Plan Review Notes
Plan Review Notes For Permit 08070320
Permit Number 08070320
Review Stop E
Sequence Number 4
Notes
Date Text
2008-12-17 11:48:35** PROVISO/REDLINED PLANS***
  
 THE FOLLOWING ITEMS SHALL BE ADDRESSED AND SUBMITTED.
  
 1) NOTE: ELECTRICAL MANUFACTURER'S SHOP DRAWINGS WILL
 BE SUBMITTED AT LATER DATE ONCE CA # FROM STATE IS
 OBTAINED.
 FS471.023,FAC 61G15-23.002
  
  
 2) NOTE: THE RISER STILL INDICATES * EQUIPMENT
 GROUNDING CONDUCTORS* BEFORE THE FIRST MEANS OF
 DISCONNECT FROM THE FPL TRANSFORMER WHICH IS NOT
 PERMITTED. THIS HAS BEEN NOTED IN ALL OF THE THREE
 PREVIOUS REVIEWS YET THE RISER NOTES HAVE NOT BEEN
 CORRECTED. THE RESPONSE LETTER MENTIONS REVISIONS WERE
 MADE HOWEVER THIS IS NOT THE CASE.
  
 3) NOTE: PLEASE SEE THE SUBMITTED ELECTRICAL PLANS FOR
 EQUIPMENT FROM ASSOCIATED ENGINEERS STILL DOES NOT HAVE
 ALL INFORMATION ON TITLE BLOCKS COMPLETE. IN FACT THE
 TITLE BLOCK WHERE THE REQUIRED CERTIFICATE OF
 AUTHORIZATION NUMBER IS SUPPOSE TO BE STATES THE CA
 NUMBER IS PENDING. THESE MAY NOT BE PART OF THE
 SUBMITTED DOCUMENTS WITHOUT COMPLETE INFORMATION. THE
 TITLE BLOCKS ARE REQUIRED TO CONTAIN THE PRINTED NAME
 AND LICENSE NUMBER OF DESIGNER ALONG WITH THE
 CERTIFICATE OF AUTHORIZATION NUMBER.\
 FAC 61G15-23.002, FS 471.023
  
  
 4) NOTE: THE STAIRS FROM THE MEZZANINE LEVEL STILL DO
 NOT INDICATE ANY LIGHTING MEETING EGRESS REQUIREMENTS.
 THE RESPONSE AND PER PHONE CONVERSATION PREVIOUSLY
 MENTIONED THIS WAS AND IS NOT AN EGRESS PATH REQUIRED
 OR OTHER WISE. THIS IS A MEANS OF ESCAPE AS DEFINE IN
 THE LIFE SAFETY CODE.
 IN ORDER NOT TO BE PART OF ANY EGRESS PATH SIGNAGE FOR
 DOOR MUST BE ON LIFE SAFETY PLANS AS WELL AS ELECTRICAL
 PLANS. PLEASE SEE NFPA-101
 7.10.8.3.1 ANY DOOR, PASSAGE, OR STAIRWAY THAT IS
 NEITHER AN EXIT NOR A WAY OF EXIT ACCESS AND THAT IS
 LOCATED OR ARRANGED SO THAT IT IS LIKELY TO BE MISTAKEN
 FOR AN EXIT SHALL BE IDENTIFIED BY A SIGN THAT READS AS
 FOLLOWS:
 NO
 EXIT
 7.10.8.3.2 THE NO EXIT SIGN SHALL HAVE THE WORD NO IN
 LETTERS 51 MM (2 IN.) HIGH, WITH A STROKE WIDTH OF 9.5
 MM ( IN.), AND THE WORD EXIT IN LETTERS 25 MM (1 IN.)
 HIGH, WITH THE WORD EXIT BELOW THE WORD NO, UNLESS SUCH
 SIGN IS AN APPROVED EXISTING SIGN.
  
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE.
  
  
 5) NOTE: PLEASE CLARIFY JOCKEY PUMP WHICH RISER
 INDICATES 30AMP DISCONNECT FUSED AT 30AMPS YET BRANCH
 FROM ELP1 ONLY HAS 20AMP OCP WITH #12 CONDUCTORS.??
 240.4,310.16, 430.
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
 *** PRO
  
 *** NOTED SEPARATE PERMITS FOR LIGHTNING PROTECTION,
 LOW VOLTAGE SYSTEMS, FIRE ALARM, FIRE SPRINKLER. THE
 BASE PLANS MAY BE REFERENCED FOR LOW VOLTAGE SYSTEM
 ONLY. SEPARATE PLANS WILL BE REQUIRED FOR LP, FS AND
 FA.
 THIS IS NOTED FOR REVIEW ONLY. NO RESPONSE OR CHANGES
 ARE NEEDED ON PLANS OR SUBMITTED DOCUMENTS.
  
  
 *** LETTER IN FILE WITH RESPECT TO BUILDING OCCUPANCY
 WHEN UNDER EMERGENCY BACK UP POWER. IN COMPLIANCE WITH
 FBC CHAPTER 10 AS WELL AS NFPA-101 THE BUILDING SHALL
 BE EVACUATED WHEN NORMAL POWER IS LOST INCLUDING ALL
 EMPLOYEEST. LETTER SUBMITTED SIGNED AND NOTARIZED FROM
 MR. PATRICK CARROLL DIRECTOR OF FACILITIES DEVELOPMENT
 IS IN FILE.
  
  