Plan Review Notes For Permit 08070320
Permit Number 08070320
Review Stop B
Sequence Number 4
Notes
Date Text
2008-12-08 16:01:08**PROVISO** - REVISE AS FOLLOWS, PRIOR TO INSTALLATION
  
 WBCM SUBMITTAL #8, CALCULATIONS CM MANUFACTURING,
 PLEASE ADDRESS:
  
 A. ASCE7-05 REFERENCED; FBC2004 REQUIRES ASCE7-02. THIS
 CAN BE DONE WITH A LETTER OR CAN BE A PROVISO ITEM.
  
 B. SEE PAGE 22, EXPOSURE B USED WITH AN IMPORTANCE
 FACTOR OF .77. IF ACCEPTABLE TO THE DESIGNER OF RECORD,
 THE REDUCED IMPORTANCE FACTOR CAN BE USED BUT PROVIDE
 JUSTIFICATION FOR USE OF EXPOSURE B. THIS JOB APPEARS
 TO HAVE EXPOSURE C CONDITIONS, FBC1609.4.
  
 C. CALCS AND PLANS DO NOT NEED TO BE REVISED, BUT
 PLEASE NOTE THAT GOVERNING CODE IS FBC2004 WITH 2007
 REVISIONS/SUPPLEMENTS. CALCS REFER TO 2005 AND 2006
 REVISIONS AND SUPPLEMENTS, PLANS STATE COMPLIANCE WITH
 INTERNATIONAL BUILDING CODE 2003. FOR FUTURE
 SUBMITTALS, PLEASE REVISE.
  
 D. PAGE 21 NOTE STATES "LATERAL IMPACT DOES NOT ALLOW
 1/3 STRESS INCREASE AS ALLOWED FOR ASD WIND LOAD
 ANALYSIS" PLEASE PROVIDE MORE INFORMATION REGARDING
 STRESS INCREASE USED AND SEE FBC1605.3.1.1 AND CLARIFY
 USE OF STRESS INCREASE.
  
  