| 2008-11-06 12:22:30 | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1-29. ADDRESSED. |
| | |
| | 30. ADDRESSED. |
| | |
| | 31C. PAGE 4 OF THE CALCULATIONS, OTHER SHEETS, PLANS, |
| | REFER TO 2004 FLORIDA STATE BUILDING CODE; PLEASE |
| | REVISE TO GOVERNING CODE WHICH IS FLORIDA BUILDING CODE |
| | 2004 WITH 2007 REVISIONS/SUPPLEMENTS. |
| | |
| | 2ND REVIEW, PLANS AND CALCS STILL STATE 2004 FLORIDA |
| | STATE BUILDING CODE; THIS SHOULD STATE FLORIDA BUILDING |
| | CODE OR FBC 2004 (WITH 2007 REVISIONS/SUPPLEMENTS). |
| | |
| | E. ALL SIGNED AND SEALED SHEETS ARE TO INCLUDE ALL |
| | INFORMATION REQUIRED BY FAC61G15-23.002. |
| | |
| | 2ND REVIEW, A NUMBER WAS INCLUDED BUT THIS NUMBER WAS |
| | ISSUED TO VP CONSOLIDATED HOLDINGS, INC. THE COMPANY ON |
| | THE PLANS IS VP BUILDINGS, INC. I WAS UNABLE TO FIND A |
| | DBA, AND HAVE CONTACTED FBPE TO DETERMINE WHETHER OR |
| | NOT THIS IS ACCEPTABLE. ALSO, VP CONSOLIDATED HOLDINGS, |
| | INC. HAVE FILED A WITHDRAWAL STATING THAT THEY WILL NO |
| | LONGER DO BUSINESS IN FLORIDA. HAS ADDITIONAL PAPERWORK |
| | BEEN FILED WHICH I AM UNABLE TO LOCATE ON THE INTERNET? |
| | COMPLIANCE WITH FS471.023(1) IS NOT CLEAR. |
| | HTTP://WWW.SUNBIZ.ORG/PDF/15259987.PDF |
| | |
| | 32?39. ADDRESSED. |
| | |
| | 40. (INFORMATIONAL) THE 3 RING BINDER ENTITLED |
| | TECHNICAL SPECIFICATIONS WILL BE INCLUDED WITH THE |
| | RECORD SET WITH THE PROVISO IN ACCORDANCE WITH FBC2004 |
| | AND PLAN. NO ACTION REQUIRED. |
| | |
| | 41-43. ADDRESSED. |
| | |
| | 44. SEE FBC TABLE 1016.1, CORRIDORS 203 AND 205 FROM |
| | VISITOR'S GALLERY TO STAIRS TO HAVE 1 HOUR FIRE |
| | RESISTIVE RATING AND THEREFORE DOORS 203 1, 204 1, 205 |
| | 1, 206 1, 200 1, TO BE RATED IN ACCORDANCE WITH |
| | FBC715.3. |
| | |
| | 2ND REVIEW, AS DISCUSSED WITH ENGINEER, THIS ITEM WILL |
| | BE ADDRESSED IN RESUBMITTAL. NOTE THAT SOME DOORS FROM |
| | FIRST REVIEW WERE REMOVED, SO THERE IS ONLY ONE |
| | CORRIDOR FROM MEZZANINE LEVEL. AS DISCUSSED, THE |
| | CORRIDOR STARTS AT THE DOOR (MEANS OF EGRESS STAIR |
| | HALLWAY TO VIEWING GALLERY) AND TERMINATES AT THE EXIT, |
| | GROUND FLOOR (CORRIDOR MUST TERMINATE AT AN EXIT, WHICH |
| | IN THIS CASE IS THE EXIT DISCHARGE), SO ALTHOUGH THIS |
| | IS NOT A RATED EXIT STAIR, THE STAIR IS CONTAINED IN A |
| | 1 HOUR CORRIDOR. PLEASE CONTACT ME IF YOU WISH TO |
| | DISCUSS. |
| | |
| | 45-54. ADDRESSED. |
| | |
| | 55. FBC13-101.1, ENERGY CALCS REQUIRED FOR BOTH THE |
| | MAIN BUILDING AND FOR THE SCALE HOUSE. |
| | |
| | 2ND REVIEW, ENERGY CALCS SUBMITTED. FOR THE MAIN |
| | BUILDING, 2 DOORS ARE SHOWN. ISN'T THE WALL BETWEEN THE |
| | ADMIN AREA AND PROCESSING TO BE TREATED AS A WALL, |
| | INCLUDED IN THE INPUT DATA REPORT, AND THE DOORS NOTED? |
| | I WAS UNABLE TO LOCATE MEZZANINE WINDOWS IN THE INPUT |
| | DATA REPORT. THE SLAB IS NOTED AS 6.38 R VALUE; PLEASE |
| | CLARIFY. THE ROOF ON THE ENERGY CALC IS SHOWN AS 32.8 R |
| | VALUE, PLAN (SEE DETAIL 9 A110CR1) SPECIFIES R19 BATT. |
| | IF THE PEMB ROOF INCLUDES INSULATION, PLEASE PROVIDE |
| | THIS INFORMATION ON THE PLAN. NOTE THAT THE TYPED NAME |
| | AND LICENSE NUMBER OF THE ARCHITECT FOR CERTIFICATION |
| | BY THE ARCHITECT IS ACCEPTABLE ON THE ENERGY CALC IN |
| | LIEU OF SIGNATURE IF ALL INFORMATION IS INCLUDED ON THE |
| | PLAN FBC13-103.1.1.1. PLEASE CONFIRM INPUT DATA |
| | REQUIREMENTS AND REVISE AS NECESSARY. THIS LIST IS NOT |
| | BE COMPREHENSIVE; PLEASE CHECK ALL. |
| | |
| | 56-58. ADDRESSED. |
| | |
| | 59. SEE FBC1016.4, AIR MOVEMENT IN CORRIDORS. PLEASE |
| | REMOVE SUPPLY, RETURN, EXHAUST, RELIEF OR VENTILATION |
| | AIR DUCTS FROM EXIT ACCESS CORRIDORS, SEE OTHER |
| | COMMENTS. PLEASE NOTE THAT THERE ARE TWO HALLS IN THE |
| | MEZZANINE WHICH SERVE AS CORRIDORS. |
| | |
| | 2ND REVIEW, ONE DOOR WAS REMOVED, SO ONLY ONE CORRIDOR |
| | SERVING THE MEZZANINE REMAINS. PLEASE REVISE PLANS IN |
| | ACCORDANCE WITH FBC1016.4, SEE ALSO OTHER COMMENTS |
| | REGARDING 1 HOUR FIRE RATING REQUIRED. |
| | |
| | 60-61. ADDRESSED. |
| | |
| | 62. A114C, SPECIFY GUARD PICKET SPACING FBC1012. |
| | |
| | A114 WAS REVISED TO SPECIFY 4IN, BUT THIS IS TO RESIST |
| | A 4IN OBJECT (REQUIRES SPACING LESS THAN 4IN). THIS CAN |
| | BE A REDLINE ITEM IF REQUESTED. |
| | |
| | 63. ADDRESSED. |
| | |
| | 64. SEE 3 A007C, THE HANDRAIL IS NOT CONTINUOUS. A106C |
| | HANDRAIL EXTENSIONS AT BOTTOM IS NOT SHOWN. PLEASE |
| | PROVIDE DETAILS AND CORRELATE A SHEETS. |
| | |
| | 2ND REVIEW, THE ELEVATION ON A106C DOES NOT SHOW THE |
| | EXTENSION REQUIRED, FBC11-4.9.4(2). AT THE BOTTOM, THE |
| | HANDRAIL SHALL CONTINUE TO SLOPE FOR THE DISTANCE OF |
| | WIDTH OF ONE TREAD FROM THE BOTTOM RISER, THE REMAINDER |
| | OF THE EXTENSION WILL BE HORIZONTAL, FBC FIGURE 19(D). |
| | SEE ALSO DETAIL 1 113, A A007 (BOTTOM). THE EXTENSIONS |
| | ARE SHOWN CORRECTLY IN OTHER DETAILS. PLEASE CHECK ALL. |
| | |
| | 65-72. ADDRESSED. |
| | |
| | 73. SHOW LOCATION OF STROBES, FBC11-4.28.1. |
| | |
| | 2ND REVIEW, PLEASE ADD TO BATHROOM 108, TRUCKER?S |
| | BATHROOM. PLEASE CONFIRM THAT STROBES ARE SHOWN IN ALL |
| | LOCATIONS REQUIRED. |
| | |
| | 74-76. ADDRESSED. |
| | |
| | 77. PROVIDE A SPECIFICATION FOR ATTACHMENT OF THE |
| | BACKING FOR THE GRAB BARS (A111C) TO SHOW COMPLIANCE |
| | WITH FBC1607.7.1.1, FBC11-4.26.3. DETAIL STATES SCREWED |
| | TO STUD BUT DOES NOT SPECIFY SIZE OF SCREWS OR DISTANCE |
| | APART, DOES NOT SPECIFY A WIDTH FOR THE 22G SHEET METAL |
| | BACKING. |
| | |
| | 2ND REVIEW, SPECIFICATION NOT PROVIDED. THIS CAN BE A |
| | PROVISO ITEM; PROVIDE SHOPS BEFORE INSTALLATION. THIS |
| | WILL BE REDLINED TO INCLUDE CONCENTRATED LOAD |
| | REQUIREMENT OF 250 PLF 1607.7.2. |
| | |
| | 78-79. ADDRESSED. |
| | |
| | 80. PLEASE SHOW COMPLIANCE WITH FBC910, SMOKE AND HEAT |
| | VENTS. PROVIDE CALCULATIONS ON THE PLAN AND SHOW |
| | COMPLIANCE WITH ALL REQUIREMENTS. |
| | |
| | THE REQUEST FOR CONSIDERATION UNDER ALTERNATE MATERIALS |
| | AND METHODS HAS BEEN FORWARDED TO ROBERT BROWN FOR |
| | REVIEW. |
| | |
| | 81-85. ADDRESSED. |
| | |
| | NEW COMMENTS (NEW SUBMITTALS) ? PLEASE NOTE THAT |
| | SUBMITTALS ARE NOT REQUIRED AT THIS TIME; THEY CAN BE |
| | SUBMITTED PRIOR TO INSTALLATION: |
| | |
| | 86. **THIS SUBMITTAL CAN BE A PROVISO ITEM (SUBMIT |
| | BEFORE INSTALLATION)** |
| | ASSOCIATED ENGINEERING INCORPORATED IS TO HAVE A |
| | CERTIFICATE OF AUTHORIZATION, FS471 (WBCM SUBMITTAL |
| | #7). "AUTH # PENDING" WAS WRITTEN ON THE SHEETS |
| | PREPARED BY RONALD T. FOSS, P.E. FOR THE SORT |
| | ENCLOSURES, BUT THIS COMPANY NAME CANNOT BE USED UNTIL |
| | THE NUMBER IS ISSUED. THE WEBSITE DOES NOT INDICATE |
| | THAT AN APPLICATION IS PENDING. ARE THESE SHEETS |
| | REQUIRED AT THIS TIME? CAN THEY BE SUBMITTED AFTER A |
| | COFA HAS BEEN OBTAINED? A SET HAS BEEN RETAINED. PLEASE |
| | INFORM MR. FOSS OF THE REQUIREMENT TO OBTAIN THIS |
| | CERTIFICATE AND PLEASE HAVE HIM SEND AN EMAIL |
| | CONFIRMING HIS UNDERSTANDING. |
| | |
| | 87. **THIS SUBMITTAL CAN BE A PROVISO ITEM (SUBMIT |
| | BEFORE INSTALLATION)** |
| | THE STRUCTURAL CALCULATIONS EQUIPMENT TIE-DOWN AND |
| | CONNECTIONS TO ROOF STRUCTURE (WBCM SUBMITTAL #12) DOES |
| | NOT INCLUDE A TITLE BLOCK, FAC61G15-23.002. |
| | |
| | 88. **THIS SUBMITTAL CAN BE A PROVISO ITEM (SUBMIT |
| | BEFORE INSTALLATION)** |
| | WBCM SUBMITTAL #8, CALCULATIONS, PLEASE ADDRESS: |
| | |
| | A. ASCE7-05 REFERENCED; FBC2004 REQUIRES ASCE7-02. THIS |
| | CAN BE DONE WITH A LETTER OR CAN BE A PROVISO ITEM. |
| | |
| | B. SEE PAGE 22, EXPOSURE B USED WITH AN IMPORTANCE |
| | FACTOR OF .77. IF ACCEPTABLE TO THE DESIGNER OF RECORD, |
| | THE REDUCED IMPORTANCE FACTOR CAN BE USED BUT PROVIDE |
| | JUSTIFICATION FOR USE OF EXPOSURE B. THIS JOB APPEARS |
| | TO HAVE EXPOSURE C CONDITIONS, FBC1609.4. |
| | |
| | C. CALCS AND PLANS DO NOT NEED TO BE REVISED, BUT |
| | PLEASE NOTE THAT GOVERNING CODE IS FBC2004 WITH 2007 |
| | REVISIONS/SUPPLEMENTS. CALCS REFER TO 2005 AND 2006 |
| | REVISIONS AND SUPPLEMENTS, PLANS STATE COMPLIANCE WITH |
| | INTERNATIONAL BUILDING CODE 2003. FOR FUTURE |
| | SUBMITTALS, PLEASE REVISE. |
| | |
| | D. PAGE 21 NOTE STATES "LATERAL IMPACT DOES NOT ALLOW |
| | 1/3 STRESS INCREASE AS ALLOWED FOR ASD WIND LOAD |
| | ANALYSIS" PLEASE PROVIDE MORE INFORMATION REGARDING |
| | STRESS INCREASE USED AND SEE FBC1605.3.1.1 AND CLARIFY |
| | USE OF STRESS INCREASE. |
| | |
| | |