| 2009-03-26 18:15:14 | ** DENIED REVIEW ** |
| | |
| | ** PLEASE SEE NOTES FROM PREVIOUS REVIEW. |
| | |
| | 1) NOTE: PLEAS SUBMIT A COMPLETE COORDINATION STUDY. |
| | THIS NEEDS TO INCLUDE COORDINATION RISER, STUDY AND |
| | TIME CURVES. THE SUBMITTED SHORT CIRCUIT ANALYSIS IS |
| | NOT ALL THE INFORMATION THAT IS NEEDED TO VERIFY |
| | MINIMUM CODE COMPLIANCE. IT WAS GONE OVER ON THE PHONE |
| | THAT THE COMPLETE STUDY ALONG WITH TIME CURVES. |
| | 700.27, 701.8, 240.12 ETC. |
| | *** IT IS IMPORTANT TO KNOW THAT SINCE THE COORDINATION |
| | STUDY HAS YET TO BE SUBMITTED THERE MAY BE NEW COMMENTS |
| | ON THE NEXT REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | 2) NOTE: AS STATED ON PREVIOUS REVIEW. THE ENGINEER FOR |
| | THE BASE BUILDING ELECTRICAL PLANS NEEDS TO SIGN THE |
| | SHOP DRAWING REVIEW STAMPED OF THE SUBMITTED ELECTRICAL |
| | ENGINEERED SYSTEMS PLANS. |
| | THE PERSON SIGNED IS NOT THE ENGINEER OF RECORD. ALL |
| | ELECTRICAL WORK, LOADS ETC IN THE BUILDING BEFORE THE |
| | CERTIFICATE OF OCCUPANCY IS ISSUED IS UNDER THE REVIEW |
| | AND RESPONSIBILITY OF THE BASE BUILDING DESIGN |
| | PROFESSIONAL TO BE AWARE OF TRACK AND ADJUST MAIN |
| | PLANS. |
| | FS 471.025 |
| | |
| | 3) NOTE: PLEASE SEE BASE BUILDING RISER AND SUBMITTED |
| | ELECTRICAL ENGINEERING PLANS ARE STILL NEED |
| | COORDINATION. PLEASE SEE E120CR1 WHICH IS NOW NOT |
| | REVISED TO MATCH THE UPDATED MSB ON E107CR4. |
| | FOR EXAMPLE: REVISED MCC1 ON E107 |
| | FOR EXAMPLE: REVISED PP-EC ON E120 WHICH IS NOT ON E |
| | 107. |
| | PLEASE PROVIDE LOADS/CIRCUITS FOR THE LC. (LOAD |
| | CENTERS) LC210- LC217 |
| | 215.5, 408.4, 230, 240 SECTIONS GIVEN FOR COORDINATION |
| | OF ELECTRICAL PLANS. |
| | THE TOTAL LOAD SHOWN ON MSB IS NOT ACCURATE. PLEASE |
| | UPDATE WITH ALL NEW LOADS. |
| | |
| | 4) NOTE: FOR CONTRACTOR INFORMATION: IF THE EQUIPMENT |
| | PLANS AND BASE BUILDING PLANS ARE CLEARED UP BASED ON |
| | NOTES #2 AND #3 THE EQUIPMENT CONTRACTOR WILL BE ABLE |
| | TO APPLY FOR PERMIT. COMMENT #1 MAY REMAIN OUTSTANDING. |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |