Plan Review Notes
Plan Review Notes For Permit 08070320
Permit Number 08070320
Review Stop E
Sequence Number 3
Notes
Date Text
2008-12-17 11:44:30** DENIED 3RD REVIEW **
  
 ** SOME ITEMS FROM PREVIOUS REVIEW ARE STILL IN NEED OF
 ADDRESSING.
 ** SOME OF THE ITEMS MAY BE ABLE TO BE SET UP AS PART
 OF A PROVISO/ISSUANCE WITH CONDITIONS HOWEVER SOME MUST
 BE ADDRESSED AT THIS TIME.
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 NEED TO BE SIGNED, DATED AND SEALED BY THE RESPONSIBLE
 DESIGNER. THE CERTIFICATION SHEET CONTAINS A SIGNATURE
 AND DATE HOWEVER NOT SEALED WITH THE RAISED SEAL. THIS
 IS FOR BOTH THE MAIN FACILITY BUILDING AS WELL AND
 SCALE HOUSE.
  
 2) NOTE: PLEASE SEE THE CALCULATIONS FOR ELECTRICAL
 LIGHTING APPEAR TO SHOW NO GROSS ERRORS AS NOTED IN FBC
 13-103.3. HOWEVER PLEASE SEE THE SCALE HOUSE
 CALCULATIONS AS THESE MOST CERTAINLY COULD NOT BE
 SIGNED AS COMPLIANT BY ELECTRICAL WHEN THERE ARE ITEMS
 FOR OTHER TRADES LEFT COMPLETELY BLANK.
 SOME OF THESE EXAMPLES WOULD BE THE IDR INDICATES:
 NO WINDOWS YET THERE ARE WINDOWS ON THE BUILDING AND
 FENESTRATIONS ARE ALSO BLANK.
 NO DOORS, YET THERE ARE DOORS ON PLANS.
 FLOORS FOR ALL AREAS NOTED AS CARPET AND RUBBER
 PADDING. THIS IS NOT POSSIBLE. THERE ARE AREAS WITH
 TILE AND OTHER SURFACES WHICH ARE NOT CARPET AND RUBBER
 PADDING.
  
 ** THESE ITEMS ARE CLEAR TO THIS REVIEWER AS GROSS
 ERRORS AND THESE CALCULATIONS COULD NOT BE STAMPED BY
 ELECTRICAL AS CODE COMPLIANT WHETHER OR NOT THEY WERE
 SIGNED AND SEALED.
 ** THESE ITEMS NEED TO BE ADDRESSED WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEW STAFF.
  
 13-400.A.3, 13-401, 13-403, 13-405
  
 3) NOTE: THE RISER STILL INDICATES * EQUIPMENT
 GROUNDING CONDUCTORS* BEFORE THE FIRST MEANS OF
 DISCONNECT FROM THE FPL TRANSFORMER WHICH IS NOT
 PERMITTED. THIS HAS BEEN NOTED IN ALL OF THE THREE
 PREVIOUS REVIEWS YET THE RISER NOTES HAVE NOT BEEN
 CORRECTED. THE RESPONSE LETTER MENTIONS REVISIONS WERE
 MADE HOWEVER THIS IS NOT THE CASE.
  
 4) NOTE: PLEASE SEE THE SUBMITTED ELECTRICAL PLANS FOR
 EQUIPMENT FROM ASSOCIATED ENGINEERS STILL DOES NOT HAVE
 ALL INFORMATION ON TITLE BLOCKS COMPLETE. IN FACT THE
 TITLE BLOCK WHERE THE REQUIRED CERTIFICATE OF
 AUTHORIZATION NUMBER IS SUPPOSE TO BE STATES THE CA
 NUMBER IS PENDING. THESE MAY NOT BE PART OF THE
 SUBMITTED DOCUMENTS WITHOUT COMPLETE INFORMATION. THE
 TITLE BLOCKS ARE REQUIRED TO CONTAIN THE PRINTED NAME
 AND LICENSE NUMBER OF DESIGNER ALONG WITH THE
 CERTIFICATE OF AUTHORIZATION NUMBER.\
 FAC 61G15-23.002, FS 471.023
 ***PRO
  
 5) NOTE: THE STAIRS FROM THE MEZZANINE LEVEL STILL DO
 NOT INDICATE ANY LIGHTING MEETING EGRESS REQUIREMENTS.
 THE RESPONSE AND PER PHONE CONVERSATION PREVIOUSLY
 MENTIONED THIS WAS AND IS NOT AN EGRESS PATH REQUIRED
 OR OTHER WISE. THIS IS A MEANS OF ESCAPE AS DEFINE IN
 THE LIFE SAFETY CODE.
 IN ORDER NOT TO BE PART OF ANY EGRESS PATH SIGNAGE FOR
 DOOR MUST BE ON LIFE SAFETY PLANS AS WELL AS ELECTRICAL
 PLANS. PLEASE SEE NFPA-101
 7.10.8.3.1 ANY DOOR, PASSAGE, OR STAIRWAY THAT IS
 NEITHER AN EXIT NOR A WAY OF EXIT ACCESS AND THAT IS
 LOCATED OR ARRANGED SO THAT IT IS LIKELY TO BE MISTAKEN
 FOR AN EXIT SHALL BE IDENTIFIED BY A SIGN THAT READS AS
 FOLLOWS:
 NO
 EXIT
 7.10.8.3.2 THE NO EXIT SIGN SHALL HAVE THE WORD NO IN
 LETTERS 51 MM (2 IN.) HIGH, WITH A STROKE WIDTH OF 9.5
 MM ( IN.), AND THE WORD EXIT IN LETTERS 25 MM (1 IN.)
 HIGH, WITH THE WORD EXIT BELOW THE WORD NO, UNLESS SUCH
 SIGN IS AN APPROVED EXISTING SIGN.
  
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE.
 *** PRO
  
 6) NOTE: PLEASE CLARIFY JOCKEY PUMP WHICH RISER
 INDICATES 30AMP DISCONNECT FUSED AT 30AMPS YET BRANCH
 FROM ELP1 ONLY HAS 20AMP OCP WITH #12 CONDUCTORS.??
 240.4,310.16, 430.
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
 *** PRO
  
 7) SEPARATE PERMITS FOR LIGHTNING PROTECTION, LOW
 VOLTAGE SYSTEMS, FIRE ALARM, FIRE SPRINKLER. THE BASE
 PLANS MAY BE REFERENCED FOR LOW VOLTAGE SYSTEM ONLY.
 SEPARATE PLANS WILL BE REQUIRED FOR LP, FS AND FA.
 THIS IS NOTED FOR REVIEW ONLY. NO RESPONSE OR CHANGES
 ARE NEEDED ON PLANS OR SUBMITTED DOCUMENTS.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-12-12 17:11:31REVIEW IS IN PROGRESS.
 REVIEW WILL BE GOING INTO FAILED STATUS ONCE COMPLETED
 AND NOTES WILL FOLLOW.