| 2009-03-10 19:15:57 | ** DENIED REVISIONS ** |
| | |
| | REVISION OF PLANS FOR BASE BUILDING AND SUBMITTAL OF |
| | ELECTRICAL MANUFACTURING EQUIPMENT PLANS. |
| | |
| | 1) NOTE: THE REVISED SHEETS FOR ARCHITECTURAL NOTES AND |
| | SHEET E104CR4 ARE OK. |
| | |
| | 2) NOTE: ELECTRICAL RISER SHEET E107CR3 WILL REMAIN IN |
| | FAILED STATUS UNTIL COORDINATION WITH MANUFACTURING |
| | PLANS AND REVISIONS ARE MADE. |
| | SEE NOTE #4 BELOW AND OTHER NOTES. |
| | |
| | ** REVIEW FOR PLANS BY ASSOCIATED ENGINEERING |
| | INCORPORATED: |
| | |
| | 3) NOTE: THE TITLE BLOCKS NEED TO CONTAIN THE PRINTED |
| | NAME AND LICENSE NUMBER OF THE PROFESSIONAL ENGINEER |
| | EVEN IF THIS INFORMATION IS IN THE SAID SEAL OF THE |
| | SAME DESIGN PROFESSIONAL. |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.002 |
| | |
| | 4) NOTE: PLANS SHOWS GFI PROTECTION FOR THE 3000AMP |
| | MAIN DISTRIBUTION CENTER. PLEASE SEE 240.13,230.95 AS |
| | THIS SHOULD BE NOTED OR IDENTIFIED AS GFP. (GROUND |
| | FAULT PROTECTION) GFI IS FOR PERSONNEL PROTECTION. |
| | THE RISER NOTES # 7 ON E107CR3 STILL NOTES GFI EVEN AS |
| | THE MSB PANEL STATES GFP. |
| | PLEASE COORDINATE. |
| | |
| | 5) NOTE: PLEASE SEE MCC1 AS THIS EQUIPMENT IS SHOWN |
| | RATED AT 450AMP YET THERE IS A 500AMP BREAKER ON E107 |
| | SHOWN FEEDING THIS EQUIPMENT. THIS IS THE SAME ON THE |
| | EQUIPMENT PLANS. |
| | 240, 230, 310, 110.14 ETC. |
| | |
| | 6) NOTE: PLEASE SEE THE EQUIPMENT PLANS AS THEY CLEARLY |
| | INDICATE A 600AMP DISTRIBUTION SECTION WHICH IS NOT ON |
| | THE E107 SHEET/ RISER. |
| | NO INFORMATION IS PROVIDED FOR THIS PROVISION ON THE |
| | BASE BUILDING PLANS. |
| | FBC 106.1.1, 106.1.2, 106.3.5.1.2, COORDINATION AND |
| | ADDITIONAL INFORMATION ON RECORD PLANS. NEC 220,215.5, |
| | 240.4,230 ETC. THESE SECTIONS ARE GIVEN AS GENERAL |
| | CHAPTERS AS PLANS ARE NOT COORDINATED. IT IS NOT |
| | POSSIBLE TO DO A SPECIFIC REVIEW. |
| | |
| | 7) NOTE: PLEASE SEE THE ELECTRICAL EQUIPMENT RISER |
| | INDICATES A NEW 300AMP BREAKER ON THE MSB FEEDING A NEW |
| | 225KVA TRANSFORMER. NEITHER OF THESE TWO ITEMS IS ON |
| | THE BASE BUILDING ELECTRICAL RISER DIAGRAM ON SHEET |
| | E107. |
| | NO INFORMATION IS PROVIDED FOR THIS PROVISION ON THE |
| | BASE BUILDING PLANS. |
| | FBC 106.1.1, 106.1.2, 106.3.5.1.2, COORDINATION AND |
| | ADDITIONAL INFORMATION ON RECORD PLANS. NEC 220,215.5, |
| | 240.4,230, 408.4ETC. THESE SECTIONS ARE GIVEN AS |
| | GENERAL CHAPTERS AS PLANS ARE NOT COORDINATED. IT IS |
| | NOT POSSIBLE TO DO A SPECIFIC REVIEW. |
| | |
| | 8) NOTE: PLEASE SEE THE ELECTRICAL EQUIPMENT RISER AS |
| | THIS RISER CONTAINS TEN ELECTRICAL PANELS WHICH ARE |
| | IDENTIFIED AS SE1 THROUGH SE 10. NONE OF THESE PANELS |
| | ARE ON THE BASE BUILDING ELECTRICAL PLANS ON E107. |
| | PLEASE SEE NOTES # 6 AND 7 ABOVE AS THESE ARE DIRECTLY |
| | AFFECTED BY THESE ITEMS. |
| | NO INFORMATION IS PROVIDED FOR THIS PROVISION ON THE |
| | BASE BUILDING PLANS. |
| | FBC 106.1.1, 106.1.2, 106.3.5.1.2, COORDINATION AND |
| | ADDITIONAL INFORMATION ON RECORD PLANS. NEC 220,215.5, |
| | 240.4,230, 408.4ETC. THESE SECTIONS ARE GIVEN AS |
| | GENERAL CHAPTERS AS PLANS ARE NOT COORDINATED. IT IS |
| | NOT POSSIBLE TO DO A SPECIFIC REVIEW. |
| | |
| | 9) NOTE: THE BASE BUILDING ELECTRICAL RISER INDICATES A |
| | MCCB YET THE EQUIPMENT RISER FROM MANUFACTURE DOES NOT |
| | INDICATE THIS MCCB. THIS IS NOT ON THE RISER OR IN THE |
| | LOAD CALCULATIONS. |
| | 215.5,220,408.4,240.4, 310.16 ETC |
| | NO INFORMATION IS PROVIDED FOR THIS PROVISION ON THE |
| | BASE BUILDING PLANS. |
| | FBC 106.1.1, 106.1.2, 106.3.5.1.2, COORDINATION AND |
| | ADDITIONAL INFORMATION ON RECORD PLANS. SECTIONS ARE |
| | GIVEN AS GENERAL CHAPTERS AS PLANS ARE NOT COORDINATED. |
| | IT IS NOT POSSIBLE TO DO A SPECIFIC REVIEW. |
| | |
| | 10) NOTE: PLEASE KEEP IN MIND A COMPLETE REVISED |
| | ELECTRICAL COORDINATION STUDY ALONG WITH TIME CURVES |
| | ETC WILL BE REQUIRED NOT THAT ALL ELECTRICAL EQUIPMENT |
| | IS NOTED, FIGURED ETC. |
| | PLEASE SEE 240.12, 700.27, 701.8. |
| | FBC 106.1.1, 106.1.2 FOR CLARITY, COORDINATION AND |
| | INFORMATION ON THE RECORD PLANS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |