| Plan Review Notes For Permit 08070320 |
| Permit Number |
08070320 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2008-12-08 16:01:08 | **PROVISO** - REVISE AS FOLLOWS, PRIOR TO INSTALLATION | | | | | | WBCM SUBMITTAL #8, CALCULATIONS CM MANUFACTURING, | | | PLEASE ADDRESS: | | | | | | A. ASCE7-05 REFERENCED; FBC2004 REQUIRES ASCE7-02. THIS | | | CAN BE DONE WITH A LETTER OR CAN BE A PROVISO ITEM. | | | | | | B. SEE PAGE 22, EXPOSURE B USED WITH AN IMPORTANCE | | | FACTOR OF .77. IF ACCEPTABLE TO THE DESIGNER OF RECORD, | | | THE REDUCED IMPORTANCE FACTOR CAN BE USED BUT PROVIDE | | | JUSTIFICATION FOR USE OF EXPOSURE B. THIS JOB APPEARS | | | TO HAVE EXPOSURE C CONDITIONS, FBC1609.4. | | | | | | C. CALCS AND PLANS DO NOT NEED TO BE REVISED, BUT | | | PLEASE NOTE THAT GOVERNING CODE IS FBC2004 WITH 2007 | | | REVISIONS/SUPPLEMENTS. CALCS REFER TO 2005 AND 2006 | | | REVISIONS AND SUPPLEMENTS, PLANS STATE COMPLIANCE WITH | | | INTERNATIONAL BUILDING CODE 2003. FOR FUTURE | | | SUBMITTALS, PLEASE REVISE. | | | | | | D. PAGE 21 NOTE STATES "LATERAL IMPACT DOES NOT ALLOW | | | 1/3 STRESS INCREASE AS ALLOWED FOR ASD WIND LOAD | | | ANALYSIS" PLEASE PROVIDE MORE INFORMATION REGARDING | | | STRESS INCREASE USED AND SEE FBC1605.3.1.1 AND CLARIFY | | | USE OF STRESS INCREASE. | | | | | | |
|