| 2008-10-25 14:47:50 | REVIEW #: 2ND |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1 THROUGH 7: OK |
| | |
| | 8. CONDENSATE DISCHARGING OUTDOORS IS OK. HOWEVER, |
| | DETAIL 12 ON PAGE M104CR1 SHOWS CONDENSATE TYING INTO |
| | STORM WATER PIPING AT AN ELEVATION LOWER THAN THE STORM |
| | WATER INLET. THIS CONFIGURATION CREATES AN OPENING IN |
| | THE STORM WATER DRAIN WITHIN THE BUILDING. SHOULD THE |
| | STORM WATER DRAIN EVER BACK UP AT A POINT DOWNSTREAM OF |
| | THE CONDENSATE PIPE, THIS WILL CAUSE THE STORM WATER TO |
| | BACKUP INTO THE CONDENSATE PIPE AND MAKE THE CONDENSATE |
| | PIPE A STORM DRAIN PIPE DISCHARGING WITHIN THE |
| | BUILDING. THIS IS NOT AN APPROVED PLACE OF CONDENSATE |
| | DISPOSAL. SEE FBCM 307.2.1 AND THE DEFINITION OF |
| | APPROVED IN SECTION 202 OF FBCM. |
| | |
| | 9 AND 10: OK |
| | |
| | 11. PROVIDE PRODUCT APPROVALS AND SUPPORTING |
| | DOCUMENTATION FOR WIND RESISTANCE FOR ALL OUTDOOR |
| | APPLIANCES WHICH ARE EXPOSED TO WIND, INCLUDING EXHAUST |
| | FANS, PACKAGE UNITS AND CONDENSING UNITS. ALL OF THESE |
| | APPLIANCES ARE NOT ONLY REQUIRED TO BE SECURED TO |
| | RESIST WIND PRESSURES, BUT ALSO BE DESIGNED AND |
| | CONSTRUCTED TO RESIST WIND PRESSURES IN ACCORDANCE WITH |
| | FBCM 301.13. ALSO, NO INFORMATION COULD BE FOUND IN |
| | STRUCTURAL PLANS FOR CONSTRUCTION AND SUPPORTS FOR WIND |
| | RESISTANCE RELATED TO EXTERIOR DUCTWORK. PLEASE PROVIDE |
| | MISSING INFORMATION IN ACCORDANCE WITH FBCM 301.13. |
| | |
| | 12. OK |
| | |
| | 13. WRITTEN RESPONSE INDICATES A CARRIER HAP REPORT IS |
| | ATTACHED TO THE WRITTEN RESPONSES FOR THE PURPOSE OF |
| | SHOWING COMPLIANCE WITH ASHRAE 62.1-2004. NO SUCH |
| | REPORT COULD BE FOUND ATTACHED TO THE WRITTEN |
| | RESPONSES. PLEASE PROVIDE THE REPORT MENTIONED IN THE |
| | RESPONSE TO DEMONSTRATE COMPLIANCE WITH FBCM 401.1. |
| | |
| | 14. OK |
| | |
| | 15. ENERGY CODE COMPLIANCE FORMS HAVE BEEN PROVIDED IN |
| | RESPONSE TO THIS COMMENT. HOWEVER, THERE ARE MULTIPLE |
| | MITSUBISHI SPLIT-SYSTEMS NOT INCLUDED IN THE ENERGY |
| | CODE COMPLIANCE FORM. PLEASE INCLUDE ALL COOLING |
| | APPLIANCES IN THE COMPLIANCE FORM. |
| | |