Plan Review Notes
Plan Review Notes For Permit 08070320
Permit Number 08070320
Review Stop E
Sequence Number 2
Notes
Date Text
2008-10-27 16:49:54 
 ** DENIED 2ND REVIEW**
  
  
 1) NOTE: PLEASE SEE THE LETTER SUBMITTED FOR THE
 BUILDING NOT TO BE OCCUPIED UNDER THE LOSS OF
 NORMAL/MAIN POWER IS TO BE REVISED. THE LETTER STATES
 THE FACILITY WILL NOT OPERATE HOWEVER THE LETTER NEEDS
 TO STATE THE BUILDING WILL NOT BE OCCUPIED BY ANY
 PERSONNEL. THE LETTER(S) NEED TO BE ORIGINAL AND
 NOTARIZED. PLEASE SEE FS 117.05 FOR NOTARIES.
 NFPA-101 7.8, 7.9
  
 2) NOTE: THE PREVIOUS REVIEW REQUESTED THE REQUIRED
 ENERGY CALCULATIONS TO BE SUBMITTED. AS THEY WERE NOT
 SUBMITTED ON THE FIRST REVIEW THEY COULD NOT BE
 REVIEWED. PLEASE SEE THE ENERGY CALCULATIONS AND THE
 INPUT DATA REPORT NEED TO COORDINATE WITH THE PLANS.
 THE INPUT DATA REPORT WILL BE NOTED BELOW AS IDR.
 TWO SEPARATE CALCULATIONS WERE SUBMITTED. THE
 *CERTIFICATIONS* SHEETS NEED TO BE COMPLETED WITH THE
 SIGNATURE, DATE AND SEAL FROM THE RESPONSIBLE DESIGNER
 OF RECORD. THE COVER SHEET WAS SIGNED AND SEALED.
 EXAMPLES OF SOME INCONSISTENCIES OF THE SUBMITTED
 CALCULATIONS AND THE IDR WILL BE NOTED.
  
 FOR EXAMPLE: PLEASE SEE THE SQUARE FOOTAGE OF THE
 CALCULATION COVER SHEET SHOWS A TOTAL OF 7022 SQ FT
 TOTAL OF CONDITIONED AND UNCONDITIONED SPACE. THIS IS
 NOT POSSIBLE AS THE SQUARE FOOTAGE SHOWN ON A001CR1
 SHOWS NUMBERS FAR GREATER. THE SUBMITTED METHOD *A* IS
 FOR WHOLE BUILDING.
  
 FOR EXAMPLE: PLEASE SEE THAT NOT ALL EXTERIOR LIGHTS ON
 PLANS ARE IN THE IDR> ONE FIXTURE TYPE ALONE WOULD BE
 THE S-7. THIS IS A 70W FIXTURE BASE DON THE FIXTURE
 LEGEND AND THERE ARE NO 70W FIXTURES ON THE IDR FOR
 EXTERIOR LIGHTING. ** THESE ARE NOT EXEMPT EVEN IF FOR
 THE SIGN** PLEASE SEE THE FBC CHAPTER 13 IN ORDER TO
 FALL UNDER EXCEPTIONS FOR THESE NOT TO BE
 INCLUDED.13-415.2.ABC.1.3
 ** PLEASE SEE SHEET E123CR1 DOES NOT LIST THESE
 FIXTURES AS PART OF THE CONTROLS EVEN AS THE SITE PLANS
 CALL FOR SLP-25.
  
 FOR EXAMPLE: THE FIXTURE S2 IS A 400W FIXTURE HOWEVER
 THE IDR SHOWS 800W. IT WAS ASSUMED THAT EACH POLE WHICH
 CONTAINS TWO FIXTURES WERE COUNTED AS ONE AND THIS IS
 WHY THE IDR SHOWS 800W WHICH ACCOUNTS FOR BOTH
 FIXTURES. HOWEVER AS THE IDR SHOWS A TOTAL OF 6-800W
 FIXTURES, WHAT ABOUT THE FIXTURES ON THE POLES WHICH
 INDICATES ONLY ONE S2 FIXTURE?
 THIS WAS NOT ACCOUNTED FOR IN THE IDR.
  
 FOR EXAMPLE: THE IDR INDICATES ALL * UNCOVERED PARKING
 AREAS* AND THESE ASSOCIATED LIGHT FIXTURES. WHAT ABOUT
 ALL OF THE OTHER FIXTURES WHICH ARE EXTERIOR FIXTURES
 ON THE OUTSIDE OF THE BUILDING? BASED ON THE IDR, THE
 LIGHTING PLANS AND THE FIXTURE LEGEND NONE OF THESE
 FIXTURES WERE INCLUDED.
 SEE E FIXTURE ALONE WHICH IS AN EXTERIOR WALL PACK.
  
 FOR EXAMPLE: PLEASE SEE THE INTERIOR LIGHT FIXTURES AS
 THERE ARE SEVERAL FIXTURES ON THE PLANS WHICH ARE NOT
 IN THE IDR. ONE OF THESE ALONE WOULD BE THE TYPE *A*
 FIXTURE.
  
 ****** THESE ARE SOME EXAMPLES ONLY OF ITEMS ON THE
 ELECTRICAL PLANS WHICH ARE NOT COORDINATED WITH THE IDR
 AND THE SUBMITTED ENERGY CALCULATIONS. ALL AREAS,
 TYPES, WATTAGES ETC NEED TO MEET THE MINIMUMS.
 PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND .1.3.
 *******
  
 3) NOTE: PLEASE BE MORE SPECIFIC TO THE TYPE OF
 OCCUPANCY SENSOR DEVICES. THE SYMBOL LEGEND DOES NOT
 EXPAND ON DEVICES FOR AREAS SUCH AS EGRESS PATHS WHICH
 ARE NOW ADDED TO PLANS.
 PLEASE INDICATE THE FAIL SAFE OPERATION FOR THESE
 DEVICES AS REQUIRED PER FBC 1006.1.2, NFPA-101
 7.8.1.2.2
 DEVICES IN THE FIRE PUMP ROOM, MAIN ELECTRICAL ROOM AND
 ELEVATOR EQUIPMENT ROOM ALSO NEED TO BE *FAIL SAFE ON*
 OPERATION ON OCCUPANCY SENSING DEVICES.
 PLEASE BE SURE THE SYMBOL LEGEND INDICATES THE TYPE AND
 MAXIMUM TIME.
  
 4) NOTE: PLEASE SEE THAT THE PREVIOUS REVIEW REQUESTED
 INFORMATION ON THE FIRE PUMP, CONTROLLER ETC. THE
 SUBMITTED PACKAGE DOES CONTAIN SHOP DRAWINGS/PRODUCT
 APPROVALS WHICH DO CONTAIN THE INFORMATION HOWEVER SOME
 OF THE SHEETS FOR THE FIRE PUMP ARE VERY FAINT AND NOT
 READABLE.
 PLEASE ALSO SHOW ON RISER, PLANS, SCHEDULE(S) WHERE AND
 HOW THE JOCKEY PUMP IS BEING FED. COULD NOT LOCATE THIS
 ON THE RISER ETC. SHEET E105CR1 INDICATES CIRCUITING TO
 LP2, THIS IS A LIFE SAFETY SYSTEM, PLEASE EXPLAIN WHY
 THIS IS NOT ON THE GENERATOR.
 PLEASE SEE SAME SHEET E105CR1 WHICH DRAWING NOTE #44
 INDICATES A 10HP FIRE PUMP. THIS SEEMS TO BE A
 MISPRINT?
 PLEASE BE SURE TO SEE NFPA-20 CHAPTERS 6 AND 7 AND ALSO
 SEE NFPA-70 695.6.C.1, 695.5 A, B.
  
 5) NOTE: PLEASE SEE THE SHEET E120C WHICH STILL SHOWS
 THE PREVIOUS RISER WHICH INDICATED THE NUMEROUS MAINS
 AND OTHER ITEMS FROM PREVIOUS REVIEW WHICH HAVE NOW
 BEEN REVISED.
 PLEASE COORDINATE PLANS/SHEETS.
 THE PREVIOUS NOTES GAVE SOME EXAMPLES OF COORDINATION
 NEEDED.
 EXAMPLE: PLEASE SEE E119C WHICH NOTES 3,4 AND 5
 INDICATE TWO PANELS AND A TRANSFORMER WHICH IS NOT ON
 THE PRIMARY RISER SHEET. THERE ARE NO PANEL SCHEDULES
 FOR THESE TWO PANELS ON THE SHEETS WITH THE OTHER PANEL
 SCHEDULES AND THE 112.5 KVA TRANSFORMER IS NOT LISTED
 ON EITHER OF THE TWO TRANSFORMER SCHEDULES ON SHEET
 E107CR1 YET THIS IS NOTED ON SHEET E120C. PLEASE
 EXPLAIN THE WORK SHOWN ON THESE OTHER SHEETS. ARE THESE
 PERMITTED UNDER THIS SAME PERMIT OR SCOPE OF WORK?
 NEC 230,240, 250, 215.5, 450ETC
 FBC 106.1.1 FOR CLARITY AND COORDINATION OF PLANS.
  
 6) NOTE: NEW NOTE: PLEASE EXPLAIN SUPPLEMENTAL LIGHTING
 PLAN.
 NEC 2005
 FBC 106.1.1 FOR ADDITIONAL INFORMATION/CLARITY
  
 7) NOTE: PLEASE SEE 13-415.1.ABC.1.1,.1.2, AND .1.3.
 THE OVER RIDES INDICATED ARE NOTED ON PLANS WITH NOTES
 FOR LABELS AND PHONETIC LETTERING HOWEVER PLEASE SEE
 SECTIONS NOTED. THE CODE REQUIRES THE OCCUPANT TO SEE
 ALL LIGHTING WHICH IS BEING OVER RIDDEN OR MEET THE
 EXCEPTION WHICH IS NOT ONLY DETAILED SIGNAGE FOR ALL
 AREAS BEING OVER RIDDEN BUT ALSO FOR REQUIRED *PILOT
 LIGHTS* OR * INDICATOR LIGHTS* OF SOME KIND.
  
 8) NOTE: PLEASE SEE NFPA-101 7.8 AND 7.9 OF PREVIOUS
 NOTES WITH RESPECT TO EGRESS LIGHTING LEVELS UNDER
 NORMAL AND EMERGENCY CONDITIONS.
 SOME LEVELS SHOWN ARE INDICATING LEVELS OF AVERAGE
 BELOW THE 10FT CANDLES UNDER NORMAL CONDITIONS. THIS
 LEVEL OF LIGHTING SHOULD BE FIGURED FROM THE STAIR
 AREAS ONLY AND NOT FIGURING IN OTHER AREAS OF AVERAGE.
 IF THERE ARE FIXTURES WHICH CONTRIBUTE TO THE LIGHTING
 LEVELS THEN PLEASE CALL TO GO OVER CONTRIBUTIONS. THE
 RESPONSE LETTER MENTIONS SOME STAIRS ARE NOT EGRESS
 LOCATIONS USED FOR EXITING.
 PLEASE SEE THE LIFE SAFETY CODE AS THE LIGHTING LEVEL
 DOES APPLY TO EGRESS PATHS FOR ALL NOT ONLY THE GENERAL
 PUBLIC.
 PLEASE SEE NFPA-101 7.10.8.3,.3.1 AND .3.2 WHICH
 REQUIRES SIGNAGE FOR ANY DOOR WHICH IS NOT AN EXIT DOOR
 TO BE LABELED AS SUCH. PLEASE SEE SECTIONS FOR MINIMUM
 SIZE AND WORDING.
  
 9) NOTE: MSB ON SHEET E120C STILL INDICATES GFIC
 PROTECTION. RESPONSE AND OTHER SHEETS WERE REVISED TO
 GFP FOR PROTECTION OF MAIN SWITCH GEAR EQUIPMENT.
  
 10) NOTE: PLEASE SEE THE RISER IS STILL SHOWING
 EQUIPMENT GROUNDING FROM FPL TRANSFORMER TO THE FIRST
 MEANS OF DISCONNECT WHICH IS NOT PERMITTED. THE
 RESPONSE MENTION FIRE PUMP CALCULATIONS PROVIDED AND
 THE MISINTERPRETATION OF THE CODE WITH RESPECT TO THE
 EQUIPMENT GROUNDING CONDUCTOR.
 250.24C REQUIRES THE *GROUNDED* CONDUCTOR TO BE BROUGHT
 TO THE FIRST MEANS OF DISCONNECT. AS THE CODE REQUIRES
 BINDING OF THE GROUNDING CONDUCTOR AT THE FIRST MEANS
 OF DISCONNECT IF AN *EQUIPMENT GROUNDING* CONDUCTOR IS
 IN THE SAME CONDUIT THIS WOULD CREATE OBJECTIONABLE
 CURRENTS PER 250.6.
 ** PLEASE CALL TO GO OVER AS THERE MUST BE A LOSS IN
 COMMUNICATION.
 ** RESPONSE ALSO MENTIONS THE PLANS/RISER WAS REVISED
 HOWEVER THE PLANS/RISER STILL INDICATES THE SAME.
  
 11) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 REQUIRED DEDICATED CIRCUITS FOR ELEVATOR EQUIPMENT
 ROOMS. 645.23,22,24.
 RESPONSE MENTIONS THE PLANS AND PANEL SCHEDULES HAVE
 BEEN REVISED HOWEVER PLEASE SEE SHEET E105CR1. BASED ON
 PLANS RECEPTACLES FED FROM RP2-35 ARE NOT MEETING THIS
 REQUIREMENT.
  
 12) NOTE: NEW NOTE: PLEASE PLACE NOTE ON PLANS FOR THE
 *COMMUNICATION ROOM*. AS THIS IS NOT AN IT ROOM BY
 DEFINITION IN NEC 645.2 PLEASE PLACE NOTE ON PLANS
 WHICH STATES * NO WIRING METHODS FROM NEC 645
 PERMITTED*
  
 13) NOTE: NOW THAT THE PLANS INDICATE THE GENERATOR
 LOCATED OUTSIDE PLEASE SEE NFPA-110 CHAPTER 7 FOR THE
 INSTALLATION REQUIREMENTS OF OUTDOOR UNITS. PLEASE
 INDICATE THE ELEVATION MEETING THE SLOSH CHARTS/100
 YEAR FLOOD. 7.3
  
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  