| Plan Review Notes For Permit 08070320 |
| Permit Number |
08070320 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-11-04 11:26:51 | ***DENIED*** | | | | | | MOST OF THE PREVIOUS COMMENTS HAVE BEEN ADDRESSED. | | | PLEASE SEE THE FOLLOWING FROM THE PREVIOUS REVIEW FOR | | | CORRECTION OR FURTHER CLARIFICATION: | | | | | | 1) OK- PLEASE ADD NFPA 101, 2003 TO THE CODE ANALYSIS | | | ON SHEET A901CR1. | | | | | | 19) OK- PLEASE ILLUSTRATE THE LOCATION OF THE FIRE | | | DEPARTMENT CONNECTION(S) ON SHEET CO12CR1. | | | | | | 20) PLEASE ILLUSTRATE THE LOCATION OF THE DOUBLE CHECK | | | DETECTOR ASSEMBLY AND ADD NOTE REGARDING CHAIN AND LOCK | | | REQUIREMENT IN ADDITION TO ELECTRONIC SUPERVISION. | | | | | | 23) EXIT SIGN IS STILL MISSING ON SHEET E102CR1. | | | | | | ADDITIONAL NOTE FOR CLARIFICATION: | | | HOSE STATIONS SHALL BE PROVIDED WITH 2 1/2" - 1 1/2" | | | CONNECTIONS WITH CHAINS. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 | | | | | | |
|