Plan Review Notes
Plan Review Notes For Permit 08070320
Permit Number 08070320
Review Stop E
Sequence Number 14
Notes
Date Text
2009-07-16 09:56:02 
  
 ** DENIED **
  
 SUBMISSION OF THE SELECTIVE COORDINATION STUDY.
  
 ** THE FOLLOWING COMMENTS ARE BASED ON THE SELECTIVE
 COORDINATION STUDY AND NEW COMMENTS DERIVED DURING
 REVIEW. A CALL WAS MADE TO GIPE AND ASSOCIATES AND
 SPOKE TO MICHAEL PURTELL.
  
 ** IN THE NOTES BELOW THE SELECTIVE COORDINATION STUDY
 WILL BE NOTED AS SCS.
  
 1) NOTE: NEW COMMENT: PLEASE SEE 700.9(B). PLEASE SEE
 NEC 2005 HANDBOOK COMMENTARY FOR WIRING OF SYSTEMS.
 PLEASE EXPLAIN HOW OPTIONAL STAND-BY LOADS SUCH AS
 CEILING FANS, SCALES AND OTHER GENERAL LOADS MAY BE
 PART OF THE LIFE SAFETY/ EMERGENCY SYSTEM. THIS WAS ON
 PREVIOUS PLANS HOWEVER WAS MISSED BY REVIEWER.
 STAND-BY LOADS MAY BE FED FROM SEPARATE FEED ON
 GENERATOR WITH SEPARATE TRANSFER SWITCH OR REMOVE ALL
 LOADS FROM EMERGENCY PANELS.
 IF ELP-1 WAS A * SWITCHBOARD * THEN THERE COULD BE A
 SEPARATE BRANCH FEED TO A STAND-BY ATS WHICH WOULD THEN
 FEED TERP-1.
  
 2) NOTE: PLEASE COORDINATE THE SCS WITH THE PLANS.
 PLEASE SEE THE SCS RISER AS THIS INDICATES ONLY ONE SET
 OF FEEDERS TO ATS-2 WHERE THE PLANS ON RECORD INDICATES
 2 SETS OF PARALLEL 3/0.
  
 3) NOTE: PLEASE EXPLAIN THE SCS RISER WHICH SEEMS TO
 INDICATE 100HP AND 50HP FOR FIRE PUMP.
  
 4) NOTE: PLEASE COORDINATE THE BREAKER ON THE GENERATOR
 FOR ATS-2E WHICH SHOWS 250A ON SCS RISER AND 200AMP ON
 PLANS.
  
 5) NOTE: ALL OCP DEVICES ON THE GENERATOR SHALL BE PART
 OF THE STUDY. PLEASE KNOW BASED ON THE 60AMP BREAKER ON
 ELP-1 THIS WOULD ALSO BE ON STUDY. ALTHOUGH PLEASE SEE
 COMMENT #1 ABOVE AS THIS DOES AFFECT THE RISER AS IT
 STANDS.
  
  
 240.12, 701.18, 700.27
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  