| Plan Review Notes For Permit 08070320 |
| Permit Number |
08070320 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2009-02-23 18:24:35 | ** DENIED/ PASSED REVISIONS ** | | | | | | | | | | | | 1) NOTE: PLEASE SEE PROVISO ISSUED 12/17/08. ITEMS | | | NUMBERS 2, 4 AND 5 NEED TO BE REVISED AT THIS TIME. | | | THESE ARE NOT ITEMS FOR *AS BUILTS*. | | | FOR INFORMATION. | | | AS-BUILTS ARE PLANS MADE UP OF ALL REVISED PLANS ALONG | | | THE PROGRESS OF THE PROJECT. THE CITY OF WEST PALM | | | BEACH DOES REQUIRE REVISIONS HOWEVER NOT A FINAL SET OF | | | AS-BUILDS. | | | | | | 2) NOTE: THE POWER PLAN SHEET WAS OK, STAMPED. | | | | | | 3) NOTE: COMMENTS FROM PROVISO WITH RESPECT TO | | | CERTIFICATE OF AUTHORIZATION NUMBERS ON REQUIRED | | | PREVIOUS PLANS IS STILL IN EFFECT. THIS WILL BE | | | ADDRESSED WHEN SUBMITTING PLANS WHICH WERE NOT REVIEWED | | | AND STAMPED. THIS IS FOR EQUIPMENT MANUFACTURE PLANS | | | AND MANUFACTURES ELECTRICAL PLANS. | | | FS 471.023,FAC 61G15-23.002. REVIEW OF SAID DOCUMENTS | | | STILL NEEDS TO TAKE PLACE FOR CODE COMPLIANCE. | | | 110.3,90.7 ETC | | | | | | ** THIS REVIEW WILL REMAINED IN A FAILED STATUS EVEN AS | | | POWER PLAN SHEET E105 IS OK. | | | | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|