ELECTRICAL | | | ENGINEERED PLANS. | | | PLEASE SEE THE PANEL PP-EC IS STILL NOT LISTED ON THE | | | MSB SWITCHBOARD. | | | THE RISER SUBMITTED FOR THE EQUIPMENT ENGINEERED PLANS | | | ALONG THE REVISED RISER ON E120 SHOWS A 175AMP BREAKER | | | FEEDING PANEL PP-EC HOWEVER PLEASE TAKE A LOOK AT MSB | | | SCHEDULE. THE ONLY 175 BREAKER ON EITHER E107 OR E120 | | | IS THE 175AMP BREAKER WHICH IS STATED FOR THE | | | *RELOCATED BALER*. TO DATE THERE IS NO PP-EC LISTED ON | | | EITHER MSB SCHEDULE. | | | PLEASE COORDINATE ALL. | | | PLEASE REVISE LOAD CALCULATIONS. | | | 408.4, 310.16, 240, 220 ETC | | | | | | 2) NOTE: SHEET E-1 THROUGH E-4 HAS BEEN STAMPED FOR | | | ELECTRICAL ENGINEERED EQUIPMENT PLANS. THIS SCOPE OF | | | WORK IS NOT PART OF THE BASE BUILDING ELECTRICAL. IN | | | FACT THIS SCOPE OF WORK IS DONE BY A SEPARATE | | | ELECTRICAL CONTRACTOR. | | | | | | A PHONE CALL WAS PLACED TO THE BASE BUILDING ELECTRICAL | | | ENGINEER FOR A RETURN CALL. | | | ONE SET OF ELECTRICAL PLANS FOR BASE BUILDING HAVE BEEN | | | RETAINED BY THIS REVIEWER. | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|