2008-10-25 14:47:50REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1 THROUGH 7: OK
  
 8. CONDENSATE DISCHARGING OUTDOORS IS OK. HOWEVER,
 DETAIL 12 ON PAGE M104CR1 SHOWS CONDENSATE TYING INTO
 STORM WATER PIPING AT AN ELEVATION LOWER THAN THE STORM
 WATER INLET. THIS CONFIGURATION CREATES AN OPENING IN
 THE STORM WATER DRAIN WITHIN THE BUILDING. SHOULD THE
 STORM WATER DRAIN EVER BACK UP AT A POINT DOWNSTREAM OF
 THE CONDENSATE PIPE, THIS WILL CAUSE THE STORM WATER TO
 BACKUP INTO THE CONDENSATE PIPE AND MAKE THE CONDENSATE
 PIPE A STORM DRAIN PIPE DISCHARGING WITHIN THE
 BUILDING. THIS IS NOT AN APPROVED PLACE OF CONDENSATE
 DISPOSAL. SEE FBCM 307.2.1 AND THE DEFINITION OF
 APPROVED IN SECTION 202 OF FBCM.
  
 9 AND 10: OK
  
 11. PROVIDE PRODUCT APPROVALS AND SUPPORTING
 DOCUMENTATION FOR WIND RESISTANCE FOR ALL OUTDOOR
 APPLIANCES WHICH ARE EXPOSED TO WIND, INCLUDING EXHAUST
 FANS, PACKAGE UNITS AND CONDENSING UNITS. ALL OF THESE
 APPLIANCES ARE NOT ONLY REQUIRED TO BE SECURED TO
 RESIST WIND PRESSURES, BUT ALSO BE DESIGNED AND
 CONSTRUCTED TO RESIST WIND PRESSURES IN ACCORDANCE WITH
 FBCM 301.13. ALSO, NO INFORMATION COULD BE FOUND IN
 STRUCTURAL PLANS FOR CONSTRUCTION AND SUPPORTS FOR WIND
 RESISTANCE RELATED TO EXTERIOR DUCTWORK. PLEASE PROVIDE
 MISSING INFORMATION IN ACCORDANCE WITH FBCM 301.13.
  
 12. OK
  
 13. WRITTEN RESPONSE INDICATES A CARRIER HAP REPORT IS
 ATTACHED TO THE WRITTEN RESPONSES FOR THE PURPOSE OF
 SHOWING COMPLIANCE WITH ASHRAE 62.1-2004. NO SUCH
 REPORT COULD BE FOUND ATTACHED TO THE WRITTEN
 RESPONSES. PLEASE PROVIDE THE REPORT MENTIONED IN THE
 RESPONSE TO DEMONSTRATE COMPLIANCE WITH FBCM 401.1.
  
 14. OK
  
 15. ENERGY CODE COMPLIANCE FORMS HAVE BEEN PROVIDED IN
 RESPONSE TO THIS COMMENT. HOWEVER, THERE ARE MULTIPLE
 MITSUBISHI SPLIT-SYSTEMS NOT INCLUDED IN THE ENERGY
 CODE COMPLIANCE FORM. PLEASE INCLUDE ALL COOLING
 APPLIANCES IN THE COMPLIANCE FORM.
  