| 2008-12-17 11:44:30 | ** DENIED 3RD REVIEW ** |
| | |
| | ** SOME ITEMS FROM PREVIOUS REVIEW ARE STILL IN NEED OF |
| | ADDRESSING. |
| | ** SOME OF THE ITEMS MAY BE ABLE TO BE SET UP AS PART |
| | OF A PROVISO/ISSUANCE WITH CONDITIONS HOWEVER SOME MUST |
| | BE ADDRESSED AT THIS TIME. |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| | NEED TO BE SIGNED, DATED AND SEALED BY THE RESPONSIBLE |
| | DESIGNER. THE CERTIFICATION SHEET CONTAINS A SIGNATURE |
| | AND DATE HOWEVER NOT SEALED WITH THE RAISED SEAL. THIS |
| | IS FOR BOTH THE MAIN FACILITY BUILDING AS WELL AND |
| | SCALE HOUSE. |
| | |
| | 2) NOTE: PLEASE SEE THE CALCULATIONS FOR ELECTRICAL |
| | LIGHTING APPEAR TO SHOW NO GROSS ERRORS AS NOTED IN FBC |
| | 13-103.3. HOWEVER PLEASE SEE THE SCALE HOUSE |
| | CALCULATIONS AS THESE MOST CERTAINLY COULD NOT BE |
| | SIGNED AS COMPLIANT BY ELECTRICAL WHEN THERE ARE ITEMS |
| | FOR OTHER TRADES LEFT COMPLETELY BLANK. |
| | SOME OF THESE EXAMPLES WOULD BE THE IDR INDICATES: |
| | NO WINDOWS YET THERE ARE WINDOWS ON THE BUILDING AND |
| | FENESTRATIONS ARE ALSO BLANK. |
| | NO DOORS, YET THERE ARE DOORS ON PLANS. |
| | FLOORS FOR ALL AREAS NOTED AS CARPET AND RUBBER |
| | PADDING. THIS IS NOT POSSIBLE. THERE ARE AREAS WITH |
| | TILE AND OTHER SURFACES WHICH ARE NOT CARPET AND RUBBER |
| | PADDING. |
| | |
| | ** THESE ITEMS ARE CLEAR TO THIS REVIEWER AS GROSS |
| | ERRORS AND THESE CALCULATIONS COULD NOT BE STAMPED BY |
| | ELECTRICAL AS CODE COMPLIANT WHETHER OR NOT THEY WERE |
| | SIGNED AND SEALED. |
| | ** THESE ITEMS NEED TO BE ADDRESSED WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEW STAFF. |
| | |
| | 13-400.A.3, 13-401, 13-403, 13-405 |
| | |
| | 3) NOTE: THE RISER STILL INDICATES * EQUIPMENT |
| | GROUNDING CONDUCTORS* BEFORE THE FIRST MEANS OF |
| | DISCONNECT FROM THE FPL TRANSFORMER WHICH IS NOT |
| | PERMITTED. THIS HAS BEEN NOTED IN ALL OF THE THREE |
| | PREVIOUS REVIEWS YET THE RISER NOTES HAVE NOT BEEN |
| | CORRECTED. THE RESPONSE LETTER MENTIONS REVISIONS WERE |
| | MADE HOWEVER THIS IS NOT THE CASE. |
| | |
| | 4) NOTE: PLEASE SEE THE SUBMITTED ELECTRICAL PLANS FOR |
| | EQUIPMENT FROM ASSOCIATED ENGINEERS STILL DOES NOT HAVE |
| | ALL INFORMATION ON TITLE BLOCKS COMPLETE. IN FACT THE |
| | TITLE BLOCK WHERE THE REQUIRED CERTIFICATE OF |
| | AUTHORIZATION NUMBER IS SUPPOSE TO BE STATES THE CA |
| | NUMBER IS PENDING. THESE MAY NOT BE PART OF THE |
| | SUBMITTED DOCUMENTS WITHOUT COMPLETE INFORMATION. THE |
| | TITLE BLOCKS ARE REQUIRED TO CONTAIN THE PRINTED NAME |
| | AND LICENSE NUMBER OF DESIGNER ALONG WITH THE |
| | CERTIFICATE OF AUTHORIZATION NUMBER.\ |
| | FAC 61G15-23.002, FS 471.023 |
| | ***PRO |
| | |
| | 5) NOTE: THE STAIRS FROM THE MEZZANINE LEVEL STILL DO |
| | NOT INDICATE ANY LIGHTING MEETING EGRESS REQUIREMENTS. |
| | THE RESPONSE AND PER PHONE CONVERSATION PREVIOUSLY |
| | MENTIONED THIS WAS AND IS NOT AN EGRESS PATH REQUIRED |
| | OR OTHER WISE. THIS IS A MEANS OF ESCAPE AS DEFINE IN |
| | THE LIFE SAFETY CODE. |
| | IN ORDER NOT TO BE PART OF ANY EGRESS PATH SIGNAGE FOR |
| | DOOR MUST BE ON LIFE SAFETY PLANS AS WELL AS ELECTRICAL |
| | PLANS. PLEASE SEE NFPA-101 |
| | 7.10.8.3.1 ANY DOOR, PASSAGE, OR STAIRWAY THAT IS |
| | NEITHER AN EXIT NOR A WAY OF EXIT ACCESS AND THAT IS |
| | LOCATED OR ARRANGED SO THAT IT IS LIKELY TO BE MISTAKEN |
| | FOR AN EXIT SHALL BE IDENTIFIED BY A SIGN THAT READS AS |
| | FOLLOWS: |
| | NO |
| | EXIT |
| | 7.10.8.3.2 THE NO EXIT SIGN SHALL HAVE THE WORD NO IN |
| | LETTERS 51 MM (2 IN.) HIGH, WITH A STROKE WIDTH OF 9.5 |
| | MM ( IN.), AND THE WORD EXIT IN LETTERS 25 MM (1 IN.) |
| | HIGH, WITH THE WORD EXIT BELOW THE WORD NO, UNLESS SUCH |
| | SIGN IS AN APPROVED EXISTING SIGN. |
| | |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | ANY OTHER TRADE. |
| | *** PRO |
| | |
| | 6) NOTE: PLEASE CLARIFY JOCKEY PUMP WHICH RISER |
| | INDICATES 30AMP DISCONNECT FUSED AT 30AMPS YET BRANCH |
| | FROM ELP1 ONLY HAS 20AMP OCP WITH #12 CONDUCTORS.?? |
| | 240.4,310.16, 430. |
| | FBC 106.1.1 FOR CLARITY AND COORDINATION. |
| | *** PRO |
| | |
| | 7) SEPARATE PERMITS FOR LIGHTNING PROTECTION, LOW |
| | VOLTAGE SYSTEMS, FIRE ALARM, FIRE SPRINKLER. THE BASE |
| | PLANS MAY BE REFERENCED FOR LOW VOLTAGE SYSTEM ONLY. |
| | SEPARATE PLANS WILL BE REQUIRED FOR LP, FS AND FA. |
| | THIS IS NOTED FOR REVIEW ONLY. NO RESPONSE OR CHANGES |
| | ARE NEEDED ON PLANS OR SUBMITTED DOCUMENTS. |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2008-12-12 17:11:31 | REVIEW IS IN PROGRESS. |
| | REVIEW WILL BE GOING INTO FAILED STATUS ONCE COMPLETED |
| | AND NOTES WILL FOLLOW. |